task: Choose what AUDIT Service stores (classifier STORAGE, AUDIT_INFO), define selection groups, run an event logger (ADTLOG) task: Choose what AUDIT Service stores (classifier STORAGE, AUDIT_INFO), define selection groups, run an event logger (ADTLOG)
version: R1.03 version: R1.03
source: IM 36K10L25-01EN §2.4, §3, §4.2, App. 1; practiced on CI-Eng-Sample 2026-10-01 source: IM 36K10L25-01EN §2.4, §3, §4.2, App. 1; practiced on CI-Eng-Sample 2026-10-01
status: verified (PROCESS-side ITEM.* events from docs) status: verified (operator-side ITEM.* value events from docs, ISS-049)
--- ---
# Configure the audit trail # Configure the audit trail
@ -33,17 +33,12 @@ switching anything off.
### Item option *Audit trailing wanted* (`AUDIT_INFO`) ### Item option *Audit trailing wanted* (`AUDIT_INFO`)
`ITEM_DF` / `SUB_ITEM_DF` / `EXTERNAL_ALARM_DF` field `AUDIT_INFO` (default 0). It switches the `ITEM_DF` / `SUB_ITEM_DF` / `EXTERNAL_ALARM_DF` field `AUDIT_INFO` (default 0). It did **not**
`ITEM.*` / `SUB-ITEM.*` events raised by ITEM Service for **operator writes**. Verified on change what the tested tools record: DSS and Engineering Module value writes are audited for all
`CI-Eng-Sample.PUMP1.MODE` with the buttons on display `CIENG_Tank`: items, `itmval -p` for none. It is meant for the `ITEM.*` / `SUB-ITEM.*` classifiers (value,
- `AUDIT_INFO` 1: a button write 0 → 1 stored `ITEM` `VALUE` `MODIFY` `OPER-INTERFACE`, user status, limits) raised by ITEM Service for operator and PROCESS writes; PROCESS (`COMPUTE`) also
`ADMIN`, old 0 / new 1, plus `ITEM` `STATUS` `MODIFY` (13 → 9). needs `AUDIT = YES` in `tls\sup\opc.sup` (installed `NO`) and its classifiers are off by default.
- `AUDIT_INFO` 0: the write 1 → 0 left **no** audit record. Not verified (ISS-049).
It does not affect DSS writes (`dssqld`, Engineering Module: always audited as `ITEM_VAL`
dataset events) or `itmval -p` (never audited). Sample: `19b_audit_item_df.qli` (`dssqld -m`,
`NAME,AUDIT_INFO`). PROCESS writes (`COMPUTE`) also need `AUDIT = YES` in `tls\sup\opc.sup`
(installed `NO`) and their classifiers are off by default; not tested.
## 2. Selection groups ## 2. Selection groups

View file

@ -35,11 +35,11 @@ Read-only. Dataset `AUDIT_TRAIL` (storage group `ADT`); every field is read-only
| Engineering Module: change an item field | `ITEM_DF` `<FIELD>` `MODIFY`, source `LOC-ENG-MOD`, user `ADMIN` (the logged-in user) | | Engineering Module: change an item field | `ITEM_DF` `<FIELD>` `MODIFY`, source `LOC-ENG-MOD`, user `ADMIN` (the logged-in user) |
| Engineering Module: right-click item › *Update value* | `ITEM_VAL` `ITEM_VALUE_STR` `MODIFY` (old/new) and `ITEM_VAL` `STATUS` `MODIFY`, source `LOC-ENG-MOD` | | Engineering Module: right-click item › *Update value* | `ITEM_VAL` `ITEM_VALUE_STR` `MODIFY` (old/new) and `ITEM_VAL` `STATUS` `MODIFY`, source `LOC-ENG-MOD` |
| Engineering Module / Operator / OPC UA server login | `CI-SERVER` `LOGIN` / `LOGOUT`, source `LOC-ENG-MOD`, `OPER-INTERFACE`, `VIA-OPC-UAS` | | Engineering Module / Operator / OPC UA server login | `CI-SERVER` `LOGIN` / `LOGOUT`, source `LOC-ENG-MOD`, `OPER-INTERFACE`, `VIA-OPC-UAS` |
| Operator display write (button / input) on an item with *Audit trailing wanted* (`AUDIT_INFO` 1) | `ITEM` `VALUE` `MODIFY` `OPER-INTERFACE` (old/new) and `ITEM` `STATUS` `MODIFY`, user = operator; with `AUDIT_INFO` 0 **nothing** |
| `itmval -p` (ITEM Service API) | **nothing**, even with `AUDIT_INFO` 1 | | `itmval -p` (ITEM Service API) | **nothing**, even with `AUDIT_INFO` 1 |
So `AUDIT_INFO` matters only for operator (and PROCESS) writes; DSS changes are always The `ITEM.VALUE.MODIFY.*` style classifiers (subject `ITEM`) were not produced by any of these
audited. The `SUBJECT_SOURCE` of a user interface comes from its *audit tools; they are expected from operator displays and PROCESS Service on items with
`AUDIT_INFO` 1 (open: ISS-049). The `SUBJECT_SOURCE` of a user interface comes from its *audit
trail id* in `dssana.sup` `USER_INTERFACE` (Engineering Module = `LOC-ENG-MOD`). trail id* in `dssana.sup` `USER_INTERFACE` (Engineering Module = `LOC-ENG-MOD`).
## 3. Export ## 3. Export

