# DEMO DOCUMENT — NOT A CONTROLLED DOCUMENT — DO NOT USE ON PLANT Document number: WRPS-DEMO-002 Title: Alarm Rationalisation Record — Wet Well Level Signal Revision: 0 Effective: 2026-01-01 ## 1. Scope A fabricated alarm rationalisation record for the wet well WW-101 level signal at the Waterloo Road Pump Station, written to give the Reference branch of the plant assistant something to retrieve and cite during a no-LLM demonstration. ## 2. LEVEL_SIGNAL_FAULT **Meaning.** The level signal fault alarm indicates that the PLC has rejected the wet well level measurement from LIT-101. In this fabricated record the rejection is described as occurring when the signal is out of range, frozen for longer than the configured period, or of bad quality. **Consequence.** With no trusted level measurement the station cannot modulate pump duty on level. This fabricated record states that control falls back to the LSHH-102 high high level switch as the only remaining level protection. **Priority.** Priority 1 in this fabricated record. The stated reasoning is that losing the level measurement on a wet well that can spill removes the station's ability to see a spill developing. **Operator response.** Not stated here. The response belongs in a procedure, and this is a rationalisation record. ## 3. HIGH_LEVEL **Meaning.** A fabricated entry stating that the wet well level has reached the high level alarm setpoint and that the station has not yet drawn the level down. **Priority.** Priority 2 in this fabricated record.