Issue review: STATION_STAT, UMH tools, CLASS_RESET_COMMAND, intdskmon (ISS-007/021/022/028/030)
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
parent
b267fbe38b
commit
19b4113b37
5 changed files with 26 additions and 16 deletions
|
|
@ -53,7 +53,9 @@ The Engineering Module also resets classes (class properties); not practiced.
|
|||
accepted with 0 errors but nothing happens.
|
||||
- `dssqld -m` on `OBJECT_DF` with `RESET` 1: refused with `OPC-E-OBJ_RSTREQ, The class needs to
|
||||
be reset first`.
|
||||
- `CLASS_RESET_COMMAND` (system-wide reset used by the Engineering Module) was not tried.
|
||||
- `CLASS_RESET_COMMAND` (system-wide reset, fields `RESET`, `GENERATE_REPORT`, `PROGRESS`,
|
||||
`OBJECTS_RESET` …): the dataset allows only read and update, `dssqld -e` returns no record,
|
||||
`dssqld -m` gives *Not found*, `dssqld -i` is refused (`DSS-E-NO_AUTH`). Verified 2026-10-01.
|
||||
|
||||
## 3. Changing prompts or signals
|
||||
|
||||
|
|
|
|||
|
|
@ -2,7 +2,7 @@
|
|||
task: BUS Service utilities - process checks, stopping single processes, message tools, adaptive queues
|
||||
version: R1.03
|
||||
source: IM 36K10L30-01EN §1, §5, §6, §10, §14; checked on the test system 2026-10-01
|
||||
status: verified for durwfp and the read-only setup file checks; umhman, umhtestprog, umhmsg fail on the test system (ISS-030)
|
||||
status: verified (durwfp, setup file checks, umhman, umhmsg, umhtestprog)
|
||||
---
|
||||
|
||||
# BUS Service utilities
|
||||
|
|
@ -28,10 +28,15 @@ then kills after 10 s. `*` wildcards stop many processes (`-p alm\*`). Never `du
|
|||
- Message log: `%TLS_LOG_PATH%\umhlog.log` (`--> From: <PROCESS> (<node>) on <time>`, then
|
||||
`FAC-S-CODE, text` lines). `UMH Message Text Error: Message number <hex> (…)` = the text
|
||||
could not be formatted (e.g. `%` in a PRINT text, ISS-025).
|
||||
- `umhman` (hex code → text), `umhtestprog` (test the log path) and `umhmsg <hex> [<var>
|
||||
<value>]` (log a message from a script) **did not work on the test system**: `umhman`
|
||||
crashes with redirected input (run it interactively), `umhtestprog` crashes, `umhmsg` stops
|
||||
with `license expired` on the unlicensed node (ISS-030).
|
||||
- `umhman` (hex code → text): answers can be piped, e.g. `printf '8010008
|
||||
|
||||
' | umhman` →
|
||||
`DUR-W-NO_MSG_FND, No selected message found`; parameters in the text stay empty.
|
||||
- `umhmsg <hex> [<var> <value>]…` logs that message from a script: it prints nothing; the
|
||||
message appears in `umhlog.log` from process `UMHMSG_<pid>`.
|
||||
- `umhtestprog` runs its self-test (`TESTING UMH MESSAGES`, `TESTING ILLEGAL CODES`).
|
||||
- On an **unlicensed** node these tools crash or stop with `license expired` once the licence
|
||||
time is nearly used up, while `dssqld`/`itmval` still work; restart CI Server (ISS-030).