View file

@ -46,20 +46,14 @@ prompt forever when the input runs out.
Afterwards `RESET_REQUIRED` = 0 and the object used the new code at once (verified). Afterwards `RESET_REQUIRED` = 0 and the object used the new code at once (verified).
**Also works** — Engineering Module: *Configuration › I/O processing › Classes* › right-click the The Engineering Module also resets classes (class properties); not practiced.
class › *Reset*. The *Class - reset* window shows *Reset required* / *Extended reset required*,
options *Force extended reset* and *Abort after first failure*, progress (reset n of m, failed)
and a reset report; click **Reset** (verified by the user 2026-10-01: 1 of 1 object reset,
`RESET_REQUIRED` 0). This window is the front end of dataset `CLASS_RESET_COMMAND`.
**Does not work** (verified 2026-09-30, ISS-028): **Does not work** (verified 2026-09-30, ISS-028):
- `dssqld -m` with `NAME,RESET` = `"<class>",1` (also with `RESET_NODE` = the host node name): - `dssqld -m` with `NAME,RESET` = `"<class>",1` (also with `RESET_NODE` = the host node name):
accepted with 0 errors but nothing happens. accepted with 0 errors but nothing happens.
- `dssqld -m` on `OBJECT_DF` with `RESET` 1: refused with `OPC-E-OBJ_RSTREQ, The class needs to - `dssqld -m` on `OBJECT_DF` with `RESET` 1: refused with `OPC-E-OBJ_RSTREQ, The class needs to
be reset first`. be reset first`.
- `CLASS_RESET_COMMAND` (system-wide reset, fields `RESET`, `GENERATE_REPORT`, `PROGRESS`, - `CLASS_RESET_COMMAND` (system-wide reset used by the Engineering Module) was not tried.
`OBJECTS_RESET` …): the dataset allows only read and update, `dssqld -e` returns no record,
`dssqld -m` gives *Not found*, `dssqld -i` is refused (`DSS-E-NO_AUTH`). Verified 2026-10-01.
## 3. Changing prompts or signals ## 3. Changing prompts or signals

View file

@ -73,11 +73,9 @@ In a `.qli` file double the quotes inside the field:
Pitfalls found on the test system: Pitfalls found on the test system:
- Namespace `http://www.yokogawa.com/CI_Server/` (the one the manual shows) holds only the - Namespace `http://www.yokogawa.com/CI_Server/` (the one the manual shows) holds only the
**types**; with it the point is silently not monitored (ISS-032). **types**; with it the point is silently not monitored (ISS-032).
- In the Engineering Module's *Browse path*, **expand the item and pick its `Value` node** - The Engineering Module's *Browse path* stops at the item and stores the **object**
(`Objects/<Section>/…/<Tag>/Value`, node ID `{"0":"Value","nsid":"<n>"}`); verified by the (`{"nsid":"<n>"}`), which has no value: *Last value* stays empty, the item stays status 13.
user: *Last value* and *Data type* filled at once. Picking the item itself stores the Type the `Value` node ID by hand (ISS-033).
**object** (`{"nsid":"<n>"}`), which has no value (status 13, never monitored) (ISS-033).
For quick load prefer `{"0":"Value","itnm":"<item>"}`: it does not depend on `nsid`.
- `nsid` numbers change when the item is deleted and created again (e.g. sample reload). - `nsid` numbers change when the item is deleted and created again (e.g. sample reload).
A point that is not accepted shows `REVISED_SAMPLING_INTERVAL` 0 in `OPCUAC_POINT_DF` and the A point that is not accepted shows `REVISED_SAMPLING_INTERVAL` 0 in `OPCUAC_POINT_DF` and the

