yau-plant-assistant/db/seed/scada-source/wrps_section_df.qli
Claude 24afc51672 Take delivery of the corrected CI Server configuration
The point list handed over in August named the points PS_STN_WET_WELL_LEVEL
and the like. Those were never CI Server names. They came from
gen_scada_points.py on the PLC side, which describes its own output as "a
starting point for CI Server configuration, not a CI Server import file",
and the CI Server generator ignored them entirely - it names points from
its own address-keyed table. The names appear in no .qli export, and
nowhere else in the WRPS project at all.

This is the corrected delivery. ci-server-points.csv is keyed on the CI
Server ITEM each point feeds, with the Modbus station and the point name
beside it, so all four namespaces are visible in one row:

  LIT-101              instrument tag
  %QW0                 PLC symbol and address
  WRPS_PLC:STN_LEVEL   CI Server point - station, colon, point name
  AID.WRPS.STN.LEVEL   CI Server item - what the historian is keyed on

The 49 rows were joined onto the .qli exports by function code and Modbus
address: 49 matched, 0 unmatched. The item and point names are read from
the exports, not invented here.

The six .qli files come too, unchanged. gen_historian_items.py needs them,
and until now they existed only on one laptop behind a --wrps path - so
the one file the rules say must never be hand-edited could be regenerated
by exactly one person. 84 KB buys the team that back.

These are uncontrolled documents: no revision, no effective date, no
approval. The README says so, says how to ask for a fresh set, and records
the two things that bite - that PS_ survives legitimately as four poll
group names, and that his_group.qli and the live export disagree about the
sample rates, with the live one winning.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
2026-09-01 19:00:20 +10:00

40 lines
944 B
Text

@LANGUAGE
ENGLISH
@VERSION
1.03.00
!==================================================================================================================================
@FIELDS
NAME,SECTION_PATH,SECTION_NAME,BLOCKED,PARENT_BLOCKED
ALARM_INHIBIT,PARENT_ALARM_INHIBIT,OPC_VISIBLE,PARENT_OPC_VISIBLE,NSID,PARENT_NSID
DESCRIPTION,CREATED_BY
@SECTION_DF
"AID.WRPS.STN","AID.WRPS","STN",0,0,\
0,0,0,0,171,170,\
"Waterloo Road PS - station wide measurements and status","unknown"
"AID.WRPS.PU301","AID.WRPS","PU301",0,0,\
0,0,0,0,172,170,\
"Pump PU-301","unknown"
"AID.WRPS.PU302","AID.WRPS","PU302",0,0,\
0,0,0,0,173,170,\
"Pump PU-302","unknown"
"AID.WRPS.PU303","AID.WRPS","PU303",0,0,\
0,0,0,0,174,170,\
"Pump PU-303","unknown"
"AID.WRPS.SP","AID.WRPS","SP",0,0,\
0,0,0,0,175,170,\
"Operator setpoints and commands","unknown"
"AID.WRPS.SIM","AID.WRPS","SIM",0,0,\
0,0,0,0,176,170,\
"Simulation control - simulation build only","unknown"