|
||||
|
||||
## Adaptive queues (read-only check)
|
||||
|
||||
|
|
|
|||
|
|
@ -25,7 +25,7 @@ development system (see "Test system" in `progress.md`); they do not exist on ot
|
|||
| ISS-004 | 2026-09-30 | ITEM (`itmval`) | `itmval -g -a <1..5>` returns `ITM-E-WRONG_ATT` on `AID.WRPS.*` items, so reading limits is unproven. | closed | Closed 2026-09-30 (confirmed by user). On `CI-Eng-Sample.TANK1.LEVEL` (limits set) `-a 1..5` returned deadband 0, low 20, high 80, low-low 10, high-high 90. The error only occurs on items without limits. | `.claude/skills/system-management/tasks/read-write-item.md` (limits section); `knowledge/progress.md` row "Read an item with `itmval -g`" |
|
||||
| ISS-005 | 2026-09-30 | DATABASE (`dssqld`) | Loading `04_item_his_df.qli` straight after creating the storage group gave 2 errors once; three other runs were clean. Error text not captured. | open | Added a 5 s pause in `load.cmd`. If it happens again, capture `04_item_his_df.qlo`. | `examples/CI-Eng-Sample/load.cmd`; `.claude/skills/system-management/tasks/load-remove-records.md` |
|
||||
| ISS-006 | 2026-09-30 | HISTORY (`ithloahis`) | Samples dated before the start of the current storage unit were not stored (no error shown); samples after it were. Also, a new storage group stored nothing until CI Server was restarted. | closed | Closed 2026-10-01 (confirmed by user). Confirm with History Management (IM 36K10L20) in phase 9: how to load into older units, and whether a restart is really required. 2026-09-30 (phase 5): IM 36K10L35 §1.3/§5 explains the first part: event storage picks the unit by time stamp, never older than 60 units, and within the storage process's `gap_time` (ITHEEX/ITHEIX 2880 min) and, for EVENT/ITEM, `max_sample_delay` (ITHEIX 14400 min); older data needs earlier unit files (`hisdbg`, `hisrecover`, `isfrename`), `ithrecover <group> -p` and a restart. Practice in phase 9. 2026-10-01 (phase 9, verified): (1) restart **is** required — `CIENG_SCAN10S` / `CIENG_AGG` loaded at 11:54 and `CIENG_EVENT` reloaded at 11:32 stored nothing until the 12:00 restart, then stored at once. (2) The first unit of a new Event/Item or Aggregation group is dated 2 days back (= `gap_time` 2880 min), but samples loaded into that pre-restart unit (11:50, 30-Sep) were still dropped; samples inside the active unit (12:02) and inside a unit closed by a forced rollover (12:03 into unit 3,1) were stored. So: samples older than the first unit opened since the restart are dropped silently. Loading older data would need `hisrecover` / `isfrename` / `ithrecover` (not practiced). Proposed close: documented in `load-history.md` and skill `history-management`. | `.claude/skills/system-management/tasks/load-history.md`; `examples/CI-Eng-Sample/README.md`; `knowledge/manuals/IM36K10J10-01EN.md` command-line tools |
|
||||
| ISS-007 | 2026-09-30 | INTEGRATION (monitoring) | `intdskmon` wrote 61.9 for a C: drive that is 61.9 % used / 38.1 % free, although the manual says it monitors the disk free space rate. `intspawn` did nothing when the command path was ~130 characters; a short path worked (limit unknown). | open | Confirm the disk value meaning and the path limit. | `.claude/skills/system-management/tasks/monitoring-processes.md`; `knowledge/manuals/IM36K10J10-01EN.md` §4.1.6; `examples/CI-Eng-Sample/monitoring/` |
|
||||