View file

@ -38,18 +38,9 @@ grep -n "<html>\|<width>\|<height>\|itemName\|itemId\|<source" <DisplayName>.xml
- `<html>true</html>` = HTML mode; `<width>`/`<height>` must be set for the HTML display. - `<html>true</html>` = HTML mode; `<width>`/`<height>` must be set for the HTML display.
- Item connections: `<itemName>` + `<itemId>` (node.group.number…); trend pens: - Item connections: `<itemName>` + `<itemId>` (node.group.number…); trend pens:
`<source type="sourceID" uri="ci:/item/<item>"/>` (`uri=""` = empty pen). `<source type="sourceID" uri="ci:/item/<item>"/>` (`uri=""` = empty pen).
- Write a fixed value with a button (verified in the HTML display, `CIENG_Tank` *Manual (0)* / - The name is what counts: after the item was deleted and loaded again (new id) the display
*Auto (1)*): `<button>` › `<data>` › `<action type="actionSetItemAttribute">` with still validated and a new session showed live values; already-open sessions kept showing the
`<event type="event" event="On action"/>`, `<filter type="filter"><value>1.0</value></filter>` old value until reopened.
and a `<connection>` with `<direction>2</direction>`, `<itemName>`, `<itemAttribute>ItemValue`
(the factory popups use `ItemValueOW`, presumably the overwrite variant like `itmval -o`; not tested). The factory popup `AOG_SetNumberPV` uses the
same action behind its *Apply* button.
- After the item is deleted and loaded again it gets a **new id**; the display still validates,
but on 2026-10-01 the HTML display showed **0** and the popup `ITM-E-NO_MAIN, No main item
found` for a number field whose stored `<itemId>` was stale, also in a fresh session. Deleting
the `<itemId>` line (keeping `<itemName>`) and redeploying fixed it: the field binds by name.
Sample displays therefore carry no `<itemId>`; for displays made in the Edit Module, reconnect
or remove the ids after reloading items (ISS-052).
## Verified (CIENG_Tank, 2026-10-01) ## Verified (CIENG_Tank, 2026-10-01)

View file

@ -53,6 +53,5 @@ session** and needs a new login. Check live values by writing a test value (`itm
## Verified (2026-10-01) ## Verified (2026-10-01)
Remove → deploy recreated both files; `-e HTML` output identical to the Edit Module's HTML; Remove → deploy recreated both files; `-e HTML` output identical to the Edit Module's HTML;
validation of `CIENG_Tank` *No problems found* (also after a sample reload with new item ids — validation of `CIENG_Tank` *No problems found* (also after a sample reload with new item ids);
but a stale `<itemId>` then shows 0 at run time, ISS-052);
search worked; browser showed live values. HTML trend without line: ISS-041. search worked; browser showed live values. HTML trend without line: ISS-041.

View file

@ -27,10 +27,6 @@ printf '\n21\n<GROUP>\n3\n\n-1\n' | timeout 20 hisdbg
| 5 | Force rollover of the current group (closes the active unit, starts the next) | changes files — with approval | | 5 | Force rollover of the current group (closes the active unit, starts the next) | changes files — with approval |
| 4, 8, 10, 12, 9 | Delete unit / group, restore unit, delete unknown files, change schedule | **no — never without explicit approval** | | 4, 8, 10, 12, 9 | Delete unit / group, restore unit, delete unknown files, change schedule | **no — never without explicit approval** |
A rollover can also be forced with `dssqld -m` on `HIS_GROUP_DF` (`NAME,FORCE_ROLLOVER` =
`"<group>",1`). A second forced rollover within 2 minutes is refused
(`DSI-E-ROLLDONE, Rollover already done in the last two minutes`; verified 2026-10-01).
History files are in `%TLS_ALLUSERS_PATH%\tls\his\` (path shown by option 21): History files are in `%TLS_ALLUSERS_PATH%\tls\his\` (path shown by option 21):
`h<node><group><unit><data>.his` with base-32 digits, e.g. group 1,54 → `h0101m…`. `h<node><group><unit><data>.his` with base-32 digits, e.g. group 1,54 → `h0101m…`.

View file

@ -134,12 +134,8 @@ Engineering Module (checked by the user 2026-10-01): the forms show the loaded f
*Report destination* = `DEST_NAME`, no field for `ADHOC_DEST`; Query with Structure / Keywords / *Report destination* = `DEST_NAME`, no field for `ADHOC_DEST`; Query with Structure / Keywords /
Datasets panes; Time scheduling with *Correct for daylight saving*; Item triggering). Right-click › Datasets panes; Time scheduling with *Correct for daylight saving*; Item triggering). Right-click ›
*Generate* opens a dialog with *Destination* (preset `<None>`, `ADHOC_DEST` is not pre-selected) and *Generate* opens a dialog with *Destination* (preset `<None>`, `ADHOC_DEST` is not pre-selected) and
one field per parameter prompt; an `[ITEM:<filter>]` prompt gives an item tree browser. The one field per parameter prompt; an `[ITEM:…]` prompt gives an item tree browser, but the filter did
filter is an `ITEM_DF` filter (DSS syntax) added with `AND` for each tree node: all sections and **not** limit it (whole tree shown, ISS-048). The run is made by the logged-in user (`ADMIN`, process
objects stay visible, but only matching items (and their sub-items) appear and can be picked.
Verified by the user: `NAME like "<Section>.*"`, `NAME like "*.L*"`, `DESCRIPTION like "Tank 1*"`
work; `%` is not a wildcard and `NAME = "….*"` matches nothing (no items, no error);
`SECTION = …` is not an `ITEM_DF` field (`DSS-E-FLT_SYN_ERR` on every expand) (ISS-048). The run is made by the logged-in user (`ADMIN`, process
`JHMISET…`) and printed to the chosen destination without errors. Generated reports are listed under `JHMISET…`) and printed to the chosen destination without errors. Generated reports are listed under
the report by local time; *View* has its own *Destination* box and *Export…*; HTML reports render as the report by local time; *View* has its own *Destination* box and *Export…*; HTML reports render as
HTML. HTML.

