@ -1,38 +0,0 @@
|
|||
---
|
||||
name: graphics
|
||||
description: >-
|
||||
CI Server R1.03 operator graphics: displays, symbols, layouts and HTML displays. Use when the
|
||||
user wants to create or change a display or symbol in the Edit Module (number field, text,
|
||||
alarm overview, trend, buttons, actions, parameters, connecting a component to an item),
|
||||
deploy or remove display files, export displays to HTML / Mobile Operator, open a display in a
|
||||
web browser (localhost:8080/mobileoperator), validate, search or unlock displays (jwuiutl,
|
||||
.lck files), find where displays, symbols and layouts are stored (DEPLOY folder,
|
||||
Layouts.xml), change layouts, menus, toolbars or frames, build dataset forms (*Dia.xml), or
|
||||
use the AOG library (Advanced Operating Graphics, AOG_Style, AOG symbols, faceplates). Sources
|
||||
IM 36K10C50-01EN, IM 36K10R30-01EN, IM 36K10C60-01EN.
|
||||
---
|
||||
|
||||
# Graphics: displays, symbols, layouts (R1.03)
|
||||
|
||||
Background: `knowledge/manuals/IM36K10C50-01EN.md` (Edit Module, components, sheets, symbols,
|
||||
`jwuiutl`, display file contents), `IM36K10R30-01EN.md` (folders, layouts, dataset forms, HTML
|
||||
display), `IM36K10C60-01EN.md` (AOG library).
|
||||
|
||||
Rules:
|
||||
- Drawing is done by the user in the **Edit Module** (GUI). Claude prepares the steps, checks the
|
||||
saved XML, deploys/exports/validates files and checks the HTML display in the browser.
|
||||
- Displays and layouts are shared by every operator: changing or deleting existing files only
|
||||
with the user's approval; keep a copy first (`Layouts-original.xml` is the factory layout file).
|
||||
- The HTML display needs a CI Server login: the user logs in; Claude never enters passwords.
|
||||
Reloading the browser page logs out — reopen displays via the display box instead.
|
||||
- `jwuiutl -vf`, `-u`, `-c`, `-a` rewrite or unlock files of **all** displays: only with approval.
|
||||
|
||||
| Task | File | Status |
|
||||
|---|---|---|
|
||||
| Build a display in the Edit Module (text, number field, alarm overview, trend) and check the saved XML | `tasks/create-display.md` | verified |
|
||||
| Deploy / remove display files, export HTML, validate and search with `jwuiutl` | `tasks/deploy-displays.md` | verified |
|
||||
| Open and check a display in the browser (HTML display / Mobile Operator) | `tasks/deploy-displays.md` §4 | verified |
|
||||
| Layouts (`Layouts.xml`), menus, toolbars, frames, dual screen | R30 summary §2 | from docs |
|
||||
| Dataset forms (`*Dia.xml`) and the form description language | R30 summary §3 | from docs |
|
||||
| Symbols, parameters, actions, localisation, record/playback | C50 summary §1, §4, §5 | from docs |
|
||||
| AOG library (styles, symbols, faceplates, templates) | C60 summary | from docs |
|
||||
|
|
@ -1,50 +0,0 @@
|
|||
---
|
||||
task: Build a display in the Edit Module and check the saved file
|
||||
version: R1.03
|
||||
source: IM 36K10C50-01EN §1.2, §1.7, §2, §4.8.1; practiced on CI-Eng-Sample (display CIENG_Tank) 2026-10-01
|
||||
status: verified
|
||||
---
|
||||
|
||||
# Build a display (Edit Module)
|
||||
|
||||
The user draws; Claude gives the steps and checks the result. Example = the sample display
|
||||
`examples/CI-Eng-Sample/displays/CIENG_Tank.xml`.
|
||||
|
||||
## Steps for the user
|
||||
|
||||
1. Start the Edit Module and log in.
|
||||
2. *File > New Display*, name `<DisplayName>`; tick **HTML display** if it should also run in a
|
||||
browser (the editor then hides unsupported components and properties).
|
||||
3. Add components from the component bar, for example:
|
||||
- **Text** — title.
|
||||
- **Number field** — in the Properties sheet click **Value**, open the connection dialog,
|
||||
*Items* tab, pick `<Section>.<Tag>`.
|
||||
- **Alarm Overview** — right-click > *Component Properties*; *Filter* tab for an ASA, section
|
||||
or tag filter; *Types* tab for current/historical.
|
||||
- **Trend** — component properties, pen 1 = `<Section>.<Tag>` (a new trend has 5 empty pens;
|
||||
the item must be in a storage group).
|
||||
4. *File > Save* (or *Save with Revision Information*). Close the tab when done: an open
|
||||
display is locked (`<DisplayName>.lck`) and `jwuiutl` skips it.
|
||||
|
||||
## Check the saved file
|
||||
|
||||
Folder `%TLS_WAP_PATH%\cfg\operatorInterfaces\DEPLOY\displays\` (and with HTML mode also
|
||||
`%TLS_WAP_PATH%\mobileoperator\operatorInterfaces\DEPLOY\displays\<DisplayName>.html`).
|
||||
|
||||
```
|
||||
grep -n "<html>\|<width>\|<height>\|itemName\|itemId\|<source" <DisplayName>.xml
|
||||
```
|
||||
|
||||
- `<html>true</html>` = HTML mode; `<width>`/`<height>` must be set for the HTML display.
|
||||
- Item connections: `<itemName>` + `<itemId>` (node.group.number…); trend pens:
|
||||
`<source type="sourceID" uri="ci:/item/<item>"/>` (`uri=""` = empty pen).
|
||||
- The name is what counts: after the item was deleted and loaded again (new id) the display
|
||||
still validated and a new session showed live values; already-open sessions kept showing the
|
||||
old value until reopened.
|
||||
|
||||
## Verified (CIENG_Tank, 2026-10-01)
|
||||
|
||||
Text `CI-Eng-Sample Tank 1`, number field on `TANK1.LEVEL` (live: 72 → 61), alarm overview
|
||||
(no filter; listed the TANK1.LEVEL alarms), trend pen `TANK1.LEVEL` (legend
|
||||
`CI-Eng-Sample.TANK1.LEVEL [CIENG_SCAN10S]` = highest-priority storage group). In the HTML
|
||||
display the trend drew no line (ISS-041).
|
||||
|
|
@ -1,56 +0,0 @@
|
|||
---
|
||||
task: Deploy, remove, export, validate and search displays; open them in the browser
|
||||
version: R1.03
|
||||
source: IM 36K10C50-01EN §1.5; IM 36K10R30-01EN §1.1, §4; practiced on CI-Eng-Sample 2026-10-01
|
||||
status: verified
|
||||
---
|
||||
|
||||
# Deploy and check displays
|
||||
|
||||
No admin rights needed (`C:\Users\Public\Yokogawa\tls\wap`). `jwuiutl.cmd` is in `tls\com`
|
||||
(on `PATH`); call it through `cmd` (`cmd /c "jwuiutl.cmd …"`).
|
||||
|
||||
## 1. Deploy / remove (sample scripts)
|
||||
|
||||
`examples/CI-Eng-Sample/displays/deploy_displays.cmd`: copies `CIENG_Tank.xml` to
|
||||
`%TLS_WAP_PATH%\cfg\operatorInterfaces\DEPLOY\displays\` and runs
|
||||
`jwuiutl.cmd -e HTML -i -f DEPLOY CIENG_Tank` (HTML into
|
||||
`%TLS_WAP_PATH%\mobileoperator\operatorInterfaces\DEPLOY\displays\`).
|
||||
`remove_displays.cmd` deletes both files (close the display in the Edit Module first).
|
||||
Deploy after `load.cmd` so the items exist.
|
||||
|
||||
For another display: copy `<name>.xml` into `DEPLOY\displays` and export it the same way.
|
||||
Displays with symbols also need the symbol files in `DEPLOY\symbols`.
|
||||
|
||||
## 2. Validate (report only)
|
||||
|
||||
```
|
||||
cmd /c "jwuiutl.cmd -d -v -i -l <scratch>\validate.txt"
|
||||
```
|
||||
|
||||
Per display: `Validating <name>` then `Info: No problems found`, or `*** Validation failed for
|
||||
display <name>:` with `Problem: <component>: Connected item is not found (<item>)`. Skipped:
|
||||
`*** Display locked <name>` (open in the Edit Module or a stale `.lck`; `-u` unlocks — with
|
||||
approval), displays saved by a newer version. `-vf` re-saves all displays — only with approval.
|
||||
|
||||
## 3. Search
|
||||
|
||||
```
|
||||
cmd /c "jwuiutl.cmd -d -m <term> > <scratch>\match.txt 2>&1"
|
||||
```
|
||||
|
||||
CSV `Type, File, Component` per match; `-M` adds actions and properties. Use it before deleting
|
||||
or renaming items to find the displays that use them.
|
||||
|
||||
## 4. Open in the browser (HTML display)
|
||||
|
||||
`http://localhost:8080/mobileoperator/?d=<display>` (`&l=<layout>`). The user logs in with a CI
|
||||
Server user. The page shows the operator frame (menu, navigation buttons, alarm banner, status
|
||||
line). To switch displays type the name in the display box and press Enter — **reloading the
|
||||
page ends the session**. Check live values by writing a test value (`itmval -p`, test items only).
|
||||
|
||||
## Verified (2026-10-01)
|
||||
|
||||
Remove → deploy recreated both files; `-e HTML` output identical to the Edit Module's HTML;
|
||||
validation of `CIENG_Tank` *No problems found* (also after a sample reload with new item ids);
|
||||
search worked; browser showed live values. HTML trend without line: ISS-041.
|
||||
|
|
@ -1,173 +1,164 @@
|
|||
# CI-Eng-Sample
|
||||
|
||||
A small, invented sample project that anyone with this repo can load into a CI Server
|
||||
**R1.03** test system. Skills use its names in their examples, and every skill task is
|
||||
re-tested against it so that no other project is needed.
|
||||
|
||||
Built and tested on CI Server R1.03.00 (unlicensed test system), 2026-09-30.
|
||||
|
||||
## Load and remove
|
||||
|
||||
Test systems only: loading writes to the CI Server database. CI Server must be running.
|
||||
From an elevated prompt, call the scripts by full path (a bare `load.cmd` may not be found
|
||||
from the current folder):
|
||||
|
||||
```
|
||||
cmd /c "<repo>\examples\CI-Eng-Sample\load.cmd"
|
||||
cmd /c "<repo>\examples\CI-Eng-Sample\remove.cmd"
|
||||
```
|
||||
|
||||
- Each step prints a summary and writes a `.qlo` listing; check that `Errors` is 0.
|
||||
- **Restart CI Server after loading** (stop, then start the CI Service): a new storage group
|
||||
stores no history until CI Server restarts.
|
||||
- `load.cmd` on a system that already has the project reports `Exists` and changes nothing.
|
||||
- `remove.cmd` takes about 1½ minutes: a storage group can only be deleted after its stop time
|
||||
has passed, so the script sets a stop time one minute ahead and waits. Removing the group
|
||||
also deletes its history.