| ISS-007 | 2026-09-30 | INTEGRATION (monitoring) | `intdskmon` wrote 61.9 for a C: drive that is 61.9 % used / 38.1 % free, although the manual says it monitors the disk free space rate. `intspawn` did nothing when the command path was ~130 characters; a short path worked (limit unknown). | open | Disk value: the test showed **used** % (61.9 on a 61.9 % used disk), and the task file says so; installed behaviour is the reference. `intspawn` path limit: not measured (needs admin edits of `tls\sup\<name>.sup` and restarts for each length); guidance kept: put the command in a `.cmd` with a short path (other CI Server tools cut paths at 79 characters, ISS-020). Ready to close. | `.claude/skills/system-management/tasks/monitoring-processes.md`; `knowledge/manuals/IM36K10J10-01EN.md` §4.1.6; `examples/CI-Eng-Sample/monitoring/` |
|
||||
| ISS-008 | 2026-09-30 | ACCESS (ODBC server `odbsrv`) | `ci_start.log` on the test system shows `CppServerAPI::Run() failed: InitializeSslCtx(): SSL_CTX_use_certificate_chain_file() failed.` right after ACCESS Service starts. Which component and certificate is not known. | closed | Closed 2026-10-01 (confirmed by user): cause known, ODBC server left as is (not licensed/used on the test system). Identify in phase 7. 2026-10-01 (phase 7): cause found. The message comes from the ODBC server `odbsrv` (ACCESS Service, Simba): `odbsrv.sup` has `USESSL = YES` and `access_start.cmd` points it at `%TLS_ROOT_PATH%\tls\pki\odbsrv\SampleServerCertificate.pem` / `SampleServerKey.pem`, but that folder does not exist and no sample certificate is installed. `odbsrv` exits right after start (`DUR-W-REM_PROC, Process ODBSRV exited unexpectedly`), port 1583 does not listen. Fix (admin, only if ODBC is licensed and wanted): install a certificate + key there, or set `USESSL = NO`. Not applied. Close when the user confirms. | `.claude/skills/installation-security/tasks/setup-check.md`; `knowledge/manuals/IM36K10L45-01EN.md` §1 (done); `.claude/skills/data-access/tasks/access-checks.md` (done) |
|
||||
| ISS-009 | 2026-09-30 | Security Guide | DCOM port range printed as 20500–20550 in the firewall table but "2500–20550" in the OPC configuration table. Taken as a typo for 20500–20550. | closed | Confirm on a system with IT security applied. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K01C30-01EN.md` §4 |
|
||||
|
||||
|
|
@ -40,16 +40,16 @@ development system (see "Test system" in `progress.md`); they do not exist on ot
|
|||
| ISS-018 | 2026-09-30 | Authorization (`dssana.sup`) | IM 36K10C10 §2.2 says the *No* login method applies the user profile `FT_NO_LOGIN`; the installed `dssana.sup` names `CI_NO_LOGIN` (and `CI_NO_LOGIN_OPCUAS` for anonymous OPC UA) as the no-login profile. `USER_DF` on the test system has `CI_NO_LOGIN_OPCUAS` but no `CI_NO_LOGIN`. | open | Installed software is the reference: use `CI_NO_LOGIN`. Still to check: behaviour of a *No* login when that user does not exist (manual: no profile applied). Covered again in phase 13 (IM 36K10J40). | `knowledge/manuals/IM36K10C10-01EN.md` §2 |
|
||||