View file

@ -2,7 +2,7 @@
task: BUS Service utilities - process checks, stopping single processes, message tools, adaptive queues task: BUS Service utilities - process checks, stopping single processes, message tools, adaptive queues
version: R1.03 version: R1.03
source: IM 36K10L30-01EN §1, §5, §6, §10, §14; checked on the test system 2026-10-01 source: IM 36K10L30-01EN §1, §5, §6, §10, §14; checked on the test system 2026-10-01
status: verified (durwfp, setup file checks, umhman, umhmsg, umhtestprog) status: verified for durwfp and the read-only setup file checks; umhman, umhtestprog, umhmsg fail on the test system (ISS-030)
--- ---
# BUS Service utilities # BUS Service utilities
@ -28,15 +28,10 @@ then kills after 10 s. `*` wildcards stop many processes (`-p alm\*`). Never `du
- Message log: `%TLS_LOG_PATH%\umhlog.log` (`--> From: <PROCESS> (<node>) on <time>`, then - Message log: `%TLS_LOG_PATH%\umhlog.log` (`--> From: <PROCESS> (<node>) on <time>`, then
`FAC-S-CODE, text` lines). `UMH Message Text Error: Message number <hex> (…)` = the text `FAC-S-CODE, text` lines). `UMH Message Text Error: Message number <hex> (…)` = the text
could not be formatted (e.g. `%` in a PRINT text, ISS-025). could not be formatted (e.g. `%` in a PRINT text, ISS-025).
- `umhman` (hex code → text): answers can be piped, e.g. `printf '8010008 - `umhman` (hex code → text), `umhtestprog` (test the log path) and `umhmsg <hex> [<var>
<value>]` (log a message from a script) **did not work on the test system**: `umhman`
' | umhman` → crashes with redirected input (run it interactively), `umhtestprog` crashes, `umhmsg` stops
`DUR-W-NO_MSG_FND, No selected message found`; parameters in the text stay empty. with `license expired` on the unlicensed node (ISS-030).
- `umhmsg <hex> [<var> <value>]…` logs that message from a script: it prints nothing; the
message appears in `umhlog.log` from process `UMHMSG_<pid>`.
- `umhtestprog` runs its self-test (`TESTING UMH MESSAGES`, `TESTING ILLEGAL CODES`).
- On an **unlicensed** node these tools crash or stop with `license expired` once the licence
time is nearly used up, while `dssqld`/`itmval` still work; restart CI Server (ISS-030).
## Adaptive queues (read-only check) ## Adaptive queues (read-only check)

View file

@ -21,10 +21,8 @@ item storage group of type *Event/Item* or *Event/Event*. The sample project pro
when an older unit's time range covers them (verified 2026-10-01, ISS-006). A restart closes when an older unit's time range covers them (verified 2026-10-01, ISS-006). A restart closes
the active unit and starts a new one, so load old data **before** restarting, or not at all. the active unit and starts a new one, so load old data **before** restarting, or not at all.
Check the unit times first: skill `history-management`, task `history-checks.md`. Check the unit times first: skill `history-management`, task `history-checks.md`.
- A dropped sample dated **shortly before** the first unit after the restart (same day) becomes - A dropped sample can still become the initial value of the next unit at the next rollover
the initial value of the next unit at the next rollover, instead of the item's live value (ISS-038): check the result after loading.
(reproduced twice; a sample one day older did not do this, ISS-038). Check the result after
loading, and do not load samples older than the active units.
- Loaded samples appear in `ITEM_HISTORY` a few seconds after `ithloahis` returns. - Loaded samples appear in `ITEM_HISTORY` a few seconds after `ithloahis` returns.
## Input files ## Input files

View file

@ -10,8 +10,7 @@ ENGLISH
! Report names: at most 16 characters. ! Report names: at most 16 characters.
! !
! CIENG_TANK1 : values of all TANK1 items plus last-hour statistics of one item (parameter ! CIENG_TANK1 : values of all TANK1 items plus last-hour statistics of one item (parameter
! @p0, chosen in an item browser that shows only TANK1 items; sections stay ! @p0, chosen in an item browser; its filter does not limit it, ISS-048); daily at 06:00.
! visible, ISS-048); daily at 06:00.
! The activation time lies in the past; CI Server moves it to the next 06:00. ! The activation time lies in the past; CI Server moves it to the next 06:00.
! CORRECT_DAYLIGHT 1 keeps 06:00 across daylight-saving changes (with 0 the ! CORRECT_DAYLIGHT 1 keeps 06:00 across daylight-saving changes (with 0 the
! interval runs in UTC and 06:00 in January became 05:00 in October). ! interval runs in UTC and 06:00 in January became 05:00 in October).

