item_name,tag_id,exclusion_reason,section_path,section,attribute,section_description,description,eng_unit,value_format,conv_type,has_sign,phys_low,phys_high,eng_gain,raw_to_eng,his_group,scan_interval_seconds,life_time,ci_station,ci_point,poll_group,iec_address,modbus_kind,modbus_address,data_type,point_time_zone AID.WRPS.PU301.RUN_CMD,AID.WRPS.PU301.RUN_CMD,,AID.WRPS.PU301,PU301,RUN_CMD,Pump PU-301,Run command,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU301_RUN_CMD,PS_STATUS_BITS,%QX0.0,coil,0,Boolean,Date+time GMT AID.WRPS.PU302.RUN_CMD,AID.WRPS.PU302.RUN_CMD,,AID.WRPS.PU302,PU302,RUN_CMD,Pump PU-302,Run command,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU302_RUN_CMD,PS_STATUS_BITS,%QX0.1,coil,1,Boolean,Date+time GMT AID.WRPS.PU303.RUN_CMD,AID.WRPS.PU303.RUN_CMD,,AID.WRPS.PU303,PU303,RUN_CMD,Pump PU-303,Run command,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU303_RUN_CMD,PS_STATUS_BITS,%QX0.2,coil,2,Boolean,Date+time GMT AID.WRPS.PU301.RUNNING,AID.WRPS.PU301.RUNNING,,AID.WRPS.PU301,PU301,RUNNING,Pump PU-301,Running,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU301_RUNNING,PS_STATUS_BITS,%QX0.3,coil,3,Boolean,Date+time GMT AID.WRPS.PU302.RUNNING,AID.WRPS.PU302.RUNNING,,AID.WRPS.PU302,PU302,RUNNING,Pump PU-302,Running,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU302_RUNNING,PS_STATUS_BITS,%QX0.4,coil,4,Boolean,Date+time GMT AID.WRPS.PU303.RUNNING,AID.WRPS.PU303.RUNNING,,AID.WRPS.PU303,PU303,RUNNING,Pump PU-303,Running,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU303_RUNNING,PS_STATUS_BITS,%QX0.5,coil,5,Boolean,Date+time GMT AID.WRPS.PU301.AVAILABLE,AID.WRPS.PU301.AVAILABLE,,AID.WRPS.PU301,PU301,AVAILABLE,Pump PU-301,Available,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU301_AVAILABLE,PS_STATUS_BITS,%QX0.6,coil,6,Boolean,Date+time GMT AID.WRPS.PU302.AVAILABLE,AID.WRPS.PU302.AVAILABLE,,AID.WRPS.PU302,PU302,AVAILABLE,Pump PU-302,Available,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU302_AVAILABLE,PS_STATUS_BITS,%QX0.7,coil,7,Boolean,Date+time GMT AID.WRPS.PU303.AVAILABLE,AID.WRPS.PU303.AVAILABLE,,AID.WRPS.PU303,PU303,AVAILABLE,Pump PU-303,Available,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU303_AVAILABLE,PS_STATUS_BITS,%QX1.0,coil,8,Boolean,Date+time GMT AID.WRPS.STN.IN_AUTO,AID.WRPS.STN.IN_AUTO,,AID.WRPS.STN,STN,IN_AUTO,Waterloo Road PS - station wide measurements and status,Station in auto,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,STN_IN_AUTO,PS_STATUS_BITS,%QX1.1,coil,9,Boolean,Date+time GMT AID.WRPS.STN.HIGH_LEVEL,AID.WRPS.STN.HIGH_LEVEL,,AID.WRPS.STN,STN,HIGH_LEVEL,Waterloo Road PS - station wide measurements and status,High level