| ISS-019 | 2026-09-30 | ITEM (string items) | Maximum string item length differs by source: IM 36K10C10 §3.3.4 says default 80, max 100; the Tutorial summary says up to 168 without audit; the data dictionary (`dssqld -f`) gives `ITEM_DF.STRING_LENGTH` range 1–200, default 80. | closed | Tested 2026-09-30 on CI-Eng-Sample (`dssqld -i`, `itmval -p/-g`, non-elevated): `STRING_LENGTH` 100, 168 and 200 load with or without `AUDIT_INFO`; 201 fails with `DSS-E-VAL_RANGE`. An item holds **length − 1** characters: a 99-character value in a length-100 item is stored with status 9 NORMAL; longer values are cut to length − 1 with status **12 OVERRANGED** (100 → 99, 200 → 199, 201 → 199). So the data dictionary (1–200) is right. Test items removed. Closed 2026-09-30 (confirmed by user). | `knowledge/manuals/IM36K10C10-01EN.md` §3; `knowledge/manuals/IM36K10G10-01EN.md` (items); `.claude/skills/item-engineering/SKILL.md` |
|
||||
| ISS-020 | 2026-09-30 | DATABASE (`dssqld`) | `dssqld -i "<long absolute path>\user.qli"` failed with `CRL-E-ENOENT` / `DSSQ-E-QLD_FILOPN`: the path in the message was cut after 79 characters (`…\73b3559a-12.`). A relative file name from the same folder works. Similar to the `intspawn` path limit (ISS-007). | closed | Tested 2026-10-01: the limit is **79 characters** for the whole path. An input file of 80–81 characters gives `DSSQ-E-Q_QLIEXT` (the name is cut, e.g. `….ql`), 85+ gives `CRL-E-ENOENT`. An `-e` output path of 80+ characters gives **no error**, but no file appears under the given name. Documented: keep paths ≤ 79 characters, or `cd` to the folder and use relative names. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/system-management/tasks/load-remove-records.md`; `.claude/skills/system-management/tasks/export-dataset.md` |
|
||||
| ISS-021 | 2026-09-30 | EQUIPMENT (`eqpiostat`) | IM 36K10L40 §2 says `eqpiostat` stores hourly I/O statistics per station line in "history group STATION_STAT". On the test system `eqpiostat` runs (started by `equipment_start.cmd` on the host node) and `STATION_STAT` is a dataset, but `dssqld -e` returned 0 records, also with filters on `TIME_STAMP` and `STATION` (AID Modbus stations, which send requests). | open | Check whether records appear after a full hour with a communicating station, or whether the dataset is read another way (e.g. Engineering Module, report). | `knowledge/manuals/IM36K10L40-01EN.md` §2 |
|
||||
| ISS-022 | 2026-09-30 | ITEM (`itmval -f`) | `itmval -f <file> vs -n CI-Eng-Sample.TANK1.LEVEL` (IM 36K10L36 §1.4, write a restore command) crashes with a segmentation fault (bash) / access violation 0xC0000005 (PowerShell) and writes no file; also with `-l`. The manual's space-separated form `-n <inst> <unit> <tag>` is rejected with `FSL-E-NARG_ALL`. `itmval -g`/`-p` work. | open | Workaround: build restore lines from `itmval -g` output. Report to Yokogawa support if needed. Retested 2026-10-01 with the documented syntax `itmval -f <file> <opts> -n <item>` (`<opts>` = letters from `vsqo`, e.g. `vs`): still a segmentation fault from bash and from `cmd`, in a short and a long folder, relative or absolute file name; `cmd` leaves an **empty** file. Treat `-f` as broken on R1.03.00. | `knowledge/manuals/IM36K10L36-01EN.md` §3; `.claude/skills/system-management/tasks/read-write-item.md` |
|
||||
| ISS-021 | 2026-09-30 | EQUIPMENT (`eqpiostat`) | IM 36K10L40 §2 says `eqpiostat` stores hourly I/O statistics per station line in "history group STATION_STAT". On the test system `eqpiostat` runs (started by `equipment_start.cmd` on the host node) and `STATION_STAT` is a dataset, but `dssqld -e` returned 0 records, also with filters on `TIME_STAMP` and `STATION` (AID Modbus stations, which send requests). | open | Answered 2026-10-01: with `CIENG_PLC` communicating (Modbus slave mirror running), `STATION_STAT` holds one record per hour per station line (10 records since 30-09-2026 18:00; e.g. `TIMESPAN` 831 s, `SENDS`/`GOODANS` 1560/1560, no errors). The earlier empty export had no communicating station. Ready to close. | `knowledge/manuals/IM36K10L40-01EN.md` §2 |