View file

@ -1,15 +0,0 @@
@LANGUAGE
ENGLISH
@VERSION
1.03.00
! CI-Eng-Sample: switch on "Audit trailing wanted" (AUDIT_INFO) for PUMP1.MODE (loaded with
! dssqld -m). Operator writes from a display (buttons Manual (0) / Auto (1) on CIENG_Tank) are
! then stored as ITEM.VALUE.MODIFY.OPER-INTERFACE with old and new value; with AUDIT_INFO 0 they
! are not audited at all. Changes through DSS (dssqld, Engineering Module) are audited anyway.
@FIELDS
NAME,AUDIT_INFO
@ITEM_DF
"CI-Eng-Sample.PUMP1.MODE",1

View file

@ -110,8 +110,7 @@ New items start with status 13 (`NOT INIT`) until a value is written.
| `equipment/eqpciengslv_start.cmd`, `_stop.cmd` | Start/stop the Modbus slave mirror (copy to `tls\com`) | | `equipment/eqpciengslv_start.cmd`, `_stop.cmd` | Start/stop the Modbus slave mirror (copy to `tls\com`) |
| `76_`…`93_remove_*.qli` | Names to delete, in reverse order (audit `79`, reports and printer `83`/`84` first, alarm definitions last, `93`) | | `76_`…`93_remove_*.qli` | Names to delete, in reverse order (audit `79`, reports and printer `83`/`84` first, alarm definitions last, `93`) |
| `load.cmd`, `remove.cmd` | Run the steps in the right order | | `load.cmd`, `remove.cmd` | Run the steps in the right order |
| `displays/CIENG_Tank.xml` | Display (HTML mode): title, number field on `TANK1.LEVEL`, `PUMP1.MODE` field with buttons *Manual (0)* / *Auto (1)* (write the item), alarm overview, trend of `TANK1.LEVEL`, button *Operator layout* | | `displays/CIENG_Tank.xml` | Display (HTML mode): title, number field on `TANK1.LEVEL`, alarm overview, trend of `TANK1.LEVEL`, button *Operator layout* |
| `19b_audit_item_df.qli` | *Audit trailing wanted* for `PUMP1.MODE` (loaded with `dssqld -m`) |
| `displays/CIENG_Menu.xml` | Navigation display (200 x 700): *Tank 1*, *Current Alarm* (main frame), *Tank 1 popup* (layout `popup`) | | `displays/CIENG_Menu.xml` | Navigation display (200 x 700): *Tank 1*, *Current Alarm* (main frame), *Tank 1 popup* (layout `popup`) |
| `layouts/CIENG_Operator.xml`, `layouts/layout.ps1` | Operator layout block and the script that adds/removes it in `Layouts.xml` | | `layouts/CIENG_Operator.xml`, `layouts/layout.ps1` | Operator layout block and the script that adds/removes it in `Layouts.xml` |
| `displays/deploy_displays.cmd`, `remove_displays.cmd` | Copy the displays into the operator interface and export their HTML versions / delete them | | `displays/deploy_displays.cmd`, `remove_displays.cmd` | Copy the displays into the operator interface and export their HTML versions / delete them |
@ -206,9 +205,6 @@ Engineering Module is in the audit trail (skill `audit-trail`):
- Generate `CIENG_AUDIT` (ad hoc, like the other reports) to list the last hour of changes on - Generate `CIENG_AUDIT` (ad hoc, like the other reports) to list the last hour of changes on
`CI-Eng-Sample.*`: time, dataset, field, action, source, user, old and new value. `CI-Eng-Sample.*`: time, dataset, field, action, source, user, old and new value.
- Operator writes: with the displays deployed, click *Manual (0)* / *Auto (1)* on `CIENG_Tank`;
each click is stored as `ITEM.VALUE.MODIFY.OPER-INTERFACE` because `PUMP1.MODE` has *Audit
trailing wanted* (`19b_audit_item_df.qli`).
- Export: `dssqld -e audit.qlo -d AUDIT_TRAIL` (whole trail) or a qli with `@SELECT` (keep `NAME` - Export: `dssqld -e audit.qlo -d AUDIT_TRAIL` (whole trail) or a qli with `@SELECT` (keep `NAME`
in `@FIELDS`). in `@FIELDS`).
- Event logger (optional, admin): copy `audit\adtlogci.sup` to `%TLS_ROOT_PATH%\tls\sup\`, then - Event logger (optional, admin): copy `audit\adtlogci.sup` to `%TLS_ROOT_PATH%\tls\sup\`, then