alarm,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,STN_HIGH_LEVEL,PS_STATUS_BITS,%QX1.2,coil,10,Boolean,Date+time GMT AID.WRPS.STN.SPILL_ACTIVE,AID.WRPS.STN.SPILL_ACTIVE,,AID.WRPS.STN,STN,SPILL_ACTIVE,Waterloo Road PS - station wide measurements and status,Spill active,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,STN_SPILL_ACTIVE,PS_STATUS_BITS,%QX1.3,coil,11,Boolean,Date+time GMT AID.WRPS.PU301.TRIPPED,AID.WRPS.PU301.TRIPPED,,AID.WRPS.PU301,PU301,TRIPPED,Pump PU-301,Tripped,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU301_TRIPPED,PS_STATUS_BITS,%QX1.4,coil,12,Boolean,Date+time GMT AID.WRPS.PU302.TRIPPED,AID.WRPS.PU302.TRIPPED,,AID.WRPS.PU302,PU302,TRIPPED,Pump PU-302,Tripped,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU302_TRIPPED,PS_STATUS_BITS,%QX1.5,coil,13,Boolean,Date+time GMT AID.WRPS.PU303.TRIPPED,AID.WRPS.PU303.TRIPPED,,AID.WRPS.PU303,PU303,TRIPPED,Pump PU-303,Tripped,,,Digital,0,0,100,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU303_TRIPPED,PS_STATUS_BITS,%QX1.6,coil,14,Boolean,Date+time GMT AID.WRPS.STN.LEVEL,AID.WRPS.STN.LEVEL,,AID.WRPS.STN,STN,LEVEL,Waterloo Road PS - station wide measurements and status,Wet well level,%,999.9,Linear,1,-546,546,0.016666666666666666,value / 60,WRPS_ONE_SEC,5,1 weeks,WRPS_PLC,STN_LEVEL,PS_PUBLISHED,%QW0,holding,0,Signed 16-bit,Date+time GMT AID.WRPS.STN.INFLOW,AID.WRPS.STN.INFLOW,,AID.WRPS.STN,STN,INFLOW,Waterloo Road PS - station wide measurements and status,Inflow,m3/h,9999.9,Linear,1,-11796.48,11796.12,0.36,value * 0.36,WRPS_ONE_SEC,5,1 weeks,WRPS_PLC,STN_INFLOW,PS_PUBLISHED,%QW1,holding,1,Signed 16-bit,Date+time GMT AID.WRPS.STN.DISCHARGE,AID.WRPS.STN.DISCHARGE,,AID.WRPS.STN,STN,DISCHARGE,Waterloo Road PS - station wide measurements and status,Total discharge flow,m3/h,9999.9,Linear,1,-11796.48,11796.12,0.36,value * 0.36,WRPS_ONE_SEC,5,1 weeks,WRPS_PLC,STN_DISCHARGE,PS_PUBLISHED,%QW2,holding,2,Signed 16-bit,Date+time GMT AID.WRPS.STN.PUMPS_RUNNING,AID.WRPS.STN.PUMPS_RUNNING,,AID.WRPS.STN,STN,PUMPS_RUNNING,Waterloo Road PS - station wide measurements and status,Pumps running,count,9,Linear,1,-32768,32767,1.0,value,WRPS_THIRTY_SEC,30,1 weeks,WRPS_PLC,STN_PUMPS_RUNNING,PS_PUBLISHED,%QW3,holding,3,Signed 16-bit,Date+time GMT AID.WRPS.STN.SPEED,AID.WRPS.STN.SPEED,,AID.WRPS.STN,STN,SPEED,Waterloo Road PS - station wide measurements and status,Common drive speed,%,999.9,Linear,1,-6553,6553,0.2,value * 0.2,WRPS_ONE_SEC,5,1 weeks,WRPS_PLC,STN_SPEED,PS_PUBLISHED,%QW4,holding,4,Signed 16-bit,Date+time GMT AID.WRPS.STN.TIME_TO_SPILL,AID.WRPS.STN.TIME_TO_SPILL,,AID.WRPS.STN,STN,TIME_TO_SPILL,Waterloo Road PS - station wide measurements and status,Time to spill weir (32767 = drawing down),s,99999,Linear,1,-32768,32767,1.0,value,WRPS_THIRTY_SEC,30,1 weeks,WRPS_PLC,STN_TIME_TO_SPILL,PS_PUBLISHED,%QW5,holding,5,Signed 16-bit,Date+time GMT AID.WRPS.STN.TIME_TO_LSHH,AID.WRPS.STN.TIME_TO_LSHH,,AID.WRPS.STN,STN,TIME_TO_LSHH,Waterloo Road PS - station wide measurements and status,Time to LSHH (32767 = drawing down),s,99999,Linear,1,-32768,32767,1.0,value,WRPS_THIRTY_SEC,30,1 weeks,WRPS_PLC,STN_TIME_TO_LSHH,PS_PUBLISHED,%QW6,holding,6,Signed 16-bit,Date+time GMT AID.WRPS.STN.NET_ACCUM,AID.WRPS.STN.NET_ACCUM,,AID.WRPS.STN,STN,NET_ACCUM,Waterloo Road PS - station wide measurements and status,Net accumulation (signed),m3/h,9999.9,Linear,1,-11796.48,11796.12,0.36,value * 0.36,WRPS_ONE_SEC,5,1 weeks,WRPS_PLC,STN_NET_ACCUM,PS_PUBLISHED,%QW7,holding,7,Signed 16-bit,Date+time GMT AID.WRPS.PU301.RUN_HOURS,AID.WRPS.PU301.RUN_HOURS,,AID.WRPS.PU301,PU301,RUN_HOURS,Pump PU-301,Run hours,h,99999,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU301_RUN_HOURS,PS_PUBLISHED,%QW8,holding,8,Signed 16-bit,Date+time GMT AID.WRPS.PU302.RUN_HOURS,AID.WRPS.PU302.RUN_HOURS,,AID.WRPS.PU302,PU302,RUN_HOURS,Pump PU-302,Run hours,h,99999,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU302_RUN_HOURS,PS_PUBLISHED,%QW9,holding,9,Signed 16-bit,Date+time GMT AID.WRPS.PU303.RUN_HOURS,AID.WRPS.PU303.RUN_HOURS,,AID.WRPS.PU303,PU303,RUN_HOURS,Pump PU-303,Run hours,h,99999,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU303_RUN_HOURS,PS_PUBLISHED,%QW10,holding,10,Signed 16-bit,Date+time GMT AID.WRPS.STN.VOL_TO_SPILL,AID.WRPS.STN.VOL_TO_SPILL,,AID.WRPS.STN,STN,VOL_TO_SPILL,Waterloo Road PS - station wide measurements and status,Volume remaining to spill,m3,9999,Linear,1,-32768,32767,1.0,value,WRPS_THIRTY_SEC,30,1 weeks,WRPS_PLC,STN_VOL_TO_SPILL,PS_PUBLISHED,%QW11,holding,11,Signed 16-bit,Date+time GMT AID.WRPS.STN.STATE,AID.WRPS.STN.STATE,,AID.WRPS.STN,STN,STATE,Waterloo Road PS - station wide measurements and status,Station state (enum 3.1),,9,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,STN_STATE,PS_PUBLISHED,%QW12,holding,12,Signed 16-bit,Date+time GMT AID.WRPS.PU301.STATE,AID.WRPS.PU301.STATE,,AID.WRPS.PU301,PU301,STATE,Pump PU-301,Pump state (enum 3.2),,9,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU301_STATE,PS_PUBLISHED,%QW13,holding,13,Signed 16-bit,Date+time GMT AID.WRPS.PU302.STATE,AID.WRPS.PU302.STATE,,AID.WRPS.PU302,PU302,STATE,Pump PU-302,Pump state (enum 3.2),,9,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU302_STATE,PS_PUBLISHED,%QW14,holding,14,Signed 16-bit,Date+time GMT AID.WRPS.PU303.STATE,AID.WRPS.PU303.STATE,,AID.WRPS.PU303,PU303,STATE,Pump PU-303,Pump state (enum 