|
||||
| ISS-022 | 2026-09-30 | ITEM (`itmval -f`) | `itmval -f <file> vs -n CI-Eng-Sample.TANK1.LEVEL` (IM 36K10L36 §1.4, write a restore command) crashes with a segmentation fault (bash) / access violation 0xC0000005 (PowerShell) and writes no file; also with `-l`. The manual's space-separated form `-n <inst> <unit> <tag>` is rejected with `FSL-E-NARG_ALL`. `itmval -g`/`-p` work. | open | Workaround: build restore lines from `itmval -g` output. Report to Yokogawa support if needed. Retested 2026-10-01 with the documented syntax `itmval -f <file> <opts> -n <item>` (`<opts>` = letters from `vsqo`, e.g. `vs`): still a segmentation fault from bash and from `cmd`, in a short and a long folder, relative or absolute file name; `cmd` leaves an **empty** file. Also crashes right after a CI Server restart (so not the licence-time effect of ISS-030). Treat `-f` as broken on R1.03.00; report to Yokogawa support if needed. | `knowledge/manuals/IM36K10L36-01EN.md` §3; `.claude/skills/system-management/tasks/read-write-item.md` |
|
||||
| ISS-023 | 2026-09-30 | ITEM / ITH (manual vs install) | Installed ITEM Service differs from IM 36K10L35/L36: `item_start.cmd` starts `itheix` (EVENT/ITEM storage, not described), aggregation `ithsag`/`ithrag`, two instances of each retrieve process, and `itmtim 100 1000 1 200 1` (five arguments, three documented); `itm.sup` item pool is 650000 KB (manual default 50000) and has `not_regained` (not described); `itheix.sup` has `max_sample_delay`, `max_samples_queued`, `max_open_files`. | closed | Closed 2026-09-30 (user decision: the installed software is the reference). Summaries describe the installed values. | `knowledge/manuals/IM36K10L35-01EN.md`; `knowledge/manuals/IM36K10L36-01EN.md` |
|
||||
| ISS-024 | 2026-09-30 | EQUIPMENT (Modbus slave) | IM 36K10L41 §3.7 says `EQPMDCSLVTCP` waits for "MODBUS RTU requests via TCP/IP" and the CI Server master should use "MODBUS RTU via TCP/IP". A Modbus master station with `PROTOCOL = RTU` to `eqpmdcslvtcp` (port 5020) got no answer (`EQP-E-TCPRCVTMO`, 4 requests, 0 valid); with `Open Modbus/TCP` it worked at once. | closed | Closed 2026-09-30 (user decision: installed software is the reference). Use `Open Modbus/TCP` towards `eqpmdcslvtcp`. | `knowledge/manuals/IM36K10L41-01EN.md` §3.7; `.claude/skills/equipment/tasks/modbus-station.md` |
|
||||
| ISS-025 | 2026-09-30 | PROCESS (PRINT) | A Traditional `PRINT "… 80 %, volume ", VOLUME;` logged `OPC-I-INFO, UMH Message Text Error: Message number 083A001B (… level reached 80 )`: the text is cut at the `%` and the rest is lost. Without `%` the full text is logged. | closed | Tested 2026-10-01 with a temporary class (removed): `PRINT "… 50 %% …"` logs `50 % …` correctly; `\%` and `%c` with 37 both give the *Message Text Error* and cut the text. Documented: write `%%`. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10P10-01EN.md` §4; `.claude/skills/class-object-engineering/tasks/traditional-class.md` |
|
||||