|
||||
|
||||
## Current contents
|
||||
|
||||
| Name | Kind | Details |
|
||||
|---|---|---|
|
||||
| `CI-Eng-Sample` | Section | Top level |
|
||||
| `CI-Eng-Sample.TANK1`, `.PUMP1`, `.SYSTEM` | Sections | Tank, pump, system monitoring |
|
||||
| `CI-Eng-Sample.TANK1.LEVEL` | Item, Real | %, format `999.9`, limits LL 10 / L 20 / H 80 / HH 90, scale 0–100, stored in `CIENG_EVENT`; alarming on (ack type `CIENG_ACK`, area `CIENG_TANKS`; `16_item_alarm_df.qli`) |
|
||||
| `CI-Eng-Sample.TANK1.INFLOW` | Item, Real | m3/h, format `9999.9`, scale 0–500, stored in `CIENG_EVENT` |
|
||||
| `CI-Eng-Sample.PUMP1.RUNNING` | Item, Boolean | |
|
||||
| `CI-Eng-Sample.PUMP1.MODE` | Item, Integer | 0 manual, 1 auto |
|
||||
| `CI-Eng-Sample.SYSTEM.CPU_LOAD` | Item, Real | Target for `intcpumon` |
|
||||
| `CI-Eng-Sample.SYSTEM.DISK_C` | Item, Real | Target for `intdskmon` (reports **used** %) |
|
||||
| `CI-Eng-Sample.SYSTEM.PING_LOCALHOST` | Item, Integer | Target for `inttcpmon` (1 = reachable) |
|
||||
| `CI-Eng-Sample.SYSTEM.PROC_ALM` | Item, Integer | Target for `intmon` (1 = `alm` process running) |
|
||||
| `CI-Eng-Sample.PUMP1.RUNNING.RUN_SECONDS` | Sub-item, Integrator | Running time in seconds (adds value × integration granule, `itm_int_secs` in `itm.sup`, default 1 s) |
|
||||
| `CI-Eng-Sample.TANK1.LEVEL.MAX` | Sub-item, Min-Max | Highest level seen |
|
||||
| `CI-Eng-Sample.DEMO` | Section | Tutorial examples |
|
||||
| `CI-Eng-Sample.DEMO.COUNTER` | Item, Integer | Counts 1…100, one step per second, written by `DEMO.INCR1` |
|
||||
| `CIENG_1S` | Trigger group | Every second |
|
||||
| `CIENG_INCR` | Class (traditional) | Increments `DEMO.COUNTER`, wraps at 100; compiled on load |
|
||||
| `CI-Eng-Sample.DEMO.INCR1` | Object | Instance of `CIENG_INCR` |
|
||||
| `CI-Eng-Sample.TEMPLATES` | Section | Template items for classes |
|
||||
| `CI-Eng-Sample.TEMPLATES.TPL_REAL` | Item, Real | Template for items that objects create (format `9999.9`, scale 0–1000) |
|
||||
| `CIENG_TANK` | Class (traditional) | Prompt *Tank capacity (m3)*; signal `LEVEL` = `<object section>.LEVEL` (trigger on value); creates `<object>.VOLUME` from `TPL_REAL`; volume = level × capacity / 100; logs when the level crosses 80; refuses capacity ≤ 0 |
|
||||
| `CI-Eng-Sample.TANK1.CALC` | Object | `CIENG_TANK`, capacity 200; creates section `TANK1.CALC` and item `TANK1.CALC.VOLUME` |
|
||||
| `CIENG_JFLOW` | Class (Java) | Attaches `<object section>.INFLOW`; creates `<object>.sPerMin` = inflow / 60; logs each change |
|
||||
| `CI-Eng-Sample.TANK1.JFLOW` | Object | `CIENG_JFLOW`; creates item `TANK1.JFLOW.sPerMin` (mixed case, as the Java identifier) |
|
||||
| `CIENG_EVENT` | Item storage group | Event/Item, lifetime 1 week, rollover 1 day |
|
||||
| `CIENG_SCAN10S` | Item storage group | Scan/Time every 10 s with quality, priority 10 (source for aggregation), lifetime 1 day, rollover 1 hour; `TANK1.LEVEL`, `TANK1.INFLOW` |
|
||||
| `CIENG_AGG` | Item storage group | Aggregation 30 min + hourly, lifetime 4 weeks, rollover 1 week; `TANK1.LEVEL` max/min/average (read with `INTERPOLATION = "30Minutes"` / `"Hour"`, `ATTRIBUTE = "Maximum"` …) |
|
||||
| `CI-Eng-Sample.PLC1` | Section | Modbus loopback station |
|
||||
| `CI-Eng-Sample.PLC1.COMM_OK` | Item, Boolean | Status item of station `CIENG_PLC` (1 = communicating, status 22 when off-scan) |
|
||||
| `CI-Eng-Sample.PLC1.SETPOINT` / `.READBACK` | Items, Integer | Written to holding register 1 (`RO:1`) / read from input register 1 (`RI:1`), same memory |
|
||||
| `CI-Eng-Sample.PLC1.CMD` / `.FEEDBACK` | Items, Boolean | Written to coil 1 (`DO:1`) / read from input bit 1 (`DI:1`), same memory |
|
||||
| `CIENG_MB_LINE` | Modbus line (TCP/IP) | Equipment manager `EQPCIENG` (created and started by loading the line) |
|
||||
| `CIENG_PLC` | Modbus station | Open Modbus/TCP to `localhost:5020`, unit 1, output method *On change and connect* |
|
||||
| `CIENG_SCAN1S` | Modbus scan type | 1000 ms |
|
||||
| `CI-Eng-Sample.UA` | Section | OPC UA loopback station |
|
||||
| `CI-Eng-Sample.UA.COMM_OK` | Item, Boolean | Status item of station `CIENG_UA` (1 = connected) |
|
||||
| `CI-Eng-Sample.UA.LEVEL_COPY` | Item, Real | `TANK1.LEVEL` read back through CI Server's own OPC UA server |
|
||||
| `CI-Eng-Sample.UA.SRV_STATE` | Item, Integer | OPC UA server state node (ns 0, i=2259), 0 = Running |
|
||||
| `CIENG_UA_LINE` | OPC UA client line | Client process `OPXCIENG` (created and started by loading the line) |
|
||||
| `CIENG_UA` | OPC UA station | `opc.tcp://localhost:34493`, Basic256Sha256 / SignAndEncrypt, anonymous; subscription `CIENG_SUB` (1 s); points `LEVEL`, `SRV_STATE` |
|
||||
| OPC visible | Flags | Sections `CI-Eng-Sample`, `TANK1` and item `TANK1.LEVEL` are OPC visible, item read-only (`12_opc_visible_df.qli`) |
|
||||
| `CIENG_ACK` | Acknowledgement type | Every alarm needs an acknowledgement; return to normal automatic only if the alarm was acknowledged (same matrix as `MANUAL`) |
|
||||
| `CIENG_TANKS` | Area of interest | Label for tank items (`TANK1.LEVEL` `AOI_1`) |
|
||||
| `CIENG_TANK1` | Alarm selection area | `SECTION = "CI-Eng-Sample.TANK1"`, compiled on load |
|
||||
| `CIENG_VIEWER` | Authorization group | Read-only: `ITEM_READ`, `SECTION_READ`, `ALARM_CURRENT_READ`, `ALARM_CHRONO_READ`. No users are created by the sample. |
|
||||
|
||||
Items created by objects (`TANK1.CALC.VOLUME`, `TANK1.JFLOW.sPerMin`) and their sections are
|
||||
deleted with the objects; they are not in `02_item_df.qli`.
|
||||
|
||||
All items except `PLC1.*` are internal (no station). The `PLC1` station talks to CI Server's own Modbus slave mirror (see below), so no PLC is needed either.
|
||||
New items start with status 13 (`NOT INIT`) until a value is written.
|
||||
|
||||
## Files
|
||||
|
||||
| File | Purpose |
|
||||
|---|---|
|
||||
| `01_section_df.qli` | Sections (`SECTION_DF`); parents before children |
|
||||
| `02_item_df.qli` | Items (`ITEM_DF`) |
|
||||
| `02b_sub_item_df.qli` | Sub-items (`SUB_ITEM_DF`) |
|
||||
| `03_his_group_df.qli` | Item storage groups (`HIS_GROUP_DF`): event, scan, aggregation |
|
||||
| `04_item_his_df.qli` | Items in the storage group (`ITEM_HIS_DF`, name `<group>:<item>`) |
|
||||
| `05_trigger_df.qli`, `06_class_df.qli`, `07_object_df.qli` | Trigger group; classes (source in the `METHOD` memo, `@"` … `"@`, `COMPILE` 1; Traditional and Java); objects (`ATTR_VALUE_1` = prompt answer) |
|
||||
| `08_auth_group_df.qli` | Authorization group (`AUTH_GROUP_DF`) |
|
||||
| `09_modbus_line_df.qli`, `10_modbus_station_df.qli`, `11_item_eqp_df.qli` | Modbus line; station, scan type, points; items connected to points |
|
||||
| `12_opc_visible_df.qli` | OPC visible / read flags (loaded with `dssqld -m`) |
|
||||
| `13_opcua_line_df.qli`, `14_opcua_station_df.qli`, `15_item_opcua_df.qli` | OPC UA client line; station, subscription, points; connected items |
|
||||
| `01b_alarm_df.qli` | Alarm definitions: acknowledgement type, area of interest, alarm selection area (`ALARM_ACK_DF`, `ALARM_AOI_DF`, `ALARM_ASA_DF`) |
|
||||
| `16_item_alarm_df.qli` | Switch on alarming for `TANK1.LEVEL` (loaded with `dssqld -m`) |
|
||||
| `equipment/eqpciengslv_start.cmd`, `_stop.cmd` | Start/stop the Modbus slave mirror (copy to `tls\com`) |
|
||||
| `76_`…`93_remove_*.qli` | Names to delete, in reverse order (alarm definitions last, `93`) |
|
||||
| `load.cmd`, `remove.cmd` | Run the steps in the right order |
|
||||
| `displays/CIENG_Tank.xml` | Display (HTML mode): title, number field on `TANK1.LEVEL`, alarm overview, trend of `TANK1.LEVEL` |
|
||||
| `displays/deploy_displays.cmd`, `remove_displays.cmd` | Copy the display into the operator interface and export its HTML version / delete both |
|
||||
| `monitoring/*.sup.txt` | Setup-file lines for the monitoring processes (not applied by `load.cmd`) |
|
||||
|
||||
## Modbus slave mirror (for station CIENG_PLC)
|
||||
|
||||
`CIENG_PLC` reads and writes CI Server's own Modbus slave: `eqpmdcmem` (slave memory) and
|
||||
`eqpmdcslvtcp` (Modbus TCP on port 5020). Without them the station reports bad communication
|
||||
(`COMM_OK` = 0) but everything loads. To start them with CI Server, an administrator copies
|
||||
`equipment/eqpciengslv_start.cmd` and `eqpciengslv_stop.cmd` to `%TLS_ROOT_PATH%\tls\com`;
|
||||
for a quick test they can also be started by hand from a normal prompt:
|
||||
|
||||
```
|
||||
start eqpmdcmem -n EQPMDCMEM
|
||||
start eqpmdcslvtcp -n EQPMDCSLVTCP -p 5020
|
||||
```
|
||||
|
||||
Remove the two files from `tls\com` when the sample is removed. See skill `equipment`, task
|
||||
`modbus-station.md`.
|
||||
|
||||
## OPC UA loopback (station CIENG_UA)
|
||||
|
||||
`CIENG_UA` is CI Server's OPC UA client connected to CI Server's own OPC UA server, so no
|
||||
external server is needed. The **first** connection on a system needs a one-time certificate
|
||||
exchange, done by the user (skill `data-access`, task `opcua-client.md` §4):
|
||||
|
||||
1. After loading, the client logs `OPXC-E-CER_NO_TRU`; trust the server certificate in
|
||||
`%TLS_ALLUSERS_PATH%\pki\opxuac\pkiclient\rejected` (Engineering Module, or move it to
|
||||
`…\pkiclient\trusted\certs`).
|
||||
2. The server then rejects the client; move `CI_SERVER_OPCUA_CLIENT_OPXCIENG […].der` from
|
||||
`%TLS_ALLUSERS_PATH%\pki\opxuas\pkiserver\rejected` to `…\pkiserver\trusted\certs`
|
||||
(PowerShell: `Move-Item -LiteralPath`, the name contains brackets).
|
||||
|
||||
Then `UA.COMM_OK` = 1 and `UA.LEVEL_COPY` follows `TANK1.LEVEL`. The trust is kept when the
|
||||
sample is removed and loaded again.
|
||||
|
||||
## Alarms (TANK1.LEVEL)
|
||||
|
||||
`TANK1.LEVEL` raises HIGH above 80 (Alarm 2, priority 2) and HIGH HIGH above 90 (Alarm 3,
|
||||
priority 1). To try it on a test system: `itmval -p -n CI-Eng-Sample.TANK1.LEVEL -v 85`, export
|
||||
`ALARM_CURRENT` (filter on `ITEM_NAME`), acknowledge with `dssqld -m` on `ALARM_CURRENT`
|
||||
(`NAME`, `ACK` 1), write the level back below 80. See skill `alarm-management`, task
|
||||
`item-alarming.md`.
|
||||
|
||||
## Display (optional)
|
||||
|
||||
After `load.cmd`, run `displays\deploy_displays.cmd` (no admin rights) and open
|
||||
`http://localhost:8080/mobileoperator/?d=CIENG_Tank` (CI Server login), or open `CIENG_Tank` in
|
||||
CI View / the Edit Module. `displays
emove_displays.cmd` deletes it again. See skill
|
||||
`graphics`.
|
||||
|
||||
## Monitoring processes (optional)
|
||||
|
||||
`monitoring/` holds the lines to add to the setup files in `%TLS_ROOT_PATH%\tls\sup\` so that
|
||||
`intcpumon`, `intdskmon`, `inttcpmon`, `intmon` and `intspawn` write into the `SYSTEM` items.
