scada-points.csv led with a scada_tag column of PS_* names derived from
the PLC register map - PS_STN_WET_WELL_LEVEL and the like. CI Server never
adopted them. They named nothing that exists, nothing in this repo read
them, and read as if authoritative they have already caused a real defect
in a downstream project.
Replaced with ci-server-points.csv, the as-built delivery from the CI
Server side (copied from yau-plant-assistant, not re-derived). It is keyed
on the CI Server item, with the station and point name beside it:
ci_item,ci_station,ci_point,description,poll_group,...
gen_scada_points.py now reproduces that file byte-identically, taking the
names from the LEAF table in gen_ciserver_qli.py so the CSV and the .qli
cannot disagree. tag_for() is gone. Verified: the CSV and all three .qli
regenerate unchanged, and all six displays still build.
The four poll groups keep their PS_ names - PS_STATUS_BITS, PS_PUBLISHED,
PS_SETPOINTS, PS_SIM_CONTROL. Those are live configuration, and are the
only legitimate PS_ names.
modbus_points/README.md gains a 'four namespaces' section - instrument tag,
PLC address, CI Server point, CI Server item - since confusing them is what
produced the placeholder column in the first place.
Also settles the historian drift left open in the previous commit. The
live export is the authority: the server runs WRPS_ONE_SEC at 5 SECONDS,
not 1, and WRPS_THIRTY_SEC at 30 seconds rather than a 60 second
WRPS_ONE_MIN. Code assuming 60 s was wrong by twelvefold. Recorded in
historian/README.md with a caution never to hardcode a sample interval.
Every .qli in the delivery was byte-identical to ours - only the CSV
differed.