| ISS-026 | 2026-09-30 | PROCESS (`opc.sup`) | Installed PROCESS setup differs from IM 36K10L10 §2: `IMMED-EVENTS = NO` (manual: default on); `FLOW-CONTROL = 30,60` (manual 300/360 s); four executors `OPCEXE1`–`4` with fixed priority ranges (manual examples `OPCEXE01`…) and `opcdbg` still defaults to `OPCEXE`; keyword `VARTAB-SIZE` (manual `VARITAB-SIZE`); hidden keywords `FLDSEP`, `IGNEXI` not described; `ALARM-ITEMS` not set; class source file `opc_clssrc.dat` (manual `opc_clasrc.dat`); `opcini.sup` (licence line) not described. | closed | Installed software is the reference (standing user decision); summary written from the installed files. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10L10-01EN.md` §2, §5 |
|
||||
| ISS-027 | 2026-09-30 | PROCESS (`opcdbg`) | IM 36K10L10 §4 says the `opcdbg` *Dump classes/objects* files can be read by `dssqld`. The files have no `@LANGUAGE`/`@FIELDS`/`@<dataset>` headers (`NAME,"desc",prio` + source lines prefixed `- `); `dssqld -i` on the object dump gave `DSS-E-UNK_DS_NM, Unknown data set name`. | open | Use `dssqld -e CLASS_DF` / `OBJECT_DF` for transfers. Maybe an old tool reads the dump format; not found. | `knowledge/manuals/IM36K10L10-01EN.md` §4; `.claude/skills/class-object-engineering/tasks/opcdbg-checks.md` |
|
||||
| ISS-028 | 2026-09-30 | PROCESS (class reset) | After recompiling a class with objects (`RESET_REQUIRED` 1), `dssqld -m` with `CLASS_DF` `RESET` = 1 (also with `RESET_NODE` = host node name) is accepted with 0 errors but does not reset; `OBJECT_DF` `RESET` = 1 is refused (`OPC-E-OBJ_RSTREQ`). `opcdbg` Classes → 8 *Reset class* works; it asks for a reset report file, which the manual does not list. | open | Use `opcdbg`. Still to try: `CLASS_RESET_COMMAND` (system-wide) and the Engineering Module's reset. | `.claude/skills/class-object-engineering/tasks/change-reset-class.md`; `knowledge/manuals/IM36K10L10-01EN.md` §4 |
|
||||
| ISS-028 | 2026-09-30 | PROCESS (class reset) | After recompiling a class with objects (`RESET_REQUIRED` 1), `dssqld -m` with `CLASS_DF` `RESET` = 1 (also with `RESET_NODE` = host node name) is accepted with 0 errors but does not reset; `OBJECT_DF` `RESET` = 1 is refused (`OPC-E-OBJ_RSTREQ`). `opcdbg` Classes → 8 *Reset class* works; it asks for a reset report file, which the manual does not list. | open | Use `opcdbg`. 2026-10-01: `CLASS_RESET_COMMAND` cannot be driven by `dssqld` (read/update only; no record to update — *Not found*; insert `DSS-E-NO_AUTH`). Test class `CIENG_INCR` was recompiled and reset again with `opcdbg` (`RESET_REQUIRED` back to 0). Still to try: the Engineering Module's reset (user). | `.claude/skills/class-object-engineering/tasks/change-reset-class.md`; `knowledge/manuals/IM36K10L10-01EN.md` §4 |
|
||||
| ISS-029 | 2026-09-30 | PROCESS (Java) | IM 36K10P11 §10.4 says a new Java class must be reset before objects are added, otherwise the code does not take effect. A Java class inserted with `COMPILE` 1 by `dssqld` ran its first object correctly without any reset (twice, including a full sample reload). | open | Installed behaviour is the reference; keep "reset after changing a class that has objects". Check whether the Engineering Module path (compile without quick load) behaves differently. | `knowledge/manuals/IM36K10P11-01EN.md` §7; `.claude/skills/class-object-engineering/tasks/java-class.md` |
|
||||