View file

@ -70,7 +70,7 @@
<htmlId>1</htmlId> <htmlId>1</htmlId>
<name>Layer1</name> <name>Layer1</name>
</visualizationLayer> </visualizationLayer>
<componentCountHint>9</componentCountHint> <componentCountHint>5</componentCountHint>
<text type="componentData"> <text type="componentData">
<htmlId>7</htmlId> <htmlId>7</htmlId>
<value>CI-Eng-Sample Tank 1</value> <value>CI-Eng-Sample Tank 1</value>
@ -95,6 +95,7 @@
</filter> </filter>
<connection type="connection"> <connection type="connection">
<itemName>CI-Eng-Sample.TANK1.LEVEL</itemName> <itemName>CI-Eng-Sample.TANK1.LEVEL</itemName>
<itemId>1.1.268.0.0.1.1.7</itemId>
<itemAttribute>ItemValue</itemAttribute> <itemAttribute>ItemValue</itemAttribute>
</connection> </connection>
</action> </action>
@ -487,70 +488,5 @@
</action> </action>
</data> </data>
</button> </button>
<text type="componentData">
<htmlId>12</htmlId>
<value>Pump 1 mode (0 manual, 1 auto)</value>
<stroke type="stroke" width="1.0"/>
<keepOriginalSize>true</keepOriginalSize>
<x>330.0</x>
<y>120.0</y>
<top>5.3125</top>
<bottom>5.3125</bottom>
<left>90.0</left>
<right>90.0</right>
<rotation>0.0</rotation>
<shear>0.0</shear>
</text>
<numberField type="componentData" x="480.0" y="120.0" top="16.0" bottom="16.0" left="30.0" right="30.0" rotation="0.0" shear="0.0">
<htmlId>13</htmlId>
<data type="data">
<action type="actionConnectTo">
<property type="property" name="numberField.value"/>
<filter type="filter">
<value>0.0</value>
</filter>
<connection type="connection">
<itemName>CI-Eng-Sample.PUMP1.MODE</itemName>
<itemAttribute>ItemValue</itemAttribute>
</connection>
</action>
</data>
</numberField>
<button type="componentData" x="590.0" y="120.0" top="16.0" bottom="16.0" left="56.0" right="56.0" rotation="0.0" shear="0.0">
<htmlId>14</htmlId>
<label>Manual (0)</label>
<data type="data">
<action type="actionSetItemAttribute">
<event type="event" event="On action"/>
<filter type="filter">
<value>0.0</value>
</filter>
<connection type="connection">
<direction>2</direction>
<location type="nodeName" node="$default$"/>
<itemName>CI-Eng-Sample.PUMP1.MODE</itemName>
<itemAttribute>ItemValue</itemAttribute>
</connection>
</action>
</data>
</button>
<button type="componentData" x="716.0" y="120.0" top="16.0" bottom="16.0" left="56.0" right="56.0" rotation="0.0" shear="0.0">
<htmlId>15</htmlId>
<label>Auto (1)</label>
<data type="data">
<action type="actionSetItemAttribute">
<event type="event" event="On action"/>
<filter type="filter">
<value>1.0</value>
</filter>
<connection type="connection">
<direction>2</direction>
<location type="nodeName" node="$default$"/>
<itemName>CI-Eng-Sample.PUMP1.MODE</itemName>
<itemAttribute>ItemValue</itemAttribute>
</connection>
</action>
</data>
</button>
</coreObjectDefinition> </coreObjectDefinition>
</visualization> </visualization>

View file

@ -44,5 +44,3 @@ dssqld -i 17_printer_df.qli -l 17_printer_df.qlo
dssqld -i 18_report_df.qli -l 18_report_df.qlo dssqld -i 18_report_df.qli -l 18_report_df.qlo
rem Audit trail: selection group (compiled on load) and an ad-hoc audit report. rem Audit trail: selection group (compiled on load) and an ad-hoc audit report.
dssqld -i 19_audit_df.qli -l 19_audit_df.qlo dssqld -i 19_audit_df.qli -l 19_audit_df.qlo
rem Audit trailing wanted for PUMP1.MODE (modify existing record)
dssqld -m 19b_audit_item_df.qli -l 19b_audit_item_df.qlo

