Corrected in README.md, CLAUDE.md, 02-environment/README.md and 03-plc/VERSIONS.md. The @VERSION 1.03.00 header inside the .qli files is the quickload FILE FORMAT version, not the CI Server release. Left alone. This also sharpens a caveat that was previously stated wrongly. The EQP-E-DUP_ITEM rejection - an item import fails if two items share an IO_ADDRESS - was observed on 2026-08-14 on the DEVELOPMENT machine, which ran R1.03. Production runs R1.05, where it has never been tested. The design still works around it by publishing level and speed in % only, and that workaround costs nothing; but anyone wanting a second unit for a measurement should try it on R1.05 before assuming they need a second PLC register to carry it. |
||
|---|---|---|
| .. | ||
| ciserver-backup-2026-08 | ||
| hmi | ||
| modbus_points | ||
| QUICKLOAD.md | ||
| README.md | ||
04-scada — the CI Server side
Everything that lives on yau-poc-cicore1 (10.0.0.21): the tag database that
reads the PLC, and the displays an operator looks at.
Two halves, two deployment mechanisms
This is the distinction to get straight before anything else. Conflating them is what makes this folder confusing.
| Configuration | Displays | |
|---|---|---|
| What | sections, items, Modbus points, historian groups | the .xml screens |
| Lives in | modbus_points/ |
hmi/ |
| Deployed by | dssqld — the quickload utility |
file copy into the displays directory |
| Generated from | 03-plc/register-map.csv |
build_display.py |
| Binds by | NSID / ID_NUMBER |
itemId — healed by name on import |
dssqld is for configuration only. It has nothing to do with displays. See
QUICKLOAD.md.
The chain
Everything derives from the PLC. The PLC side leads, always.
03-plc/src/*.st
│ build.py
▼
03-plc/register-map.csv the contract - 69 points
│ gen_scada_points.py
▼
modbus_points/ci-server-points.csv the SCADA view - 49 points, poll groups, units
│ gen_ciserver_qli.py
▼
modbus_points/*.qli 6 sections · 49 Modbus points · 49 items
│ dssqld -i
▼
CI SERVER ◄──── Modbus TCP ──── the PLC on 10.0.0.17:502
▲
│ file copy
│
hmi/out/*.xml 6 displays
▲ build_display.py
│
hmi/item-ids.csv 49 itemIds, MEASURED from CI Server
Nothing in this chain is hand-edited. Change a register in 03-plc/build.py,
rebuild, then re-run both generators. If CI Server needs a field the generators do
not emit, it goes in the generator.
One exception: the historian has no generator. See
modbus_points/historian/README.md.
Layout
QUICKLOAD.md dssqld - export and import configuration
modbus_points/ the tag database (named for the protocol: CI Server
configures other protocols differently)
historian/ collection groups and item bindings - HAND-MADE
hmi/ displays, and the generator that builds them
ciserver-backup-2026-08/ ⚠️ outdated exports, evidence only - never import
⚠️ "The values on my display are not updating"
First, and before any other investigation:
Open the display in CI Server's Editor Module and validate it. Then report what happened.
Validation resolves every connection by name and repairs the file. It fixes the overwhelmingly common cause in seconds — an itemId that no longer matches, which happens every time the items are re-imported. CI Server recreates items on import rather than updating them in place, so every id in every display moves at once, and every value goes dead together.
That simultaneity is the signature: everything dying at the same moment is ids, not communications.
Only once validation has been ruled out, work down these:
| Symptom | Cause |
|---|---|
| Some values dead, others fine | Those items were never measured. Harvest the ids — see hmi/DEPLOY.md. |
| Every analogue reads 0, always | You are polling %IW/%IX (FC04/FC02). Those are field inputs; in the simulation build nothing writes them. Live values are in the %QW block (FC03). |
| Values frozen at a plausible number | Communications stopped. Is the container up? Is a program running? The runtime opens its Modbus slave only while a program runs — a stopped program means port 502 refuses. |
| Values moving but wrong | Addressing. %MW starts at holding register 1024, not 0. A wrong-by-1024 read succeeds and returns plausible nonsense. |
| Alarm word goes negative | %QW17 must be read unsigned. Bit 15 does not fit a signed INT. |
What this repo cannot tell you: whether CI Server's own poll groups are
actually scanning. That lives on cicore1. If the PLC polls correctly with
05-tests/verify_modbus.py and the ids are good, that is the remaining place to
look.
Status
| Points and items | Imported and reading live PLC values (2026-08-14), verified against a direct Modbus read |
| Generators | Verified reproducible 2026-09-02 — ci-server-points.csv and all three .qli regenerate byte-identically |
| Displays | Six built; build_display.py runs clean |
| Historian | 3 groups, 49 bindings — hand-made, and the live rates differ from these files. The server runs WRPS_ONE_SEC at 5 s and WRPS_THIRTY_SEC at 30 s. See modbus_points/historian/README.md. |
| CI Server state | ⚠️ Unverified. No access to cicore1 during this audit. Everything here is what the repo believes, not what the server holds. |
Two things left for you
- Alarm and trend limits. Every item imports with alarming off and limits at 0. Which points alarm, at what threshold and priority, is engineering judgement about the plant — not something to derive from a register map.
- Re-export the configuration from
cicore1and diff it against this folder. Until then,ciserver-backup-2026-08/is the only record of the server's own state, and it is known to disagree withmodbus_points/historian/.