| ISS-030 | 2026-10-01 | BUS (UMH tools) | `umhman` (hex code → text) crashes with redirected input (bash: segmentation fault 139 with CRLF input; PowerShell `Start-Process -RedirectStandardInput`: 0xC0000005); with an argument it only prompts. `umhtestprog` prints `UMH TEST UTILITY` and crashes (segmentation fault). `umhmsg 8010008` stops with `umh_panic: …umhmsg.exe, license expired` although other tools (`dssqld`, `itmval`) still worked at that time. | open | Try `umhman` interactively in a console; check `umhmsg` on a licensed system. Similar to ISS-022 (`itmval -f`). | `.claude/skills/system-management/tasks/bus-utilities.md`; `knowledge/manuals/IM36K10L30-01EN.md` §3 |
|
||||
| ISS-030 | 2026-10-01 | BUS (UMH tools) | `umhman` (hex code → text) crashes with redirected input (bash: segmentation fault 139 with CRLF input; PowerShell `Start-Process -RedirectStandardInput`: 0xC0000005); with an argument it only prompts. `umhtestprog` prints `UMH TEST UTILITY` and crashes (segmentation fault). `umhmsg 8010008` stops with `umh_panic: …umhmsg.exe, license expired` although other tools (`dssqld`, `itmval`) still worked at that time. | open | Retested 2026-10-01 right after a CI Server restart: all three work — `umhman` with piped input (bash, LF or CRLF; via `cmd <` too), `umhmsg 083A001B text "…"` writes the message to `umhlog.log` (process `UMHMSG_<pid>`, prints nothing), `umhtestprog` runs its self-test. The earlier failures came late in an unlicensed session (licence nearly expired). `itmval -f` (ISS-022) still crashes on a fresh start, so it is a separate fault. Ready to close. | `.claude/skills/system-management/tasks/bus-utilities.md`; `knowledge/manuals/IM36K10L30-01EN.md` §3 |
|
||||
| ISS-031 | 2026-10-01 | LICENCE (unlicensed node) | The unlicensed test node counts down about 1 hour of run time per CI Server start (`License time left` in `smd_<node>_LOW_smdsnp_general.log`, 3600 s → `*** license problem : 3 ***`); then `dssqld`/`itmval` stop with `license expired` and `ISF-F-LIC_PROB, DATABASE Service is not licensed`. A PC sleep pauses the count (start 17:25, ran out 09:52 next day). Restart of the CI Service resets it (verified 2026-10-01, back after ~45 s). | closed | Closed 2026-10-01 (confirmed by user): known limitation of the unlicensed test system, documented in system-check. Known limitation of the test system, documented in `system-check`. Plan tests in ≤ 1 h blocks. Close when the user confirms. | `.claude/skills/system-check/SKILL.md` §3 (done) |
|
||||
| ISS-032 | 2026-10-01 | ACCESS (OPC UA server node IDs) | IM 36K10L45 §10.3 shows CI Server node IDs (`{"nsid":"32"}`, `{"0":"Value","itnm":"ITEM1"}`) and the CI Server namespace `http://www.yokogawa.com/CI_Server/` (ns 3) but not which namespace the **entities** use. With that URI (or `urn:<host>:Yokogawa:CI_SERVER_OPC_UA_SERVER`) the client point was silently not monitored. Browsing (`OPCUAC_TAG_DF`) shows sections/items in **`urn:Yokogawa:CI_SERVER_OPC_UA_SERVER`**; with it `{"0":"Value","itnm":"<item>"}` and `{"0":"Value","nsid":"<n>"}` both work. IM 36K10E20 §2.2.6 also asks to enable `OPXUAS_USE_NAME_NODEIDS` and restart for CI client ↔ CI server; not needed on the test system. | closed | Closed 2026-10-01 (user decision: installed software is the reference). Installed software is the reference (standing user decision). Close when the user confirms. | `knowledge/manuals/IM36K10L45-01EN.md` §7 (done); `knowledge/manuals/IM36K10E20-01EN.md` §3 (done); `.claude/skills/data-access/tasks/opcua-client.md` (done) |
|
||||