|
||||
These change the system's own setup files: back the files up first and restore them after
|
||||
testing. See the `system-management` skill, task `monitoring-processes.md`.
|
||||
|
||||
## Planned additions
|
||||
|
||||
| Phase | Adds |
|
||||
|---|---|
|
||||
| 10 | A symbol (the display `CIENG_Tank` exists) |
|
||||
| 11 | A report |
|
||||
|
||||
## Rules
|
||||
|
||||
- Test systems only; invented names only, no real plant or customer data.
|
||||
- Keep the load order: sections → template items → classes (compiled) → objects → other
|
||||
items → storage groups → items in storage groups (IM 36K10J10 §5.6). Keep `remove.cmd` in
|
||||
reverse order.
|
||||
- Every file notes the CI Server version it was built and tested on.
|
||||
# CI-Eng-Sample
|
||||
|
||||
A small, invented sample project that anyone with this repo can load into a CI Server
|
||||
**R1.03** test system. Skills use its names in their examples, and every skill task is
|
||||
re-tested against it so that no other project is needed.
|
||||
|
||||
Built and tested on CI Server R1.03.00 (unlicensed test system), 2026-09-30.
|
||||
|
||||
## Load and remove
|
||||
|
||||
Test systems only: loading writes to the CI Server database. CI Server must be running.
|
||||
From an elevated prompt, call the scripts by full path (a bare `load.cmd` may not be found
|
||||
from the current folder):
|
||||
|
||||
```
|
||||
cmd /c "<repo>\examples\CI-Eng-Sample\load.cmd"
|
||||
cmd /c "<repo>\examples\CI-Eng-Sample\remove.cmd"
|
||||
```
|
||||
|
||||
- Each step prints a summary and writes a `.qlo` listing; check that `Errors` is 0.
|
||||
- **Restart CI Server after loading** (stop, then start the CI Service): a new storage group
|
||||
stores no history until CI Server restarts.
|
||||
- `load.cmd` on a system that already has the project reports `Exists` and changes nothing.
|
||||
- `remove.cmd` takes about 1½ minutes: a storage group can only be deleted after its stop time
|
||||
has passed, so the script sets a stop time one minute ahead and waits. Removing the group
|
||||
also deletes its history.
|
||||
|
||||
## Current contents
|
||||
|
||||
| Name | Kind | Details |
|
||||
|---|---|---|
|
||||
| `CI-Eng-Sample` | Section | Top level |
|
||||
| `CI-Eng-Sample.TANK1`, `.PUMP1`, `.SYSTEM` | Sections | Tank, pump, system monitoring |
|
||||
| `CI-Eng-Sample.TANK1.LEVEL` | Item, Real | %, format `999.9`, limits LL 10 / L 20 / H 80 / HH 90, scale 0–100, stored in `CIENG_EVENT`; alarming on (ack type `CIENG_ACK`, area `CIENG_TANKS`; `16_item_alarm_df.qli`) |
|
||||
| `CI-Eng-Sample.TANK1.INFLOW` | Item, Real | m3/h, format `9999.9`, scale 0–500, stored in `CIENG_EVENT` |
|
||||
| `CI-Eng-Sample.PUMP1.RUNNING` | Item, Boolean | |
|
||||
| `CI-Eng-Sample.PUMP1.MODE` | Item, Integer | 0 manual, 1 auto |
|
||||
| `CI-Eng-Sample.SYSTEM.CPU_LOAD` | Item, Real | Target for `intcpumon` |
|
||||
| `CI-Eng-Sample.SYSTEM.DISK_C` | Item, Real | Target for `intdskmon` (reports **used** %) |
|
||||
| `CI-Eng-Sample.SYSTEM.PING_LOCALHOST` | Item, Integer | Target for `inttcpmon` (1 = reachable) |
|
||||
| `CI-Eng-Sample.SYSTEM.PROC_ALM` | Item, Integer | Target for `intmon` (1 = `alm` process running) |
|
||||
| `CI-Eng-Sample.PUMP1.RUNNING.RUN_SECONDS` | Sub-item, Integrator | Running time in seconds (adds value × integration granule, `itm_int_secs` in `itm.sup`, default 1 s) |
|
||||
| `CI-Eng-Sample.TANK1.LEVEL.MAX` | Sub-item, Min-Max | Highest level seen |
|
||||
| `CI-Eng-Sample.DEMO` | Section | Tutorial examples |
|
||||
| `CI-Eng-Sample.DEMO.COUNTER` | Item, Integer | Counts 1…100, one step per second, written by `DEMO.INCR1` |
|
||||
| `CIENG_1S` | Trigger group | Every second |
|
||||
| `CIENG_INCR` | Class (traditional) | Increments `DEMO.COUNTER`, wraps at 100; compiled on load |
|
||||
| `CI-Eng-Sample.DEMO.INCR1` | Object | Instance of `CIENG_INCR` |
|
||||
| `CI-Eng-Sample.TEMPLATES` | Section | Template items for classes |
|
||||
| `CI-Eng-Sample.TEMPLATES.TPL_REAL` | Item, Real | Template for items that objects create (format `9999.9`, scale 0–1000) |
|
||||
| `CIENG_TANK` | Class (traditional) | Prompt *Tank capacity (m3)*; signal `LEVEL` = `<object section>.LEVEL` (trigger on value); creates `<object>.VOLUME` from `TPL_REAL`; volume = level × capacity / 100; logs when the level crosses 80; refuses capacity ≤ 0 |
|
||||
| `CI-Eng-Sample.TANK1.CALC` | Object | `CIENG_TANK`, capacity 200; creates section `TANK1.CALC` and item `TANK1.CALC.VOLUME` |
|
||||
| `CIENG_JFLOW` | Class (Java) | Attaches `<object section>.INFLOW`; creates `<object>.sPerMin` = inflow / 60; logs each change |
|
||||
| `CI-Eng-Sample.TANK1.JFLOW` | Object | `CIENG_JFLOW`; creates item `TANK1.JFLOW.sPerMin` (mixed case, as the Java identifier) |
|
||||
| `CIENG_EVENT` | Item storage group | Event/Item, lifetime 1 week, rollover 1 day |
|
||||
| `CIENG_SCAN10S` | Item storage group | Scan/Time every 10 s with quality, priority 10 (source for aggregation), lifetime 1 day, rollover 1 hour; `TANK1.LEVEL`, `TANK1.INFLOW` |
|
||||
| `CIENG_AGG` | Item storage group | Aggregation 30 min + hourly, lifetime 4 weeks, rollover 1 week; `TANK1.LEVEL` max/min/average (read with `INTERPOLATION = "30Minutes"` / `"Hour"`, `ATTRIBUTE = "Maximum"` …) |
|
||||
| `CI-Eng-Sample.PLC1` | Section | Modbus loopback station |
|
||||
| `CI-Eng-Sample.PLC1.COMM_OK` | Item, Boolean | Status item of station `CIENG_PLC` (1 = communicating, status 22 when off-scan) |
|
||||
| `CI-Eng-Sample.PLC1.SETPOINT` / `.READBACK` | Items, Integer | Written to holding register 1 (`RO:1`) / read from input register 1 (`RI:1`), same memory |
|
||||
| `CI-Eng-Sample.PLC1.CMD` / `.FEEDBACK` | Items, Boolean | Written to coil 1 (`DO:1`) / read from input bit 1 (`DI:1`), same memory |
|
||||
| `CIENG_MB_LINE` | Modbus line (TCP/IP) | Equipment manager `EQPCIENG` (created and started by loading the line) |
|
||||
| `CIENG_PLC` | Modbus station | Open Modbus/TCP to `localhost:5020`, unit 1, output method *On change and connect* |
|
||||
| `CIENG_SCAN1S` | Modbus scan type | 1000 ms |
|
||||
| `CI-Eng-Sample.UA` | Section | OPC UA loopback station |
|
||||
| `CI-Eng-Sample.UA.COMM_OK` | Item, Boolean | Status item of station `CIENG_UA` (1 = connected) |
|
||||
| `CI-Eng-Sample.UA.LEVEL_COPY` | Item, Real | `TANK1.LEVEL` read back through CI Server's own OPC UA server |
|
||||
| `CI-Eng-Sample.UA.SRV_STATE` | Item, Integer | OPC UA server state node (ns 0, i=2259), 0 = Running |
|
||||
| `CIENG_UA_LINE` | OPC UA client line | Client process `OPXCIENG` (created and started by loading the line) |
|
||||
| `CIENG_UA` | OPC UA station | `opc.tcp://localhost:34493`, Basic256Sha256 / SignAndEncrypt, anonymous; subscription `CIENG_SUB` (1 s); points `LEVEL`, `SRV_STATE` |
|
||||
| OPC visible | Flags | Sections `CI-Eng-Sample`, `TANK1` and item `TANK1.LEVEL` are OPC visible, item read-only (`12_opc_visible_df.qli`) |
|
||||
| `CIENG_ACK` | Acknowledgement type | Every alarm needs an acknowledgement; return to normal automatic only if the alarm was acknowledged (same matrix as `MANUAL`) |
|
||||
| `CIENG_TANKS` | Area of interest | Label for tank items (`TANK1.LEVEL` `AOI_1`) |
|
||||
| `CIENG_TANK1` | Alarm selection area | `SECTION = "CI-Eng-Sample.TANK1"`, compiled on load |
|
||||
| `CIENG_VIEWER` | Authorization group | Read-only: `ITEM_READ`, `SECTION_READ`, `ALARM_CURRENT_READ`, `ALARM_CHRONO_READ`. No users are created by the sample. |
|
||||
|
||||
Items created by objects (`TANK1.CALC.VOLUME`, `TANK1.JFLOW.sPerMin`) and their sections are
|
||||
deleted with the objects; they are not in `02_item_df.qli`.
|
||||
|
||||
All items except `PLC1.*` are internal (no station). The `PLC1` station talks to CI Server's own Modbus slave mirror (see below), so no PLC is needed either.
|
||||
New items start with status 13 (`NOT INIT`) until a value is written.
|
||||
|
||||
## Files
|
||||
|
||||
| File | Purpose |
|
||||
|---|---|
|
||||
| `01_section_df.qli` | Sections (`SECTION_DF`); parents before children |
|
||||
| `02_item_df.qli` | Items (`ITEM_DF`) |
|
||||
| `02b_sub_item_df.qli` | Sub-items (`SUB_ITEM_DF`) |
|
||||
| `03_his_group_df.qli` | Item storage groups (`HIS_GROUP_DF`): event, scan, aggregation |
|
||||
| `04_item_his_df.qli` | Items in the storage group (`ITEM_HIS_DF`, name `<group>:<item>`) |
|
||||
| `05_trigger_df.qli`, `06_class_df.qli`, `07_object_df.qli` | Trigger group; classes (source in the `METHOD` memo, `@"` … `"@`, `COMPILE` 1; Traditional and Java); objects (`ATTR_VALUE_1` = prompt answer) |
|
||||
| `08_auth_group_df.qli` | Authorization group (`AUTH_GROUP_DF`) |
|
||||
| `09_modbus_line_df.qli`, `10_modbus_station_df.qli`, `11_item_eqp_df.qli` | Modbus line; station, scan type, points; items connected to points |
|
||||
| `12_opc_visible_df.qli` | OPC visible / read flags (loaded with `dssqld -m`) |
|
||||
| `13_opcua_line_df.qli`, `14_opcua_station_df.qli`, `15_item_opcua_df.qli` | OPC UA client line; station, subscription, points; connected items |
|
||||
| `01b_alarm_df.qli` | Alarm definitions: acknowledgement type, area of interest, alarm selection area (`ALARM_ACK_DF`, `ALARM_AOI_DF`, `ALARM_ASA_DF`) |
|
||||
| `16_item_alarm_df.qli` | Switch on alarming for `TANK1.LEVEL` (loaded with `dssqld -m`) |
|
||||
| `equipment/eqpciengslv_start.cmd`, `_stop.cmd` | Start/stop the Modbus slave mirror (copy to `tls\com`) |
|
||||
| `76_`…`93_remove_*.qli` | Names to delete, in reverse order (alarm definitions last, `93`) |
|
||||
| `load.cmd`, `remove.cmd` | Run the steps in the right order |
|
||||
| `monitoring/*.sup.txt` | Setup-file lines for the monitoring processes (not applied by `load.cmd`) |
|
||||
|
||||
## Modbus slave mirror (for station CIENG_PLC)
|
||||
|
||||
`CIENG_PLC` reads and writes CI Server's own Modbus slave: `eqpmdcmem` (slave memory) and
|
||||
`eqpmdcslvtcp` (Modbus TCP on port 5020). Without them the station reports bad communication
|
||||
(`COMM_OK` = 0) but everything loads. To start them with CI Server, an administrator copies
|
||||
`equipment/eqpciengslv_start.cmd` and `eqpciengslv_stop.cmd` to `%TLS_ROOT_PATH%\tls\com`;
|
||||
for a quick test they can also be started by hand from a normal prompt:
|
||||
|
||||
```
|
||||
start eqpmdcmem -n EQPMDCMEM
|
||||
start eqpmdcslvtcp -n EQPMDCSLVTCP -p 5020
|
||||
```
|
||||
|
||||
Remove the two files from `tls\com` when the sample is removed. See skill `equipment`, task
|
||||
`modbus-station.md`.