View file

@ -23,9 +23,9 @@ development system (see "Test system" in `progress.md`); they do not exist on ot
| ISS-002 | 2026-09-30 | DATABASE (`dsschk`) | `dsschk -d ITEM_DF -v` (check only) exits 0 with no console output and nothing new in `umhlog.log`. Where results are reported is unknown. | closed | Closed 2026-09-30 (confirmed by user). 2026-09-30: `dsschk -e -v` prints a start/end line per dataset (228 checked, no problems) and logs to `umhlog.log`. Plain `dsschk` only compares copies between nodes, so it prints nothing on a single-node system. `ismchk` needs a database file name (usage: `ismchk data_base_name`), not run yet. | Create `.claude/skills/system-management/tasks/consistency-check.md` and add it to that skill's `SKILL.md`; `knowledge/manuals/IM36K10J10-01EN.md` §4.1.1 consistency tools (add where output goes); `knowledge/progress.md` row "Consistency check" | | ISS-002 | 2026-09-30 | DATABASE (`dsschk`) | `dsschk -d ITEM_DF -v` (check only) exits 0 with no console output and nothing new in `umhlog.log`. Where results are reported is unknown. | closed | Closed 2026-09-30 (confirmed by user). 2026-09-30: `dsschk -e -v` prints a start/end line per dataset (228 checked, no problems) and logs to `umhlog.log`. Plain `dsschk` only compares copies between nodes, so it prints nothing on a single-node system. `ismchk` needs a database file name (usage: `ismchk data_base_name`), not run yet. | Create `.claude/skills/system-management/tasks/consistency-check.md` and add it to that skill's `SKILL.md`; `knowledge/manuals/IM36K10J10-01EN.md` §4.1.1 consistency tools (add where output goes); `knowledge/progress.md` row "Consistency check" |
| ISS-003 | 2026-09-30 | DATABASE (`dssqld`) | Filtered export (`dssqld -e <out> <filter>.qli`) failed with a guessed filter syntax (`@ITEM_DF`, `@FIELD`, `@SELECT`). | closed | Closed 2026-09-30 (confirmed by user). 2026-09-30: the quick load **data** format is now known and verified (`@LANGUAGE`, `@VERSION`, `@FIELDS`, `@<DATASET>`, quoted CSV records, `\` continuation, `!` comments; IM 36K10L45 §9.11). Filter syntax found (IM 36K10L50 §3.6) and practiced, awaiting confirmation: a file with `@SELECT`, then the filter in single quotes (strings in double quotes), then `@<DATASET>`; run `dssqld -e <out> <filter>.qli`. `ITEM_HISTORY` returns nothing unless the filter names `ITEM_NAME` and a `SAMPLE_TIME` range (`SAMPLE_TIME > "dd-mm-yyyy hh:mm:ss" and SAMPLE_TIME < ...`). | `.claude/skills/system-management/tasks/export-dataset.md` section "Filtered exports"; `knowledge/manuals/IM36K10J10-01EN.md` §5.6 step 1; `knowledge/progress.md` row "Export a dataset" | | ISS-003 | 2026-09-30 | DATABASE (`dssqld`) | Filtered export (`dssqld -e <out> <filter>.qli`) failed with a guessed filter syntax (`@ITEM_DF`, `@FIELD`, `@SELECT`). | closed | Closed 2026-09-30 (confirmed by user). 2026-09-30: the quick load **data** format is now known and verified (`@LANGUAGE`, `@VERSION`, `@FIELDS`, `@<DATASET>`, quoted CSV records, `\` continuation, `!` comments; IM 36K10L45 §9.11). Filter syntax found (IM 36K10L50 §3.6) and practiced, awaiting confirmation: a file with `@SELECT`, then the filter in single quotes (strings in double quotes), then `@<DATASET>`; run `dssqld -e <out> <filter>.qli`. `ITEM_HISTORY` returns nothing unless the filter names `ITEM_NAME` and a `SAMPLE_TIME` range (`SAMPLE_TIME > "dd-mm-yyyy hh:mm:ss" and SAMPLE_TIME < ...`). | `.claude/skills/system-management/tasks/export-dataset.md` section "Filtered exports"; `knowledge/manuals/IM36K10J10-01EN.md` §5.6 step 1; `knowledge/progress.md` row "Export a dataset" |
| ISS-004 | 2026-09-30 | ITEM (`itmval`) | `itmval -g -a <1..5>` returns `ITM-E-WRONG_ATT` on `AID.WRPS.*` items, so reading limits is unproven. | closed | Closed 2026-09-30 (confirmed by user). On `CI-Eng-Sample.TANK1.LEVEL` (limits set) `-a 1..5` returned deadband 0, low 20, high 80, low-low 10, high-high 90. The error only occurs on items without limits. | `.claude/skills/system-management/tasks/read-write-item.md` (limits section); `knowledge/progress.md` row "Read an item with `itmval -g`" | | ISS-004 | 2026-09-30 | ITEM (`itmval`) | `itmval -g -a <1..5>` returns `ITM-E-WRONG_ATT` on `AID.WRPS.*` items, so reading limits is unproven. | closed | Closed 2026-09-30 (confirmed by user). On `CI-Eng-Sample.TANK1.LEVEL` (limits set) `-a 1..5` returned deadband 0, low 20, high 80, low-low 10, high-high 90. The error only occurs on items without limits. | `.claude/skills/system-management/tasks/read-write-item.md` (limits section); `knowledge/progress.md` row "Read an item with `itmval -g`" |
