@ -0,0 +1,33 @@
@LANGUAGE
ENGLISH
@VERSION
1.03.00
! Alarm definitions used by TANK1.LEVEL (16_item_alarm_df.qli). Load before the items refer to them.
! Acknowledgement type: every alarm needs a manual acknowledgement; a return to normal is
! acknowledged automatically only if the alarm was acknowledged (same matrix as MANUAL).
! Field <from><A|N>_<to>: from state N/A1/A2/A3 with Ack/Nack, to state N/A1/A2/A3; 1 = automatic.
! Unlisted matrix fields default to 0 (manual).
@FIELDS
NAME,DESCRIPTION,EAL_ACK,NA_N,NN_N,A1A_N,A2A_N,A3A_N
@ALARM_ACK_DF
"CIENG_ACK","CI-Eng-Sample: manual ack; auto ack on return to normal if acked",0,1,1,1,1,1
! Area of interest (alarm grouping for displays and destinations)
@FIELDS
NAME,DESCRIPTION
@ALARM_AOI_DF
"CIENG_TANKS","CI-Eng-Sample tank items"
! Alarm selection area, compiled on load (COMPILE = 1). Keywords and operators need spaces.
@FIELDS
NAME,DESCRIPTION,COMPILE,EXPRESSION
@ALARM_ASA_DF
"CIENG_TANK1","Alarms of section CI-Eng-Sample.TANK1",1,\
@"
/* Alarm selection area : CIENG_TANK1 */
SECTION = "CI-Eng-Sample.TANK1""@

View file

@ -0,0 +1,13 @@
@LANGUAGE
ENGLISH
@VERSION
1.03.00
! Switch on alarming for TANK1.LEVEL (limits 10/20/80/90 come from 02_item_df.qli). Load with dssqld -m.
! Status and alarm state come from STATUS_DF: > 80 HIGH (Alarm 2, prio 2), > 90 HIGH HIGH (Alarm 3, prio 1).
@FIELDS
NAME,ALARMING,ACKN_TYPE,AOI_1
@ITEM_DF
"CI-Eng-Sample.TANK1.LEVEL",1,"CIENG_ACK","CIENG_TANKS"

View file

@ -0,0 +1,18 @@
@LANGUAGE
ENGLISH
@VERSION
1.03.00
! Remove CI-Eng-Sample alarm definitions (after the items: an acknowledgement type in use cannot be deleted)
@FIELDS
NAME
@ALARM_ASA_DF
"CIENG_TANK1"
@ALARM_AOI_DF
"CIENG_TANKS"
@ALARM_ACK_DF
"CIENG_ACK"