|
||||
|
||||
## OPC UA loopback (station CIENG_UA)
|
||||
|
||||
`CIENG_UA` is CI Server's OPC UA client connected to CI Server's own OPC UA server, so no
|
||||
external server is needed. The **first** connection on a system needs a one-time certificate
|
||||
exchange, done by the user (skill `data-access`, task `opcua-client.md` §4):
|
||||
|
||||
1. After loading, the client logs `OPXC-E-CER_NO_TRU`; trust the server certificate in
|
||||
`%TLS_ALLUSERS_PATH%\pki\opxuac\pkiclient\rejected` (Engineering Module, or move it to
|
||||
`…\pkiclient\trusted\certs`).
|
||||
2. The server then rejects the client; move `CI_SERVER_OPCUA_CLIENT_OPXCIENG […].der` from
|
||||
`%TLS_ALLUSERS_PATH%\pki\opxuas\pkiserver\rejected` to `…\pkiserver\trusted\certs`
|
||||
(PowerShell: `Move-Item -LiteralPath`, the name contains brackets).
|
||||
|
||||
Then `UA.COMM_OK` = 1 and `UA.LEVEL_COPY` follows `TANK1.LEVEL`. The trust is kept when the
|
||||
sample is removed and loaded again.
|
||||
|
||||
## Alarms (TANK1.LEVEL)
|
||||
|
||||
`TANK1.LEVEL` raises HIGH above 80 (Alarm 2, priority 2) and HIGH HIGH above 90 (Alarm 3,
|
||||
priority 1). To try it on a test system: `itmval -p -n CI-Eng-Sample.TANK1.LEVEL -v 85`, export
|
||||
`ALARM_CURRENT` (filter on `ITEM_NAME`), acknowledge with `dssqld -m` on `ALARM_CURRENT`
|
||||
(`NAME`, `ACK` 1), write the level back below 80. See skill `alarm-management`, task
|
||||
`item-alarming.md`.
|
||||
|
||||
## Monitoring processes (optional)
|
||||
|
||||
`monitoring/` holds the lines to add to the setup files in `%TLS_ROOT_PATH%\tls\sup\` so that
|
||||
`intcpumon`, `intdskmon`, `inttcpmon`, `intmon` and `intspawn` write into the `SYSTEM` items.
|
||||
These change the system's own setup files: back the files up first and restore them after
|
||||
testing. See the `system-management` skill, task `monitoring-processes.md`.
|
||||
|
||||
## Planned additions
|
||||
|
||||
| Phase | Adds |
|
||||
|---|---|
|
||||
| 10 | A display and symbol |
|
||||
| 11 | A report |
|
||||
|
||||
## Rules
|
||||
|
||||
- Test systems only; invented names only, no real plant or customer data.
|
||||
- Keep the load order: sections → template items → classes (compiled) → objects → other
|
||||
items → storage groups → items in storage groups (IM 36K10J10 §5.6). Keep `remove.cmd` in
|
||||
reverse order.
|
||||
- Every file notes the CI Server version it was built and tested on.
|
||||
|
|
|
|||
|
|
@ -1,487 +0,0 @@
|
|||
<?xml version="1.0" encoding="utf-8" ?>
|
||||
<visualization protocolVersion="1.3.0.0">
|
||||
<globalSection/>
|
||||
<coreObjectDefinition type="displayDefinition">
|
||||
<version type="version" value="1.3.0.0"/>
|
||||
<html>true</html>
|
||||
<width>1984</width>
|
||||
<height>760</height>
|
||||
<referenceCheck>4</referenceCheck>
|
||||
<defaultBgColor type="colorSet" r="255" g="255" b="255"/>
|
||||
<defaultFgColor type="colorSet" r="0" g="0" b="0"/>
|
||||
<defaultFont type="font" name="Tahoma" size="11" underline="false" strikethrough="false"/>
|
||||
<defaultStroke type="stroke" width="1.0"/>
|
||||
<grid type="grid" gridVisible="true" snappingActive="true" verticalSnapInterval="8" horizontalSnapInterval="8" onTop="false">
|
||||
<color type="colorSet" r="0" g="0" b="0"/>
|
||||
</grid>
|
||||
<revisionHistory type="revisionHistory">
|
||||
<revision type="revision" who="ADMIN" when="2026.10.01 14:29:31.493 AEST" what="Created" where="PXiSEDev"/>
|
||||
</revisionHistory>
|
||||
<blinkDelay>500</blinkDelay>
|
||||
<blinkEnabled>true</blinkEnabled>
|
||||
<mousePassThrough>false</mousePassThrough>
|
||||
<visibilityGroup type="componentData">
|
||||
<htmlId>2</htmlId>
|
||||
<name>Overview</name>
|
||||
<description>Always shown</description>
|
||||
<minimumZoomEnabled>true</minimumZoomEnabled>
|
||||
<minimumZoomFactor>10.0</minimumZoomFactor>
|
||||
</visibilityGroup>
|
||||
<visibilityGroup type="componentData">
|
||||
<htmlId>3</htmlId>
|
||||
<name>Rough</name>
|
||||
<description>Shown when viewing viewing a large area</description>
|
||||
<minimumZoomEnabled>true</minimumZoomEnabled>
|
||||
<minimumZoomFactor>25.0</minimumZoomFactor>
|
||||
</visibilityGroup>
|
||||
<visibilityGroup type="componentData">
|
||||
<htmlId>4</htmlId>
|
||||
<name>Standard</name>
|
||||
<description>Shown when using the default view setting</description>
|
||||
<minimumZoomEnabled>true</minimumZoomEnabled>
|
||||
<minimumZoomFactor>100.0</minimumZoomFactor>
|
||||
</visibilityGroup>
|
||||
<visibilityGroup type="componentData">
|
||||
<htmlId>5</htmlId>
|
||||
<name>Detail</name>
|
||||
<description>Shown only when viewing a small area</description>
|
||||
<minimumZoomEnabled>true</minimumZoomEnabled>
|
||||
<minimumZoomFactor>400.0</minimumZoomFactor>
|
||||
</visibilityGroup>
|
||||
<visibilityGroup type="componentData">
|
||||
<htmlId>6</htmlId>
|
||||
<name>Intricacies</name>
|
||||
<description>Shown only when viewing a very small area</description>
|
||||
<minimumZoomEnabled>true</minimumZoomEnabled>
|
||||
<minimumZoomFactor>1000.0</minimumZoomFactor>
|
||||
</visibilityGroup>
|
||||
<visualizationLayer type="componentData">
|
||||
<htmlId>1</htmlId>
|
||||
<name>Layer1</name>
|
||||
</visualizationLayer>
|
||||
<componentCountHint>4</componentCountHint>
|
||||
<text type="componentData">
|
||||
<htmlId>7</htmlId>
|
||||
<value>CI-Eng-Sample Tank 1</value>
|
||||
<stroke type="stroke" width="1.0"/>
|
||||
<keepOriginalSize>true</keepOriginalSize>
|
||||
<x>124.734375</x>
|
||||
<y>36.953125</y>
|
||||
<top>5.3125</top>
|
||||
<bottom>5.3125</bottom>
|
||||
<left>52.375</left>
|
||||
<right>52.375</right>
|
||||
<rotation>0.0</rotation>
|
||||
<shear>0.0</shear>
|
||||
</text>
|
||||
<numberField type="componentData" x="120.0" y="120.0" top="16.0" bottom="16.0" left="40.0" right="40.0" rotation="0.0" shear="0.0">
|
||||
<htmlId>8</htmlId>
|
||||
<data type="data">
|
||||
<action type="actionConnectTo">
|
||||
<property type="property" name="numberField.value"/>
|
||||
<filter type="filter">
|
||||
<value>0.0</value>
|
||||
</filter>
|
||||
<connection type="connection">
|
||||
<itemName>CI-Eng-Sample.TANK1.LEVEL</itemName>
|
||||
<itemId>1.1.268.0.0.1.1.7</itemId>
|
||||
<itemAttribute>ItemValue</itemAttribute>
|
||||
</connection>
|
||||
</action>
|
||||
</data>
|
||||
</numberField>
|
||||
<alarmOverview type="componentData" x="1020.0" y="296.0" top="72.0" bottom="72.0" left="964.0" right="964.0" rotation="0.0" shear="0.0">
|
||||
<htmlId>9</htmlId>
|
||||
<data type="data">
|
||||
<action type="actionInternalServiced"/>
|
||||
</data>
|
||||
</alarmOverview>
|
||||
<chart type="componentData">
|
||||
<htmlId>10</htmlId>
|
||||
<config type="graphicInfo">
|
||||
<version type="version" value="1.3.0.0"/>
|
||||
<backgroundBorder type="border" value="BorderEmpty"/>
|
||||
<penPanelVisible>false</penPanelVisible>
|
||||
<penPanelHeight>-1</penPanelHeight>
|
||||
<toolbarVisible>true</toolbarVisible>
|
||||
<toolbarPosition type="borderLayoutPosition" value="PositionNorth"/>
|
||||
<shiftOffset>0</shiftOffset>
|
||||
<shiftLength>0</shiftLength>
|
||||
<protection type="protection" active="false" password="">
|
||||
<userProtection type="userProtection" user=""/>
|
||||
</protection>
|
||||
<enterpriseGroupLocation type="nodeName" node="$display$"/>
|
||||
<chartPanel>
|
||||
<name/>
|
||||
<author/>
|
||||
<version type="version" value="1.3.0.0"/>
|
||||
<description/>
|
||||
<forAllUsers>false</forAllUsers>
|
||||
<template>false</template>
|
||||
<group>@NULL</group>
|
||||
<XyMode>false</XyMode>
|
||||
<x>0</x>
|
||||
<y>0</y>
|
||||
<width>800</width>
|
||||
<heigth>400</heigth>
|
||||
<iconized>false</iconized>
|
||||
<backgroundBorder type="border" value="BorderEmpty"/>
|
||||
<foregroundColor type="colorSet" r="0" g="0" b="0"/>
|
||||
<backgroundPaint type="paint">
|
||||
<paint type="colorSet" r="240" g="240" b="240"/>
|
||||
</backgroundPaint>
|
||||
<plotAreaBorder type="border" value="BorderEmpty"/>
|
||||
<plotAreaTransparent>true</plotAreaTransparent>
|
||||
<plotAreaIcon>@NULL</plotAreaIcon>
|
||||
<plotAreaPaint type="paint">
|
||||
<paint type="colorSet" r="255" g="255" b="255"/>
|
||||
</plotAreaPaint>
|
||||
<hairlineColor type="colorSet" r="0" g="0" b="0"/>
|
||||
<hairlineVisible>false</hairlineVisible>
|
||||
<antialiasingText>false</antialiasingText>
|
||||
<antialiasingData>true</antialiasingData>
|
||||
<renderMode type="chartRendering" value="Rendering2d"/>
|
||||
<timeNavigatorVisible>true</timeNavigatorVisible>
|
||||
<timeRangeControlVisible>true</timeRangeControlVisible>
|
||||
<autoUpdateInterval>false</autoUpdateInterval>
|
||||
<legendVisible>true</legendVisible>
|
||||
<legendTitle/>
|
||||
<legendHeading/>
|
||||
<legendColor type="colorSet" r="0" g="0" b="0"/>
|
||||
<legendBackgroundColor type="colorSet" r="240" g="240" b="240"/>
|
||||
<legendFont type="font" name="Tahoma" size="11" underline="false" strikethrough="false"/>
|
||||
<legendTransparancy>0.2705882352941177</legendTransparancy>
|
||||
<legendBorderType type="border" value="BorderLine"/>
|
||||
<legendPositionType type="position" value="PositionNorthEast"/>
|
||||
<timeSliderVisible>true</timeSliderVisible>
|
||||
<timeSliderAbove>false</timeSliderAbove>
|
||||
<valueSliderVisible>true</valueSliderVisible>
|
||||
<valueSliderLeft>false</valueSliderLeft>
|
||||
<xAxisReversed>false</xAxisReversed>
|
||||
<yAxisReversed>false</yAxisReversed>
|
||||
<projectorReversed>false</projectorReversed>
|
||||
<scalingFonts>false</scalingFonts>
|
||||
<maximumPens>5</maximumPens>
|
||||
<pensPerPack>0</pensPerPack>
|
||||
<triggerPen>0</triggerPen>
|
||||
<timeAxisVisible>true</timeAxisVisible>
|
||||
<timeAxisMajorTickVisible>true</timeAxisMajorTickVisible>