3.2),,9,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,PU303_STATE,PS_PUBLISHED,%QW15,holding,15,Signed 16-bit,Date+time GMT AID.WRPS.STN.DUTY_PUMP,AID.WRPS.STN.DUTY_PUMP,,AID.WRPS.STN,STN,DUTY_PUMP,Waterloo Road PS - station wide measurements and status,"Current duty pump (0 = none, 1-3)",,9,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,STN_DUTY_PUMP,PS_PUBLISHED,%QW16,holding,16,Signed 16-bit,Date+time GMT AID.WRPS.STN.ALARM_WORD,AID.WRPS.STN.ALARM_WORD,,AID.WRPS.STN,STN,ALARM_WORD,Waterloo Road PS - station wide measurements and status,Alarm bitmask (section 6) - READ AS UNSIGNED,,99999,Linear,0,0,65535,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,STN_ALARM_WORD,PS_PUBLISHED,%QW17,holding,17,Unsigned 16-bit,Date+time GMT AID.WRPS.STN.CMD_ACK,AID.WRPS.STN.CMD_ACK,,AID.WRPS.STN,STN,CMD_ACK,Waterloo Road PS - station wide measurements and status,Command acknowledge (echoes %MW1),,99,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,STN_CMD_ACK,PS_PUBLISHED,%QW20,holding,20,Signed 16-bit,Date+time GMT AID.WRPS.SP.MODE,AID.WRPS.SP.MODE,,AID.WRPS.SP,SP,MODE,Operator setpoints and commands,"Station mode: 1 = auto, 2 = off",,9,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,SP_MODE,PS_SETPOINTS,%MW0,holding,1024,Signed 16-bit,Date+time GMT AID.WRPS.SP.CMD_WORD,AID.WRPS.SP.CMD_WORD,,AID.WRPS.SP,SP,CMD_WORD,Operator setpoints and commands,Command word (section 3.3),,99,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,SP_CMD_WORD,PS_SETPOINTS,%MW1,holding,1025,Signed 16-bit,Date+time GMT AID.WRPS.SP.CMD_PARAM,AID.WRPS.SP.CMD_PARAM,,AID.WRPS.SP,SP,CMD_PARAM,Operator setpoints and commands,Command parameter (pump number),,9,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,SP_CMD_PARAM,PS_SETPOINTS,%MW2,holding,1026,Signed 16-bit,Date+time GMT AID.WRPS.SP.LEVEL_SP,AID.WRPS.SP.LEVEL_SP,,AID.WRPS.SP,SP,LEVEL_SP,Operator setpoints and commands,Level control setpoint,%,999.9,Linear,1,-546,546,0.016666666666666666,value / 60,WRPS_EVENT,,1 weeks,WRPS_PLC,SP_LEVEL_SP,PS_SETPOINTS,%MW3,holding,1027,Signed 16-bit,Date+time GMT AID.WRPS.SP.START_DUTY,AID.WRPS.SP.START_DUTY,,AID.WRPS.SP,SP,START_DUTY,Operator setpoints and commands,Start duty level,%,999.9,Linear,1,-546,546,0.016666666666666666,value / 60,WRPS_EVENT,,1 weeks,WRPS_PLC,SP_START_DUTY,PS_SETPOINTS,%MW4,holding,1028,Signed 16-bit,Date+time GMT AID.WRPS.SP.START_P2,AID.WRPS.SP.START_P2,,AID.WRPS.SP,SP,START_P2,Operator setpoints and commands,Start pump 2 level,%,999.9,Linear,1,-546,546,0.016666666666666666,value / 60,WRPS_EVENT,,1 weeks,WRPS_PLC,SP_START_P2,PS_SETPOINTS,%MW5,holding,1029,Signed 16-bit,Date+time GMT AID.WRPS.SP.START_P3,AID.WRPS.SP.START_P3,,AID.WRPS.SP,SP,START_P3,Operator setpoints