View file

@ -31,7 +31,7 @@ cmd /c "<repo>\examples\CI-Eng-Sample\remove.cmd"
|---|---|---|
| `CI-Eng-Sample` | Section | Top level |
| `CI-Eng-Sample.TANK1`, `.PUMP1`, `.SYSTEM` | Sections | Tank, pump, system monitoring |
| `CI-Eng-Sample.TANK1.LEVEL` | Item, Real | %, format `999.9`, limits LL 10 / L 20 / H 80 / HH 90, scale 0–100 (alarming off), stored in `CIENG_EVENT` |
| `CI-Eng-Sample.TANK1.LEVEL` | Item, Real | %, format `999.9`, limits LL 10 / L 20 / H 80 / HH 90, scale 0–100, stored in `CIENG_EVENT`; alarming on (ack type `CIENG_ACK`, area `CIENG_TANKS`; `16_item_alarm_df.qli`) |
| `CI-Eng-Sample.TANK1.INFLOW` | Item, Real | m3/h, format `9999.9`, scale 0–500, stored in `CIENG_EVENT` |
| `CI-Eng-Sample.PUMP1.RUNNING` | Item, Boolean | |
| `CI-Eng-Sample.PUMP1.MODE` | Item, Integer | 0 manual, 1 auto |
@ -67,6 +67,9 @@ cmd /c "<repo>\examples\CI-Eng-Sample\remove.cmd"
| `CIENG_UA_LINE` | OPC UA client line | Client process `OPXCIENG` (created and started by loading the line) |
| `CIENG_UA` | OPC UA station | `opc.tcp://localhost:34493`, Basic256Sha256 / SignAndEncrypt, anonymous; subscription `CIENG_SUB` (1 s); points `LEVEL`, `SRV_STATE` |
| OPC visible | Flags | Sections `CI-Eng-Sample`, `TANK1` and item `TANK1.LEVEL` are OPC visible, item read-only (`12_opc_visible_df.qli`) |
| `CIENG_ACK` | Acknowledgement type | Every alarm needs an acknowledgement; return to normal automatic only if the alarm was acknowledged (same matrix as `MANUAL`) |
| `CIENG_TANKS` | Area of interest | Label for tank items (`TANK1.LEVEL` `AOI_1`) |
| `CIENG_TANK1` | Alarm selection area | `SECTION = "CI-Eng-Sample.TANK1"`, compiled on load |
| `CIENG_VIEWER` | Authorization group | Read-only: `ITEM_READ`, `SECTION_READ`, `ALARM_CURRENT_READ`, `ALARM_CHRONO_READ`. No users are created by the sample. |
Items created by objects (`TANK1.CALC.VOLUME`, `TANK1.JFLOW.sPerMin`) and their sections are
@ -89,8 +92,10 @@ New items start with status 13 (`NOT INIT`) until a value is written.
| `09_modbus_line_df.qli`, `10_modbus_station_df.qli`, `11_item_eqp_df.qli` | Modbus line; station, scan type, points; items connected to points |
| `12_opc_visible_df.qli` | OPC visible / read flags (loaded with `dssqld -m`) |
| `13_opcua_line_df.qli`, `14_opcua_station_df.qli`, `15_item_opcua_df.qli` | OPC UA client line; station, subscription, points; connected items |
| `01b_alarm_df.qli` | Alarm definitions: acknowledgement type, area of interest, alarm selection area (`ALARM_ACK_DF`, `ALARM_AOI_DF`, `ALARM_ASA_DF`) |
| `16_item_alarm_df.qli` | Switch on alarming for `TANK1.LEVEL` (loaded with `dssqld -m`) |
| `equipment/eqpciengslv_start.cmd`, `_stop.cmd` | Start/stop the Modbus slave mirror (copy to `tls\com`) |
| `80_`…`92_remove_*.qli` | Names to delete, in reverse order |
| `76_`…`93_remove_*.qli` | Names to delete, in reverse order (alarm definitions last, `93`) |
| `load.cmd`, `remove.cmd` | Run the steps in the right order |
| `monitoring/*.sup.txt` | Setup-file lines for the monitoring processes (not applied by `load.cmd`) |
@ -126,6 +131,14 @@ exchange, done by the user (skill `data-access`, task `opcua-client.md` §4):
Then `UA.COMM_OK` = 1 and `UA.LEVEL_COPY` follows `TANK1.LEVEL`. The trust is kept when the
sample is removed and loaded again.
## Alarms (TANK1.LEVEL)
`TANK1.LEVEL` raises HIGH above 80 (Alarm 2, priority 2) and HIGH HIGH above 90 (Alarm 3,
priority 1). To try it on a test system: `itmval -p -n CI-Eng-Sample.TANK1.LEVEL -v 85`, export
`ALARM_CURRENT` (filter on `ITEM_NAME`), acknowledge with `dssqld -m` on `ALARM_CURRENT`
(`NAME`, `ACK` 1), write the level back below 80. See skill `alarm-management`, task
`item-alarming.md`.
## Monitoring processes (optional)
`monitoring/` holds the lines to add to the setup files in `%TLS_ROOT_PATH%\tls\sup\` so that
@ -137,7 +150,6 @@ testing. See the `system-management` skill, task `monitoring-processes.md`.
| Phase | Adds |
|---|---|
| 8 | Alarm settings on sample items |
| 9 | More storage groups (scan/time, aggregation) |
| 10 | A display and symbol |
| 11 | A report |

View file

@ -5,6 +5,8 @@ rem Results go to *.qlo listing files; check that Errors = 0.
rem Restart CI Server afterwards: new storage groups only start storing after a restart.
cd /d "%~dp0"
dssqld -i 01_section_df.qli -l 01_section_df.qlo
rem Alarm definitions (acknowledgement type, area of interest, alarm selection area)
dssqld -i 01b_alarm_df.qli -l 01b_alarm_df.qlo
dssqld -i 02_item_df.qli -l 02_item_df.qlo
dssqld -i 02b_sub_item_df.qli -l 02b_sub_item_df.qlo
dssqld -i 03_his_group_df.qli -l 03_his_group_df.qlo
@ -33,3 +35,5 @@ echo Waiting 10 seconds for OPC UA client OPXCIENG to start...
powershell -NoProfile -Command "Start-Sleep -Seconds 10"
dssqld -i 14_opcua_station_df.qli -l 14_opcua_station_df.qlo
dssqld -i 15_item_opcua_df.qli -l 15_item_opcua_df.qlo
rem Alarming: switch on alarms for TANK1.LEVEL (modify existing record)
dssqld -m 16_item_alarm_df.qli -l 16_item_alarm_df.qlo

View file

@ -24,4 +24,6 @@ dssqld -r 90_remove_his_group_df.qli -l 90_remove_his_group_df.qlo
dssqld -r 90b_remove_sub_item_df.qli -l 90b_remove_sub_item_df.qlo
dssqld -r 91_remove_item_df.qli -l 91_remove_item_df.qlo
dssqld -r 92_remove_section_df.qli -l 92_remove_section_df.qlo
rem Alarm definitions last: an acknowledgement type still used by an item cannot be deleted.
dssqld -r 93_remove_alarm_df.qli -l 93_remove_alarm_df.qlo
del 90a_stop_his_group_df.qli