|
||||
<timeAxisMinorTickVisible>false</timeAxisMinorTickVisible>
|
||||
<timeAxisColor type="colorSet" r="0" g="0" b="0"/>
|
||||
<timeAxisFont type="font" name="Tahoma" size="11" underline="false" strikethrough="false"/>
|
||||
<timeAxisLabelColor type="colorSet" r="0" g="0" b="0"/>
|
||||
<timeAxisLabelVisible>true</timeAxisLabelVisible>
|
||||
<timeAxisLongLabelVisible>true</timeAxisLongLabelVisible>
|
||||
<timeAxisLabelRotation>0</timeAxisLabelRotation>
|
||||
<timeAxisTitle/>
|
||||
<timeAxisTitleRotation>0</timeAxisTitleRotation>
|
||||
<timeAxisTitlePlacement>50</timeAxisTitlePlacement>
|
||||
<timeAxisMajorGridVisible>true</timeAxisMajorGridVisible>
|
||||
<timeAxisMajorGridColor type="colorSet" r="192" g="192" b="192"/>
|
||||
<timeAxisMajorGridStroke type="stroke" width="1.0" endCap="butt" lineJoin="bevel"/>
|
||||
<timeAxisMinorGridVisible>false</timeAxisMinorGridVisible>
|
||||
<timeAxisMinorGridColor type="colorSet" r="192" g="192" b="192"/>
|
||||
<timeAxisMinorGridStroke type="stroke" width="1.0" endCap="butt" lineJoin="bevel"/>
|
||||
<headerText/>
|
||||
<headerColor type="colorSet" r="0" g="0" b="0"/>
|
||||
<headerFont type="font" name="Tahoma" size="11" underline="false" strikethrough="false"/>
|
||||
<headerJustification type="jTextJustification" value="TextJustificationLeft"/>
|
||||
<footerText/>
|
||||
<footerColor type="colorSet" r="0" g="0" b="0"/>
|
||||
<footerFont type="font" name="Tahoma" size="11" underline="false" strikethrough="false"/>
|
||||
<footerJustification type="jTextJustification" value="TextJustificationLeft"/>
|
||||
<enterprisePrimarySourceLocation type="nodeName" node="$default$"/>
|
||||
<enterpriseSecondarySourceLocation type="nodeName" node="$default$"/>
|
||||
<enterprisePrimaryHistoryLocation type="nodeName" node="$default$"/>
|
||||
<enterpriseSecondaryHistoryLocation type="nodeName" node="$default$"/>
|
||||
<updateFromHistory>true</updateFromHistory>
|
||||
<useSampleInterval>true</useSampleInterval>
|
||||
<sampleInterval>0</sampleInterval>
|
||||
<optimised>true</optimised>
|
||||
<chartProtection type="protection" active="false" password="">
|
||||
<userProtection type="userProtection" user=""/>
|
||||
</chartProtection>
|
||||
<pen type="pen">
|
||||
<type>256</type>
|
||||
<color type="colorSet" r="65" g="105" b="225"/>
|
||||
<stroke type="stroke" width="1.5"/>
|
||||
<paint>@NULL</paint>
|
||||
<visible>true</visible>
|
||||
<visibleLegend>true</visibleLegend>
|
||||
<source type="sourceID" uri="ci:/item/CI-Eng-Sample.TANK1.LEVEL?historygroup=CIENG_SCAN10S"/>
|
||||
<axisVisible>false</axisVisible>
|
||||
<axisPosition>0</axisPosition>
|
||||
<labelVisible>true</labelVisible>
|
||||
<majorTickVisible>true</majorTickVisible>
|
||||
<minorTickVisible>true</minorTickVisible>
|
||||
<axisColor>@NULL</axisColor>
|
||||
<labelColor>@NULL</labelColor>
|
||||
<scaleRangeType>0</scaleRangeType>
|
||||
<minimum>NaN</minimum>
|
||||
<maximum>NaN</maximum>
|
||||
<procentual>false</procentual>
|
||||
<title/>
|
||||
<description>Tank 1 level (%)</description>
|
||||
<legendText/>
|
||||
<titlePlacement>0</titlePlacement>
|
||||
<titleRotation>0</titleRotation>
|
||||
<labelRotation>0</labelRotation>
|
||||
<majorGridVisible>false</majorGridVisible>
|
||||
<minorGridVisible>false</minorGridVisible>
|
||||
<lowHighLimitGridVisible>false</lowHighLimitGridVisible>
|
||||
<lowHighLimitGridAreaVisible>false</lowHighLimitGridAreaVisible>
|
||||
<lowLowHighHighLimitGridVisible>false</lowLowHighHighLimitGridVisible>
|
||||
<majorGridColor>@NULL</majorGridColor>
|
||||
<minorGridColor>@NULL</minorGridColor>
|
||||
<lowHighLimitGridColor>@NULL</lowHighLimitGridColor>
|
||||
<lowHighLimitGridAreaColor>@NULL</lowHighLimitGridAreaColor>
|
||||
<lowLowHighHighLimiGridColor>@NULL</lowLowHighHighLimiGridColor>
|
||||
<majorGridStroke type="stroke" width="0.1"/>
|
||||
<minorGridStroke type="stroke" width="0.1"/>
|
||||
<lowHighLimitGridStroke type="stroke" width="0.1"/>
|
||||
<lowLowHighHighLimiGridStroke type="stroke" width="0.1"/>
|
||||
<lowLimit>20.0</lowLimit>
|
||||
<highLimit>80.0</highLimit>
|
||||
<lowLowLimit>10.0</lowLowLimit>
|
||||
<highHighLimit>90.0</highHighLimit>
|
||||
<annotationVisible>false</annotationVisible>
|
||||
<timeShift>0</timeShift>
|
||||
</pen>
|
||||
<pen type="pen">
|
||||
<type>256</type>
|
||||
<color type="colorSet" r="241" g="76" b="20"/>
|
||||
<stroke type="stroke" width="1.5"/>
|
||||
<paint>@NULL</paint>
|
||||
<visible>true</visible>
|
||||
<visibleLegend>true</visibleLegend>
|
||||
<source type="sourceID" uri=""/>
|
||||
<axisVisible>false</axisVisible>
|
||||
<axisPosition>0</axisPosition>
|
||||
<labelVisible>true</labelVisible>
|
||||
<majorTickVisible>true</majorTickVisible>
|
||||
<minorTickVisible>true</minorTickVisible>
|
||||
<axisColor>@NULL</axisColor>
|
||||
<labelColor>@NULL</labelColor>
|
||||
<scaleRangeType>0</scaleRangeType>
|
||||
<minimum>NaN</minimum>
|
||||
<maximum>NaN</maximum>
|
||||
<procentual>false</procentual>
|
||||
<title/>
|
||||
<description/>
|
||||
<legendText/>
|
||||
<titlePlacement>0</titlePlacement>
|
||||
<titleRotation>0</titleRotation>
|
||||
<labelRotation>0</labelRotation>
|
||||
<majorGridVisible>false</majorGridVisible>
|
||||
<minorGridVisible>false</minorGridVisible>
|
||||
<lowHighLimitGridVisible>false</lowHighLimitGridVisible>
|
||||
<lowHighLimitGridAreaVisible>false</lowHighLimitGridAreaVisible>
|
||||
<lowLowHighHighLimitGridVisible>false</lowLowHighHighLimitGridVisible>
|
||||
<majorGridColor>@NULL</majorGridColor>
|
||||
<minorGridColor>@NULL</minorGridColor>
|
||||
<lowHighLimitGridColor>@NULL</lowHighLimitGridColor>
|
||||
<lowHighLimitGridAreaColor>@NULL</lowHighLimitGridAreaColor>
|
||||
<lowLowHighHighLimiGridColor>@NULL</lowLowHighHighLimiGridColor>
|
||||
<majorGridStroke type="stroke" width="0.1"/>
|
||||
<minorGridStroke type="stroke" width="0.1"/>
|
||||
<lowHighLimitGridStroke type="stroke" width="0.1"/>
|
||||
<lowLowHighHighLimiGridStroke type="stroke" width="0.1"/>
|
||||
<lowLimit>NaN</lowLimit>
|
||||
<highLimit>NaN</highLimit>
|
||||
<lowLowLimit>NaN</lowLowLimit>
|
||||
<highHighLimit>NaN</highHighLimit>
|
||||
<annotationVisible>false</annotationVisible>
|
||||
<timeShift>0</timeShift>
|
||||
</pen>
|
||||
<pen type="pen">
|
||||
<type>256</type>
|
||||
<color type="colorSet" r="127" g="255" b="0"/>
|
||||
<stroke type="stroke" width="1.5"/>
|
||||
<paint>@NULL</paint>
|
||||
<visible>true</visible>
|
||||
<visibleLegend>true</visibleLegend>
|
||||
<source type="sourceID" uri=""/>
|
||||
<axisVisible>false</axisVisible>
|
||||
<axisPosition>0</axisPosition>
|
||||
<labelVisible>true</labelVisible>
|
||||
<majorTickVisible>true</majorTickVisible>
|
||||
<minorTickVisible>true</minorTickVisible>
|
||||
<axisColor>@NULL</axisColor>
|
||||
<labelColor>@NULL</labelColor>
|
||||
<scaleRangeType>0</scaleRangeType>
|
||||
<minimum>NaN</minimum>
|
||||
<maximum>NaN</maximum>
|
||||
<procentual>false</procentual>
|
||||
<title/>
|
||||
<description/>
|
||||
<legendText/>
|
||||
<titlePlacement>0</titlePlacement>
|
||||
<titleRotation>0</titleRotation>
|
||||
<labelRotation>0</labelRotation>
|
||||
<majorGridVisible>false</majorGridVisible>
|
||||
<minorGridVisible>false</minorGridVisible>
|
||||
<lowHighLimitGridVisible>false</lowHighLimitGridVisible>
|
||||
<lowHighLimitGridAreaVisible>false</lowHighLimitGridAreaVisible>
|
||||
<lowLowHighHighLimitGridVisible>false</lowLowHighHighLimitGridVisible>
|
||||
<majorGridColor>@NULL</majorGridColor>
|
||||
<minorGridColor>@NULL</minorGridColor>
|
||||
<lowHighLimitGridColor>@NULL</lowHighLimitGridColor>
|
||||
<lowHighLimitGridAreaColor>@NULL</lowHighLimitGridAreaColor>
|
||||
<lowLowHighHighLimiGridColor>@NULL</lowLowHighHighLimiGridColor>
|
||||
<majorGridStroke type="stroke" width="0.1"/>
|
||||
<minorGridStroke type="stroke" width="0.1"/>
|
||||
<lowHighLimitGridStroke type="stroke" width="0.1"/>
|
||||
<lowLowHighHighLimiGridStroke type="stroke" width="0.1"/>
|
||||
<lowLimit>NaN</lowLimit>
|
||||
<highLimit>NaN</highLimit>
|
||||
<lowLowLimit>NaN</lowLowLimit>
|
||||
<highHighLimit>NaN</highHighLimit>
|
||||
<annotationVisible>false</annotationVisible>
|
||||
<timeShift>0</timeShift>
|
||||
</pen>
|
||||
<pen type="pen">
|
||||
<type>256</type>
|
||||
<color type="colorSet" r="0" g="0" b="139"/>
|
||||
<stroke type="stroke" width="1.5"/>
|
||||
<paint>@NULL</paint>
|
||||
<visible>true</visible>
|
||||
<visibleLegend>true</visibleLegend>
|
||||
<source type="sourceID" uri=""/>
|
||||
<axisVisible>false</axisVisible>
|
||||
<axisPosition>0</axisPosition>
|
||||
<labelVisible>true</labelVisible>
|
||||
<majorTickVisible>true</majorTickVisible>
|
||||
<minorTickVisible>true</minorTickVisible>
|
||||
<axisColor>@NULL</axisColor>
|
||||
<labelColor>@NULL</labelColor>
|
||||
<scaleRangeType>0</scaleRangeType>
|
||||
<minimum>NaN</minimum>
|
||||
<maximum>NaN</maximum>
|
||||
<procentual>false</procentual>
|
||||
<title/>
|
||||
<description/>
|
||||
<legendText/>
|
||||
<titlePlacement>0</titlePlacement>
|
||||
<titleRotation>0</titleRotation>
|
||||
<labelRotation>0</labelRotation>
|
||||
<majorGridVisible>false</majorGridVisible>
|
||||
<minorGridVisible>false</minorGridVisible>
|
||||
<lowHighLimitGridVisible>false</lowHighLimitGridVisible>
|
||||
<lowHighLimitGridAreaVisible>false</lowHighLimitGridAreaVisible>
|
||||
<lowLowHighHighLimitGridVisible>false</lowLowHighHighLimitGridVisible>
|
||||
<majorGridColor>@NULL</majorGridColor>
|
||||
<minorGridColor>@NULL</minorGridColor>
|
||||
<lowHighLimitGridColor>@NULL</lowHighLimitGridColor>
|
||||
<lowHighLimitGridAreaColor>@NULL</lowHighLimitGridAreaColor>
|
||||
