Adds what the folder was missing for someone picking it up cold.
as-built/ the STruC++ output copied out of the live container - the C++
the PLC is actually executing, plus program.st and the Modbus
buffer config. The running image was made with docker commit
and exists in no registry, so this is the only other copy of
the compiled form.
Verified while copying: the deployed program.st matches
build/wrps.st generated from src/. Identical POU structure,
ZERO differences in non-declaration lines. src/ is genuinely
canonical and the running PLC agrees with it.
VERSIONS.md every version read from the running system, not from
documentation: runtime v4.1.10, STruC++ 0.6.2, Editor
4.2.11, Debian 12, g++ 12.2, pymodbus 3.11.2, CI
Server R1.03. Plus which plugins are enabled -
ethercat is on for no reason - and a v3-vs-v4 table,
since most OpenPLC guidance online is for v3 and the
%MW HR1024 change silently produces wrong data.
GETTING-STARTED.md three questions answered in a page: how to modify the
program, how to stand up a new PLC container from
scratch, how to move this one. Includes the compose
file, the Editor steps that are not generated and are
always missed, and a symptom-to-document table.