Both were found hand-verifying the measures on fixtures, and both are left
unfixed deliberately: fixing either now means guessing at what imh contains,
and a guess baked into the seed data or the models is harder to find later than
an open finding. Flagged at Phase 4, in the README, in the model files at the
point of use, and as eval cases that fail until they are settled.
(a) The wet well level tag does not join, and fails as "no records found".
History is keyed PS_STN_WET_WELL_LEVEL, which process_values.yml hardcodes
in seconds_above_high_level_alarm and seconds_above_lshh. tags.csv carries
that name only as an ALIAS of LIT-101, so public.tags has no row with that
tag_id and all 43,201 level rows - a third of the history, on the most
important tag at this station - are unreachable from a tag-level lookup.
Resolve "wet well" -> WW-101 -> LIT-101 -> filter history on LIT-101 ->
zero rows -> "no records found".
That is the failure mode worth being loudest about: it is the safety
behaviour, produced by a key mismatch rather than by an absence of data,
and indistinguishable from the real thing on screen. Filtering by
equipment_id works, so whether a level question fails depends on which path
the agent takes.
The two flow tags use the opposite, self-consistent convention -
PS_STN_INFLOW is a row in its own right and FIT-201 is marked NOT
HISTORISED - so applying that to level is the likely fix. It still waits
for the register map and for imh to say what CI Server historises the point
as. Seed, hardcoded model names and 002_fixtures.sql change together.
(b) alarms.first_alarm and last_alarm return UTC, not SITE_TIMEZONE.
Cube converts time dimensions to the query timezone; a min/max measure over
a timestamp comes back unconverted. The Sydney day bucket for 2026-08-01
returns 2026-07-31T20:00:35 - the right instant, ten hours and one calendar
day out, beside a bucket label that IS in site time.
This breaks "convert to SITE_TIMEZONE exactly once, in Cube", and the fix
has to stay in Cube - the API compensating with timezone arithmetic is the
thing that rule exists to prevent. Which fix is right depends on whether
imh stores UTC or local, which is Phase 4 task 4. Until then these two must
not be quoted to an operator as a clock time.
Phase 4's gate gains an item for each. Everything else verified in this pass -
alarms, operations, the equipment join, alias resolution and the Sydney/UTC day
boundaries - matched hand-written SQL exactly.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>