<lowLowHighHighLimiGridColor>@NULL</lowLowHighHighLimiGridColor>
|
||||
<majorGridStroke type="stroke" width="0.1"/>
|
||||
<minorGridStroke type="stroke" width="0.1"/>
|
||||
<lowHighLimitGridStroke type="stroke" width="0.1"/>
|
||||
<lowLowHighHighLimiGridStroke type="stroke" width="0.1"/>
|
||||
<lowLimit>NaN</lowLimit>
|
||||
<highLimit>NaN</highLimit>
|
||||
<lowLowLimit>NaN</lowLowLimit>
|
||||
<highHighLimit>NaN</highHighLimit>
|
||||
<annotationVisible>false</annotationVisible>
|
||||
<timeShift>0</timeShift>
|
||||
</pen>
|
||||
<pen type="pen">
|
||||
<type>256</type>
|
||||
<color type="colorSet" r="199" g="9" b="16"/>
|
||||
<stroke type="stroke" width="1.5"/>
|
||||
<paint>@NULL</paint>
|
||||
<visible>true</visible>
|
||||
<visibleLegend>true</visibleLegend>
|
||||
<source type="sourceID" uri=""/>
|
||||
<axisVisible>false</axisVisible>
|
||||
<axisPosition>0</axisPosition>
|
||||
<labelVisible>true</labelVisible>
|
||||
<majorTickVisible>true</majorTickVisible>
|
||||
<minorTickVisible>true</minorTickVisible>
|
||||
<axisColor>@NULL</axisColor>
|
||||
<labelColor>@NULL</labelColor>
|
||||
<scaleRangeType>0</scaleRangeType>
|
||||
<minimum>NaN</minimum>
|
||||
<maximum>NaN</maximum>
|
||||
<procentual>false</procentual>
|
||||
<title/>
|
||||
<description/>
|
||||
<legendText/>
|
||||
<titlePlacement>0</titlePlacement>
|
||||
<titleRotation>0</titleRotation>
|
||||
<labelRotation>0</labelRotation>
|
||||
<majorGridVisible>false</majorGridVisible>
|
||||
<minorGridVisible>false</minorGridVisible>
|
||||
<lowHighLimitGridVisible>false</lowHighLimitGridVisible>
|
||||
<lowHighLimitGridAreaVisible>false</lowHighLimitGridAreaVisible>
|
||||
<lowLowHighHighLimitGridVisible>false</lowLowHighHighLimitGridVisible>
|
||||
<majorGridColor>@NULL</majorGridColor>
|
||||
<minorGridColor>@NULL</minorGridColor>
|
||||
<lowHighLimitGridColor>@NULL</lowHighLimitGridColor>
|
||||
<lowHighLimitGridAreaColor>@NULL</lowHighLimitGridAreaColor>
|
||||
<lowLowHighHighLimiGridColor>@NULL</lowLowHighHighLimiGridColor>
|
||||
<majorGridStroke type="stroke" width="0.1"/>
|
||||
<minorGridStroke type="stroke" width="0.1"/>
|
||||
<lowHighLimitGridStroke type="stroke" width="0.1"/>
|
||||
<lowLowHighHighLimiGridStroke type="stroke" width="0.1"/>
|
||||
<lowLimit>NaN</lowLimit>
|
||||
<highLimit>NaN</highLimit>
|
||||
<lowLowLimit>NaN</lowLowLimit>
|
||||
<highHighLimit>NaN</highHighLimit>
|
||||
<annotationVisible>false</annotationVisible>
|
||||
<timeShift>0</timeShift>
|
||||
</pen>
|
||||
<penPanelLayout type="xyPenPanelLayout">
|
||||
<Height>417</Height>
|
||||
<AutoSize>true</AutoSize>
|
||||
<SplitLocation>-1</SplitLocation>
|
||||
<column index="0" visible="true" width="20"/>
|
||||
<column index="1" visible="true" width="20"/>
|
||||
<column index="2" visible="true" width="150"/>
|
||||
<column index="3" visible="true" width="120"/>
|
||||
<column index="4" visible="true" width="60"/>
|
||||
<column index="5" visible="false" width="120"/>
|
||||
<column index="6" visible="false" width="120"/>
|
||||
<column index="7" visible="false" width="60"/>
|
||||
<column index="8" visible="true" width="60"/>
|
||||
<column index="9" visible="true" width="60"/>
|
||||
<column index="10" visible="false" width="20"/>
|
||||
<column index="11" visible="true" width="90"/>
|
||||
<column index="12" visible="false" width="130"/>
|
||||
<column index="13" visible="true" width="200"/>
|
||||
<column index="14" visible="false" width="240"/>
|
||||
<column index="15" visible="false" width="280"/>
|
||||
</penPanelLayout>
|
||||
<timeRange type="timeRangeLast" count="1">
|
||||
<type type="timeUnit" value="TimeUnitHour"/>
|
||||
</timeRange>
|
||||
<updateInterval>30</updateInterval>
|
||||
<fillHistory>true</fillHistory>
|
||||
<updating>false</updating>
|
||||
</chartPanel>
|
||||
</config>
|
||||
<x>472.0</x>
|
||||
<y>588.0</y>
|
||||
<top>172.0</top>
|
||||
<bottom>172.0</bottom>
|
||||
<left>344.0</left>
|
||||
<right>344.0</right>
|
||||
<rotation>0.0</rotation>
|
||||
<shear>0.0</shear>
|
||||
<data type="data">
|
||||
<action type="actionInternalServiced"/>
|
||||
<action type="actionConnectTo">
|
||||
<property type="property" name="chart.attribute[00]"/>
|
||||
<filter type="filter">
|
||||
<value>0.0</value>
|
||||
</filter>
|
||||
<connection type="connection">
|
||||
<itemName>CI-Eng-Sample.TANK1.LEVEL</itemName>
|
||||
<itemId>1.1.268.0.0.1.1.7</itemId>
|
||||
<itemAttribute>ItemValue</itemAttribute>
|
||||
</connection>
|
||||
</action>
|
||||
</data>
|
||||
</chart>
|
||||
</coreObjectDefinition>
|
||||
</visualization>
|
||||
|
|
@ -1,10 +0,0 @@
|
|||
@echo off
|
||||
rem Deploy the CI-Eng-Sample displays into the operator interface (deployment DEPLOY).
|
||||
rem CI Server R1.03.00. Load the sample (load.cmd) first; no admin rights needed.
|
||||
rem Copies the display XML, then creates the HTML (Mobile Operator) version with jwuiutl;
|
||||
rem without -o the HTML goes to %TLS_WAP_PATH%\mobileoperator\operatorInterfaces\DEPLOY.
|
||||
cd /d "%~dp0"
|
||||
set WAP=%TLS_WAP_PATH%
|
||||
if not defined TLS_WAP_PATH set WAP=C:\Users\Public\Yokogawa\tls\wap
|
||||
copy /y CIENG_Tank.xml "%WAP%\cfg\operatorInterfaces\DEPLOY\displays\"
|
||||
call jwuiutl.cmd -e HTML -i -f DEPLOY CIENG_Tank
|
||||
|
|
@ -1,7 +0,0 @@
|
|||
@echo off
|
||||
rem Remove the CI-Eng-Sample displays (operator interface and HTML version). CI Server R1.03.00.
|
||||
rem Close CIENG_Tank in the Edit Module first.
|
||||
set WAP=%TLS_WAP_PATH%
|
||||
if not defined TLS_WAP_PATH set WAP=C:\Users\Public\Yokogawa\tls\wap
|
||||
del /q "%WAP%\cfg\operatorInterfaces\DEPLOY\displays\CIENG_Tank.xml"
|
||||
del /q "%WAP%\mobileoperator\operatorInterfaces\DEPLOY\displays\CIENG_Tank.html"
|
||||
|
|
@ -60,4 +60,3 @@ development system (see "Test system" in `progress.md`); they do not exist on ot
|
|||
| ISS-038 | 2026-10-01 | HISTORY (`ithloahis` + rollover) | An `ithloahis` sample that was dropped (dated 11:50, before the active unit) still became the **initial value** of the next unit: after a forced rollover at 12:05:26 `ITEM_HISTORY` shows `CI-Eng-Sample.TANK1.INFLOW` = 95 (`INITIAL_VALUE` 1) although the item's value was 112. History after loading old samples can therefore show a wrong value at the next rollover. | open | Accept as a caution (documented in `load-history.md`), or retest after a CI Server restart to see whether the wrong initial value persists. | `.claude/skills/system-management/tasks/load-history.md`; `knowledge/manuals/IM36K10C40-01EN.md` §3 |
|
||||
| ISS-039 | 2026-10-01 | HISTORY (setup) | Installed vs manuals: `hisdbg` menu runs to option 22 (manual text: `-1 - 10`, list to 22) and lists history types 4 (`STATION_STAT`) and 36 (`SYS_LOG`) not in IM 36K10L20 §3.1; `ithsag.sup` keyword `run_interval` (manual: *Heartbeat*) and `queue_size` 500 KB (manual default 200); the option-type table in IM 36K10L20 §3.1 is garbled in the PDF (observed: Scan/Time `1 1`, Event/Item `2 2`, Aggregation `4 4`). | open | Installed software is the reference (standing user decision). Close when the user confirms. | `knowledge/manuals/IM36K10L20-01EN.md` §3; `knowledge/manuals/IM36K10C40-01EN.md` §2 |
|
||||
| ISS-040 | 2026-10-01 | HISTORY (aggregation) | Aggregation group `CIENG_AGG` (30 min + hour, `TANK1.LEVEL` max/min/avg) ran (`ithsag.log`: *Aggregation Completed*) but stored no values: retrieval gave `0x09 = ITM error` per period. `TANK1.LEVEL` was in `CIENG_EVENT` and `CIENG_SCAN10S`, both priority 0. Also `INTERPOLATION = "30 minutes"` is refused by `dssqld`; the installed name is `30Minutes`. | closed | Closed 2026-10-01 (confirmed by user). 2026-10-01 14:02: after `CIENG_SCAN10S` got `PRIORITY` 10, the 13:30–14:00 period stored max 77, min 33, avg 52.7, quality 1000 (`ithdbg` 20 and `dssqld` with `INTERPOLATION = "30Minutes"`). Cause: equal source priorities (C40 §2.1 says the highest-priority group is the source, but not that a tie gives nothing). Sample fixed (priority 10). The hourly value for 13:00–14:00 was not stored (first half had no source); not rechecked. Proposed close. | `.claude/skills/history-management/tasks/storage-groups.md` §4 (done); `knowledge/manuals/IM36K10C40-01EN.md` §3 (done); `examples/CI-Eng-Sample/03_his_group_df.qli`, `README.md` (done) |
|
||||
| ISS-041 | 2026-10-01 | GRAPHICS (HTML trend) | In the HTML display (`localhost:8080/mobileoperator/?d=CIENG_Tank`) the trend shows the pen legend `CI-Eng-Sample.TANK1.LEVEL [CIENG_SCAN10S]` and time axis but draws no line, although `ITEM_HISTORY` has 420 samples in the shown hour. Browser console: `Mismatch between number of labels (Time,CI-Eng-Sample.TANK1.LEVEL [CIENG_SCAN10S]) and number of columns in array (51)`. The trend has 4 further empty pens. | open | Check the same display in CI View (Java operator interface); try a trend with only one pen (remove the empty ones) or a Micro Trend; check the HTML-supported trend properties (IM 36K10R30 §4.8.7). | `.claude/skills/graphics/tasks/create-display.md`; `knowledge/manuals/IM36K10R30-01EN.md` §4 |
|
||||
|
|
|
|||
|
|
@ -1,98 +0,0 @@
|
|||
---
|
||||
manual: IM 36K10C50-01EN
|
||||
title: Edit Module
|
||||
edition: 3rd Edition, Sep. 2023
|
||||
version: R1.03
|
||||
status: display CIENG_Tank built by the user in the Edit Module (text, number field, alarm overview, trend) and checked as XML and HTML 2026-10-01; jwuiutl search, validate and HTML export verified; other components, symbols, actions and the tutorial from docs
|
||||
---
|
||||
|
||||
# Edit Module (R1.03)
|
||||
|
||||
The Edit Module draws displays and symbols for the operator interface (CI View) and the HTML
|
||||
display. Displays are XML files (`IM36K10R30-01EN.md` §1). Section numbers refer to the manual.