and commands,Start pump 3 level,%,999.9,Linear,1,-546,546,0.016666666666666666,value / 60,WRPS_EVENT,,1 weeks,WRPS_PLC,SP_START_P3,PS_SETPOINTS,%MW6,holding,1030,Signed 16-bit,Date+time GMT AID.WRPS.SP.STOP_ALL,AID.WRPS.SP.STOP_ALL,,AID.WRPS.SP,SP,STOP_ALL,Operator setpoints and commands,Stop all level,%,999.9,Linear,1,-546,546,0.016666666666666666,value / 60,WRPS_EVENT,,1 weeks,WRPS_PLC,SP_STOP_ALL,PS_SETPOINTS,%MW7,holding,1031,Signed 16-bit,Date+time GMT AID.WRPS.SP.HIGH_ALARM,AID.WRPS.SP.HIGH_ALARM,,AID.WRPS.SP,SP,HIGH_ALARM,Operator setpoints and commands,High level alarm,%,999.9,Linear,1,-546,546,0.016666666666666666,value / 60,WRPS_EVENT,,1 weeks,WRPS_PLC,SP_HIGH_ALARM,PS_SETPOINTS,%MW8,holding,1032,Signed 16-bit,Date+time GMT AID.WRPS.SP.MIN_SPEED,AID.WRPS.SP.MIN_SPEED,,AID.WRPS.SP,SP,MIN_SPEED,Operator setpoints and commands,Minimum drive speed,%,999.9,Linear,1,-6553,6553,0.2,value * 0.2,WRPS_EVENT,,1 weeks,WRPS_PLC,SP_MIN_SPEED,PS_SETPOINTS,%MW9,holding,1033,Signed 16-bit,Date+time GMT AID.WRPS.SP.SERVICE_HRS,AID.WRPS.SP.SERVICE_HRS,,AID.WRPS.SP,SP,SERVICE_HRS,Operator setpoints and commands,Service interval,h,99999,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,SP_SERVICE_HRS,PS_SETPOINTS,%MW10,holding,1034,Signed 16-bit,Date+time GMT AID.WRPS.SIM.INFLOW,,"simulation control, not a plant measurement - answering from it would report the scenario driver as though it were the real inflow",AID.WRPS.SIM,SIM,INFLOW,Simulation control - simulation build only,manual inflow (mode 0),m3/h,9999.9,Linear,1,-11796.48,11796.12,0.36,value * 0.36,WRPS_EVENT,,1 weeks,WRPS_PLC,SIM_INFLOW,PS_SIM_CONTROL,%MW20,holding,1044,Signed 16-bit,Date+time GMT AID.WRPS.SIM.SCENARIO,,"simulation control, not a plant measurement",AID.WRPS.SIM,SIM,SCENARIO,Simulation control - simulation build only,scenario 0=man 1=diurnal 2=wet 3=ref,,9,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,SIM_SCENARIO,PS_SIM_CONTROL,%MW21,holding,1045,Signed 16-bit,Date+time GMT AID.WRPS.SIM.RESET,,"simulation control, not a plant measurement",AID.WRPS.SIM,SIM,RESET,Simulation control - simulation build only,"write 1 to reset scenario, self-clearing",,9,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,SIM_RESET,PS_SIM_CONTROL,%MW22,holding,1046,Signed 16-bit,Date+time GMT AID.WRPS.SIM.TIME_SCALE,,simulation control - a non-unity time scale means wall-clock durations in the history are compressed and must not be quoted as real durations,AID.WRPS.SIM,SIM,TIME_SCALE,Simulation control - simulation build only,time scale 1-120,x,999,Linear,1,-32768,32767,1.0,value,WRPS_EVENT,,1 weeks,WRPS_PLC,SIM_TIME_SCALE,PS_SIM_CONTROL,%MW23,holding,1047,Signed 16-bit,Date+time GMT