| ISS-033 | 2026-10-01 | ACCESS (Engineering Module OPC UA point) | Tested by the user: the point form's *Browse path* stops at the item (`Objects/CI-Eng-Sample/TANK1/INFLOW`) and stores the item **object** `{"nsid":"548"}`; the point is not monitored (revised sampling interval 0, connected item status 13, *Last value*/*Data type* empty). Typing `{"0":"Value","itnm":"CI-Eng-Sample.TANK1.INFLOW"}` in *Node Id* fixed it (values followed at once). Browsing into an item that is OPC visible but not *Read* fails (`UncertainNotAllNodesAvailable`, `OPXC-E-BRW_NODE`). | open | Check whether the browse dialog can expand an item to `Value` (e.g. double-click); otherwise type the node ID. | `knowledge/manuals/IM36K10E20-01EN.md` §2 (done); `.claude/skills/data-access/tasks/opcua-client.md` §3 (done) |
|
||||
|
|
|
|||
|
|
@ -3,7 +3,7 @@ manual: IM 36K10L30-01EN
|
|||
title: BUS Service Engineering
|
||||
edition: 3rd Edition, Sep. 2023
|
||||
version: R1.03
|
||||
status: from docs; installed tools, setup files (dur.sup, durm_1_udp.sup, time_table.sup, fmfprt.sup, durutl.sup) and durm_start.cmd checked read-only 2026-10-01; durwfp verified; umhman, umhtestprog, umhmsg fail on the test system (ISS-030)
|
||||
status: from docs; installed tools, setup files (dur.sup, durm_1_udp.sup, time_table.sup, fmfprt.sup, durutl.sup) and durm_start.cmd checked read-only 2026-10-01; durwfp verified; umhman, umhtestprog, umhmsg verified after a fresh start (ISS-030)
|
||||
---
|
||||
|
||||
# BUS Service Engineering (R1.03)
|
||||
|
|
@ -57,9 +57,9 @@ second node; `durutl.sup` has no active lines.
|
|||
`-q <printer queue>` prints too.
|
||||
- Tools: `umhtestprog` (tests the message path), `umhmsg <hex code> [<var> <value>]…`
|
||||
(issue a message from a script), `umhman` (look up a hex code, interactive),
|
||||
`umhlogtoo` (copy of all messages to a terminal). **On the test system** `umhman` crashes
|
||||
with redirected input, `umhtestprog` crashes, and `umhmsg` ends with "license expired"
|
||||
(ISS-030).
|
||||
`umhlogtoo` (copy of all messages to a terminal). **Verified** after a fresh start: `umhman`
|
||||
with piped input, `umhmsg` (message appears in `umhlog.log`) and `umhtestprog` work; late in an
|
||||
unlicensed session they crashed or reported "license expired" (ISS-030).
|
||||
- A message shown as `UMH Message Text Error: Message number <hex> (…)` means the text could
|
||||
not be formatted (e.g. a `%` in a PRINT text, ISS-025).
|
||||
|
||||
|
|
|
|||
|
|
@ -48,7 +48,10 @@ No setup file, no parameters. On the test system `equipment_start.cmd` starts it
|
|||
automatically on the host node, and it was running. The manual calls the target a history
|
||||
group; it is the dataset **`STATION_STAT`** (fields: time stamp, station, line, time span,
|
||||
sends, good answers, bad return code, timeouts, frame errors, bad CRC, retries, line bad).
|
||||
An export returned no records on the test system (ISS-021).
|
||||
**Verified:** `dssqld -e st.qlo -d STATION_STAT` lists one record per station line per hour
|
||||
(`NAME` = `<DD-MON-YY hh:00>/<station>/<line>`), e.g. `CIENG_PLC` with `TIMESPAN` (seconds
|
||||
counted in that hour), `SENDS` and `GOODANS` 1560/1560. Only stations that actually sent requests
|
||||
appear; the first export (no communicating station) was empty (ISS-021). History type 4.
|
||||
|
||||
## 3. Debugger: `eqpdbg` (§3)
|
||||
|
||||
|
|
|
|||
Loading…
Add table