|
||||
|
||||
## 1. Window and files (§1)
|
||||
|
||||
- Window: sheets, component bar, graphic sheet, symbols sheet, menu, toolbar, edit area.
|
||||
- *File > New Display* (Ctrl+N), *New Symbol* (Ctrl+Shift+N), *Save* (Ctrl+S), *Save with
|
||||
Revision Information* (who/when/why, kept in `revisionHistory`), *Save As*, *Save Selection
|
||||
as* (new symbol or display), print area, print. Open displays are locked (`<name>.lck`);
|
||||
autosave writes `<name>.xml.autosave`.
|
||||
- *Edit > Find* searches the open display; `jwuiutl -m` searches all.
|
||||
- **HTML display** check box (new display dialog / display properties): the editor then offers
|
||||
only HTML-supported components, properties and actions, and saving also writes the HTML file.
|
||||
HTML mode can be switched off later. Not for enterprise displays. The tab icon shows normal /
|
||||
HTML / HTML with unsupported content.
|
||||
- Localisation: *Tools > Configure Localization* → *Extract Text*, add locale, translate;
|
||||
global and per-file tables; the operator's locale decides.
|
||||
- *Playback > Record* records operator/editor sessions; *Open viewer* plays them back.
|
||||
|
||||
## 2. `jwuiutl` — batch operations (§1.5)
|
||||
|
||||
`jwuiutl.cmd` (in `tls\com`, Java; runs from a normal prompt):
|
||||
|
||||
| Option | Use |
|
||||
|---|---|
|
||||
| `-d` / `-s` | Only displays / only symbols (`-p <palette>`, `-g <group>`) |
|
||||
| `-v` | Validate (connected items exist, components defined); report only. `-l <file>` writes the result, `-i` shows progress (`Validating <name>` / `Info: No problems found`) |
|
||||
| `-vf` | Force validation and **save** every display/symbol |
|
||||
| `-u` | Unlock locked files (`.lck` left by a crashed editor) |
|
||||
| `-c` / `-a` | Clean up temporary files / validate + unlock + clean up |
|
||||
| `-m <terms>` / `-M <terms>` | Print matching components (CSV) / with actions and properties |
|
||||
| `-e HTML [-o <dir>] [-f <deployment>] [<display>]` | Export HTML displays |
|
||||
| `-b`, `-z`, `-h true/false` | Also save `.xml.bin` (faster loading) / compressed / set HTML mode |
|
||||
| `-un`, `-pw` | User for enterprise displays |
|
||||
|
||||
**Verified on the test system:** `-d -m TANK1` and `-d -v -i -l` ran without errors; locked
|
||||
displays and displays saved by a newer version are skipped (`*** Display locked <name>`,
|
||||
`… created with a newer version of CI Server (R1.04.0.0)`); `-e HTML -i -f DEPLOY CIENG_Tank`
|
||||
wrote `mobileoperator\operatorInterfaces\DEPLOY\displays\CIENG_Tank.html`.
|
||||
|
||||
## 3. Components (§2)
|
||||
|
||||
Shapes (rectangle, ellipse, arc, polygon, spline, line, links), text / text field / text area
|
||||
/ password field, number and number field, icon, rectangular and circular scales, radial, data
|
||||
bar, spinner, slider, push/toggle button, check box, radio button, combo box, list box, date
|
||||
and time field, **alarm overview** (current/historical; acknowledge, block, shelve, link display,
|
||||
export; dialog tabs Types, Columns, Filter, Alarm link display, Appearance, Header and footer,
|
||||
Fetching, Alarm Shelving, Enterprise, Advanced, Attributes), list of blocked items, alarm
|
||||
sound, dataset tables (view/edit dataset records), report, **trend** (pens on items with
|
||||
history; shows limits; time slider and controls; definitions can be saved from the operator
|
||||
interface), DTS trend, micro trend, playback indicator, calculation/function, JavaScript
|
||||
function, web browser, PDF viewer, navigation tree, display generator, map viewer.
|
||||
|
||||
## 4. Sheets (§4)
|
||||
|
||||
Visualization (displays/symbols tree), zoom, visibility groups (shown by zoom factor),
|
||||
**parameters** (default read-only ones such as `name`, `attachedObject`, `client`, `server`,
|
||||
`mouseX`; user-defined with scope; `$name` in command lines), messages, symbols, **properties**
|
||||
(connect a property to an item attribute, parameter or dataset field; linear transformations;
|
||||
writable properties: value, item name parts, id, units, description, status number/text,
|
||||
control status, option bits), layers, attributes, edit history (undo/redo), **actions** (open /
|
||||
close display, execute command, read/write parameters; triggered by component events).
|
||||
|
||||
## 5. Symbols (§5)
|
||||
|
||||
*File > New Symbol*; put it on a palette (attributes sheet); external user-defined parameters
|
||||
become properties of each instance; after changing a symbol run *Tools > Validate all
|
||||
Symbols* and *Validate all Displays* (with all tabs closed); a symbol can be linked to a
|
||||
PROCESS Service class so each instance shows one object; data location (display, operator's
|
||||
CI Portal, display's server, enterprise, node).
|
||||
|
||||
## 6. What the display file stores (verified with CIENG_Tank)
|
||||
|
||||
- `<coreObjectDefinition type="displayDefinition">` with `<html>true</html>`, `<width>`,
|
||||
`<height>`, grid, revision history, visibility groups, layers.
|
||||
- Components as elements (`text`, `numberField`, `alarmOverview`, `chart` = trend).
|
||||
- Item connections in `<globalSection>`: `<itemName>CI-Eng-Sample.TANK1.LEVEL</itemName>` **and**
|
||||
`<itemId>1.1.248.0.0.1.1.7</itemId>`. Trend pens: `<source uri="ci:/item/<item>"/>`; a new
|
||||
trend has 5 empty pens.
|
||||
- **After a sample remove/reload the item got id 268** while the file kept 248: `jwuiutl -v` still
|
||||
reported *No problems found*, and a newly opened session showed the live value — the name is
|
||||
what counts. Sessions that were already open kept the old binding (value frozen) until the
|
||||
display was opened in a new session.
|
||||
|
||||
## 7. Tutorial (§6)
|
||||
|
||||
Builds wheels, faceplates, valve symbols, indicators, PID faceplates with mode and setpoint
|
||||
dialogs, scales, limit colours, tag info and pinning buttons — a guided exercise in the GUI.
|
||||
|
|
@ -1,54 +0,0 @@
|
|||
---
|
||||
manual: IM 36K10C60-01EN
|
||||
title: Advanced Operating Graphics
|
||||
edition: 3rd Edition, Sep. 2023
|
||||
version: R1.03
|
||||
status: from docs; installed AOG displays checked read-only (DEPLOY\displays, mobileoperator) 2026-10-01
|
||||
---
|
||||
|
||||
# Advanced Operating Graphics — AOG library (R1.03)
|
||||
|
||||
A ready-made library of symbols and displays in a consistent, high-performance HMI style,
|
||||
used from the Edit Module's Visualization sheet. Section numbers refer to the manual.
|
||||
|
||||
## 1. Symbols (§1.1)
|
||||
|
||||
| Kind | Purpose | Palettes / examples |
|
||||
|---|---|---|
|
||||
| Equipment symbols | Static equipment, no live data | `AOG_ContainersAndVessels` (AOG_Tank, AOG_Vessel, AOG_Reactor, …), `AOG_HeatTransfer`, `AOG_Indicator`, `AOG_MaterialHandling`, `AOG_Mixing`, `AOG_Rotating` (pumps, compressors, turbine), `AOG_Separators`, `AOG_ValvesAndActuators`, `AOG_Electrical`, `AOG_Filters`, `AOG_Others` (Yokogawa systems such as AOG_CentumFCS, AOG_ProsafeRS, AOG_StardomFCN, AOG_FAM3, AOG_DTS; field devices; stations) |
|
||||
| Item symbols | Show and change one or more item attributes | indicators (bar, needle, circular, radial, number, text, on/off, manual, alarm, trend), valves (2-way, 3-way, on/off), selection box, name/info |
|
||||
| Object symbols (`AOG_O…`) | Same, driven by PROCESS Service object signals | e.g. `AOG_ONumberIndicator`, `AOG_OHorizontalBarIndicator` |
|
||||
| Navigation symbol, components | Navigation between displays | |
|
||||
|
||||
## 2. Displays (§1.2)
|
||||
|
||||
Standard displays: `AOG_Default`, `AOG_DisplayTemplate` (start for new displays), `AOG_Style`
|
||||
(global style parameters), `AOG_MenuMain`, alarm displays (`AOG_AlarmBanner`, `AOG_AlarmCurrent`,
|
||||
`AOG_AlarmHistory`, `AOG_AlarmShelved`), `AOG_AuditTrail`, `AOG_ItemFaceplate`,
|
||||
`AOG_ItemTuningPanel`, `AOG_ObjectFaceplate`, `AOG_ObjectTuningPanel`, `AOG_SetItemMode`,
|
||||
`AOG_SetObjectMode`, `AOG_SetNumberPV/SV/SL/SH/SLL/SHH`, `AOG_LockStatus`, `AOG_TrendOpen`,
|
||||
OPC UA method call displays; plus demo displays. **Installed**: these are in
|
||||
`DEPLOY\displays`, and the alarm, audit, default, menu, style, trend and UA method displays also
|
||||
exist as HTML displays.
|
||||
|
||||
## 3. Global style parameters (§1.1, §2.1.1)
|
||||
|
||||
Defined once on the `AOG_Style` display (*Parameters* tab) and used by all AOG symbols:
|
||||
colours (`AOG_C…`: alarm high/medium/low/diagnostic/off, display background, equipment
|
||||
running/off/not running, fluid and gas lines, indicator background/limit/normal/outline/signal,
|
||||
manual control, selector, text 1–4), strokes (`AOG_S…`), fonts (`AOG_FT1–4`), engineering unit
|
||||
texts (`AOG_EF1` flow, `AOG_EL1` level, `AOG_EP1` pressure, `AOG_ET1/2` temperature), on/off
|
||||
texts, `AOG_BlinkOnNotAcknowledged`. Changing a value changes every symbol that uses it.
|
||||
|
||||
## 4. Building an HMI (§2)
|
||||
|
||||
Edit Module → (optionally) adjust `AOG_Style` and save → *New display* or start from
|
||||
`AOG_DisplayTemplate` → place AOG symbols from the Visualization sheet → connect them to items
|
||||
or objects → save → open in the operator interface. New symbols can be made in the same style.
|
||||
|
||||
## 5. Enterprise (§3)
|
||||
|
||||
Enterprise displays and AOG item/object symbols for enterprise engineering (items/objects on
|
||||
several servers; locations chosen per symbol).
|
||||
|
||||
Not practiced: the sample display uses plain components; AOG symbols need the Edit Module GUI.
|
||||
|
|
@ -1,83 +0,0 @@
|
|||
---
|
||||
manual: IM 36K10R30-01EN
|
||||
title: Graphic Display Setup
|
||||
edition: 3rd Edition, Sep. 2023
|
||||
version: R1.03
|
||||
status: HTML display (Mobile Operator) verified with CI-Eng-Sample display CIENG_Tank 2026-10-01; layout file and form folders checked read-only; layout editing, dataset forms, form language and dual screen from docs
|
||||
---
|
||||
|
||||
# Graphic Display Setup (R1.03)
|
||||
|
||||
How the operator interface is framed (layouts), how custom dataset forms are added, and how
|
||||
displays run in a web browser (HTML display, "Mobile Operator"). Section numbers refer to the
|
||||
manual. Building displays: `IM36K10C50-01EN.md`; AOG library: `IM36K10C60-01EN.md`.
|
||||
|
||||
## 1. Files and folders (installed)
|
||||
|
||||
| What | Where (`%TLS_WAP_PATH%` = `C:\Users\Public\Yokogawa\tls\wap`) |
|
||||
|---|---|
|
||||
| Displays (operator interface) | `cfg\operatorInterfaces\DEPLOY\displays\<name>.xml` (plus `.lck` while open in the Edit Module, `.autosave`) |
|
||||
| Symbols | `cfg\operatorInterfaces\DEPLOY\symbols\` (≈ 3100 files incl. the AOG library) |
|
||||
| Layouts | `cfg\operatorInterfaces\DEPLOY\layouts\Layouts.xml` (+ `Layouts.readme`, `Layouts-original.xml`) |
|
||||
| Components, locales, thresholds | `cfg\operatorInterfaces\DEPLOY\components\`, `locales\`, `thresholds\` |
|
||||
| HTML displays | `mobileoperator\operatorInterfaces\DEPLOY\displays\<name>.html` |
|
||||
| Dataset forms | `cfg\dialog\dialogs\<name>Dia.xml` (components `<name>Com.xml`, definitions `JToolsGlobalDef.xml`); texts in `cfg\properties\` |
|
||||
|
||||
`DEPLOY` is the deployment name (a user's *Operator Interface Deployment* field selects another;
|
||||
empty = `deploy`).
|
||||
|
||||
## 2. Layouts (§1)
|
||||
|
||||
- `Layouts.xml` holds several `<layout>` elements under `<layouts>` (common options such as
|
||||
`debugActivationKey="CONTROL SHIFT F6"` for the graphics debugger, Java only). A layout =
|
||||
menu, toolbar, **frame set (required)**, status line.
|
||||
- Layout options: `name`, `icon`, `title` (`$<frame>` = title of the display in that frame),
|
||||
`drawBorder`, `sizingAllowed`, `minimizingAllowed`, `closingAllowed`, `alwaysOnTop`, `modal`,
|
||||
`lookAndFeel`, `initialPosition` (… `fitFrames`), `initialPositionX/Y`, `initialSize`,
|
||||
`initialSizeWidth/Height`, `maximumOpen`, print orientation and margins (Java only).
|
||||
- Menu items (§1.5, e.g. `menu.file.login`, `menu.view.reload`), toolbar (§1.6), status line
|
||||
items (§1.7, e.g. graphics queue level), frames and tabs (§1.8), translations (§1.9).
|
||||
- Which layout opens: *In layout* of an *Open display* action (Edit Module), or the user's
|
||||
*Layout* field (Engineering Module, Authorization > Users); empty = `default`.
|
||||
- Dual screen (§1.10): copy the layout and the banner display as `<name>_1` / `<name>_2` and let
|
||||
each banner open its main display in its own layout.
|
||||
- **Installed layouts**: `mobile`, `default`, `sxga1f/r`, `uxga1f/r`, `wxga1f/r`, `wsxga1f/r`,
|
||||
`wsxgap1f/r`, `wuxga1f/r`, `ResizablePopup`, `FixedPopup`, `popup`, `Splash`, `tuningpanel`,
|
||||
`faceplate`, `SelectMode`, `Setpoint`, `mapviewer` (`f` fixed / `r` resizable per screen
|
||||
size). The test system's `Layouts.xml` also has a custom layout added by the author; keep a copy
|
||||
of the original before editing.
|
||||
|
||||
## 3. Dataset forms (§2, §3)
|
||||
|
||||
Engineering-Module-style forms for operators: write `<name>Dia.xml` in `cfg\dialog\dialogs`
|
||||
(never change the existing forms there), optionally a property file per language, then place a
|
||||
*Dataset form* component on a display. Objects: `label`, `textField`, `checkBox`, `comboBox`,
|
||||
`panel`, `component` (`JhmiRecordNameCom`, `JhmiTreeComboBoxCom`, `JhmiSelectAvailableCom`,
|
||||
`JhmiTimeSelectorCom`); `meta` links an object to a dataset field: `field=`, `mixedValue=`,
|
||||
`choices=<dataset>[,<field>[,<filter>]]`, `none=`, `available=`/`selected=`, `label=`,
|
||||
`dateVisible=`, `visibility=`. Layout by `column`, `top="+"`, `right="*"`. Localisation via
|
||||
property files and language codes (§3.5).
|
||||
|
||||
## 4. HTML display / Mobile Operator (§4)
|
||||
|
||||
- Export: Edit Module saves the HTML version automatically when the display has **HTML
|
||||
display** ticked; or `jwuiutl -e HTML -i [-o <path>] [-f <deployment>] [<display>]` (without
|
||||
`-o` it writes into `mobileoperator\operatorInterfaces\<deployment>`). **Verified**: both give
|
||||
identical HTML (except a time stamp).
|
||||
- Open: `http(s)://<host>:8080|8443/mobileoperator?d=<display>&l=<layout>&u=<user>` or *Open* of
|
||||
*Mobile Operator* on the Remote Connect page. Login with a CI Server user (manual, or SSO via
|
||||
`https://<host>:8443/auth/mbl`); user profile fields used: password, authorization group, ASA,
|
||||
shelving group, process areas, logoff timeout, deployment, initial display, locale (layout
|
||||
not). Login control: `dssana.sup` interface *mobile operator*.
|
||||
- **Verified**: `http://localhost:8080/mobileoperator/?d=CIENG_Tank` showed the CI View-like
|
||||
frame (menu, navigation buttons, alarm banner, status line) and the display; the number field
|
||||
updated live; the alarm overview listed the sample's alarms. **Reloading the browser page ends
|
||||
the session** (login again); open other displays with the display box instead.
|
||||
- Differences from the Java operator interface (§4.7): layout windows live inside the browser
|
||||
window (no resizing of embedded layouts); displays need explicit width/height; names are
|
||||
case-sensitive; zoom and pan not supported; some mouse/keyboard events and actions missing;
|
||||
no enterprise displays. Components supported (§4.8): alarm overview, display, group, symbol,
|
||||
trend, visibility group/layer, parameters, web browser (with listed properties).
|
||||
- Full screen F11, Chrome shortcuts or `chrome.exe --app=http://<host>:<port>`.
|
||||
- **Test system**: the HTML trend of `CIENG_Tank` drew no line although history existed; browser
|
||||
console `Mismatch between number of labels … and number of columns in array (51)` (ISS-041).
|
||||
|
|
@ -53,9 +53,9 @@ AID is not needed.
|
|||
| 8 | IM 36K10E30 | Alarm System Performance Analysis | summarized, from docs (ASPA GUI not practiced; launcher and fetch limits checked) ([notes](manuals/IM36K10E30-01EN.md)) |
|
||||
| 9 | IM 36K10L20 | History Management Engineering | done for `hisdbg` checks, files and rollover; archive and repair utilities from docs ([notes](manuals/IM36K10L20-01EN.md)); skill `history-management` |
|
||||
| 9 | IM 36K10C40 | Engineering Module - Historical | done by quick load for Event/Item, Scan/Time and Aggregation groups (aggregation needs a higher-priority source group, ISS-040); archive from docs ([notes](manuals/IM36K10C40-01EN.md)) |
|
||||
| 10 | IM 36K10R30 | Graphic Display Setup | done for HTML display and folders; layouts, dataset forms, form language from docs ([notes](manuals/IM36K10R30-01EN.md)); skill `graphics` |
|
||||
| 10 | IM 36K10C50 | Edit Module | done for one display (built by the user) and `jwuiutl` validate/search/export; other components, symbols, actions from docs ([notes](manuals/IM36K10C50-01EN.md)) |
|
||||
| 10 | IM 36K10C60 | Advanced Operating Graphics | summarized, from docs (AOG displays checked read-only) ([notes](manuals/IM36K10C60-01EN.md)) |
|
||||
| 10 | IM 36K10R30 | Graphic Display Setup | not started |
|
||||
| 10 | IM 36K10C50 | Edit Module | not started |
|
||||
| 10 | IM 36K10C60 | Advanced Operating Graphics | not started |
|
||||
| 11 | IM 36K10L50 | Data Set Service Engineering | not started |
|
||||
| 11 | IM 36K10P30 | Data Set Service Language | not started |
|
||||
| 11 | IM 36K10P20 | Report Generation Language | not started |
|
||||
|
|
@ -107,7 +107,7 @@ now come before classes and objects (phase 6), and the other interfaces follow a
|
|||
| G10/C10 | Authorization group and user creation ([task](../.claude/skills/authorization/tasks/users-groups.md)) | passed | passed | Group `CIENG_VIEWER` (sample file `08_auth_group_df.qli`) loaded/removed by Claude; test user `CIENG_TEST` (no password) loaded by the user, checked and removed. The sample creates no users. |
|
||||
| C10 | String items: length 1–200, holds length − 1 characters ([task](../.claude/skills/item-engineering/tasks/string-items.md)) | passed | passed | Tested with temporary `CI-Eng-Sample.DEMO.STR*` items (removed): 201 rejected; too-long writes cut, status 12 OVERRANGED ([ISS-019](issues.md)). |
|
||||
| C10 | Integrator time unit: integration granule `itm_int_secs` in `itm.sup` ([task](../.claude/skills/item-engineering/tasks/sub-items.md)) | passed | passed | 60 → `RUN_SECONDS` +1 per minute; restored to 1 (file identical to backup), +1 per second again ([ISS-010](issues.md)). Elevated restarts run by the user. |
|
||||
| G10 | Displays, symbols, Operator Interface test | display done (phase 10); symbols not practiced | display added | Display `CIENG_Tank` built in the Edit Module and checked in the HTML display. |
|
||||
| G10 | Displays, symbols, Operator Interface test | not practiced | pending | GUI (Edit Module); phase 10. |
|
||||
| L41/C10 | Modbus TCP line, station, scan type, points, connected items by quick load ([task](../.claude/skills/equipment/tasks/modbus-station.md)) | passed | passed | Loopback to CI Server's own Modbus slave (`eqpmdcmem` + `eqpmdcslvtcp` on 5020, started by hand). Line load created and started `EQPCIENG`; removal stopped it and deleted its files. Write/read-back, off-scan/on-scan checked; full remove/reload from sample files. Protocol must be Open Modbus/TCP ([ISS-024](issues.md)). Mirror start files copied to `tls\com` by the user; after a restart everything came back under the CI Service and the setpoint was re-sent on connect. |
|
||||
| G10 | Alarms, reports, audit, RDBMS, history | alarms done (phase 8); others not practiced | alarms added | Covered in their own phases (7–12). |
|
||||
| R10/R20 | Read a setup file: active settings and keyword help ([task](../.claude/skills/portal-setup/tasks/read-setup-file.md)) | passed | n/a | Read-only. Compared with the Setup File Editor GUI for `wfla_display.sup`, `wflgdi.sup` and all 9 tabs of `jwuiisg.sup`: fields and values identical. Manual differences logged as ISS-012 to ISS-017 (installed software taken as the reference). |
|
||||
|
|
@ -130,6 +130,3 @@ now come before classes and objects (phase 6), and the other interfaces follow a
|
|||
| L20 | `hisdbg` read-only checks and forced rollover ([task](../.claude/skills/history-management/tasks/history-checks.md)) | passed | passed | 45 groups, 30 clients; group/unit info; rollover of `CIENG_EVENT` closed unit 3,1. Extra history types 4 and 36 (ISS-039). |
|
||||
| L20/L35 | `ithloahis` into older units ([task](../.claude/skills/system-management/tasks/load-history.md)) | passed | passed | Samples in the active unit or a unit closed after the restart stored; older ones dropped silently (ISS-006); dropped sample became the next unit's initial value (ISS-038). |
|
||||
| L20/C40 | Archive and retrieve, `hasdbg`, `hisrecover`, `hiswrn`, `hisrep` by hand | not practiced | n/a | No archive device configured (`has.sup`); would change history administration. |
|
||||
| C50 | Build a display in the Edit Module, check the XML ([task](../.claude/skills/graphics/tasks/create-display.md)) | passed | passed | User built `CIENG_Tank` (HTML mode): text, number field, alarm overview, trend. File stores item name + id; after a sample reload (id 248 → 268) validation still passed and a new session showed live values. |
|
||||
| C50/R30 | Deploy/remove, `jwuiutl` HTML export, validate, search; HTML display in the browser ([task](../.claude/skills/graphics/tasks/deploy-displays.md)) | passed | passed | Scripts `displays/deploy_displays.cmd` / `remove_displays.cmd`; command-line HTML identical to the Edit Module's. Number field live in the browser; HTML trend draws no line (ISS-041). Page reload ends the browser session. |
|
||||
| R30/C50/C60 | Layouts, dataset forms, symbols, actions, AOG library | not practiced | n/a | GUI work in the Edit Module; layouts are shared system files. |
|
||||
|
|
|
|||
Loading…