| ISS-005 | 2026-09-30 | DATABASE (`dssqld`) | Loading `04_item_his_df.qli` straight after creating the storage group gave 2 errors once; three other runs were clean. Error text not captured. | open | Added a 5 s pause in `load.cmd`. No recurrence since: every full sample reload in phases 6-12 (latest 2026-10-01) loaded `04_item_his_df.qli` with 0 errors. Ready to close. | `examples/CI-Eng-Sample/load.cmd`; `.claude/skills/system-management/tasks/load-remove-records.md` | | ISS-005 | 2026-09-30 | DATABASE (`dssqld`) | Loading `04_item_his_df.qli` straight after creating the storage group gave 2 errors once; three other runs were clean. Error text not captured. | open | Added a 5 s pause in `load.cmd`. If it happens again, capture `04_item_his_df.qlo`. | `examples/CI-Eng-Sample/load.cmd`; `.claude/skills/system-management/tasks/load-remove-records.md` |
| ISS-006 | 2026-09-30 | HISTORY (`ithloahis`) | Samples dated before the start of the current storage unit were not stored (no error shown); samples after it were. Also, a new storage group stored nothing until CI Server was restarted. | closed | Closed 2026-10-01 (confirmed by user). Confirm with History Management (IM 36K10L20) in phase 9: how to load into older units, and whether a restart is really required. 2026-09-30 (phase 5): IM 36K10L35 §1.3/§5 explains the first part: event storage picks the unit by time stamp, never older than 60 units, and within the storage process's `gap_time` (ITHEEX/ITHEIX 2880 min) and, for EVENT/ITEM, `max_sample_delay` (ITHEIX 14400 min); older data needs earlier unit files (`hisdbg`, `hisrecover`, `isfrename`), `ithrecover <group> -p` and a restart. Practice in phase 9. 2026-10-01 (phase 9, verified): (1) restart **is** required — `CIENG_SCAN10S` / `CIENG_AGG` loaded at 11:54 and `CIENG_EVENT` reloaded at 11:32 stored nothing until the 12:00 restart, then stored at once. (2) The first unit of a new Event/Item or Aggregation group is dated 2 days back (= `gap_time` 2880 min), but samples loaded into that pre-restart unit (11:50, 30-Sep) were still dropped; samples inside the active unit (12:02) and inside a unit closed by a forced rollover (12:03 into unit 3,1) were stored. So: samples older than the first unit opened since the restart are dropped silently. Loading older data would need `hisrecover` / `isfrename` / `ithrecover` (not practiced). Proposed close: documented in `load-history.md` and skill `history-management`. | `.claude/skills/system-management/tasks/load-history.md`; `examples/CI-Eng-Sample/README.md`; `knowledge/manuals/IM36K10J10-01EN.md` command-line tools | | ISS-006 | 2026-09-30 | HISTORY (`ithloahis`) | Samples dated before the start of the current storage unit were not stored (no error shown); samples after it were. Also, a new storage group stored nothing until CI Server was restarted. | closed | Closed 2026-10-01 (confirmed by user). Confirm with History Management (IM 36K10L20) in phase 9: how to load into older units, and whether a restart is really required. 2026-09-30 (phase 5): IM 36K10L35 §1.3/§5 explains the first part: event storage picks the unit by time stamp, never older than 60 units, and within the storage process's `gap_time` (ITHEEX/ITHEIX 2880 min) and, for EVENT/ITEM, `max_sample_delay` (ITHEIX 14400 min); older data needs earlier unit files (`hisdbg`, `hisrecover`, `isfrename`), `ithrecover <group> -p` and a restart. Practice in phase 9. 2026-10-01 (phase 9, verified): (1) restart **is** required — `CIENG_SCAN10S` / `CIENG_AGG` loaded at 11:54 and `CIENG_EVENT` reloaded at 11:32 stored nothing until the 12:00 restart, then stored at once. (2) The first unit of a new Event/Item or Aggregation group is dated 2 days back (= `gap_time` 2880 min), but samples loaded into that pre-restart unit (11:50, 30-Sep) were still dropped; samples inside the active unit (12:02) and inside a unit closed by a forced rollover (12:03 into unit 3,1) were stored. So: samples older than the first unit opened since the restart are dropped silently. Loading older data would need `hisrecover` / `isfrename` / `ithrecover` (not practiced). Proposed close: documented in `load-history.md` and skill `history-management`. | `.claude/skills/system-management/tasks/load-history.md`; `examples/CI-Eng-Sample/README.md`; `knowledge/manuals/IM36K10J10-01EN.md` command-line tools |
| ISS-007 | 2026-09-30 | INTEGRATION (monitoring) | `intdskmon` wrote 61.9 for a C: drive that is 61.9 % used / 38.1 % free, although the manual says it monitors the disk free space rate. `intspawn` did nothing when the command path was ~130 characters; a short path worked (limit unknown). | open | Disk value: the test showed **used** % (61.9 on a 61.9 % used disk), and the task file says so; installed behaviour is the reference. `intspawn` path limit: not measured (needs admin edits of `tls\sup\<name>.sup` and restarts for each length); guidance kept: put the command in a `.cmd` with a short path (other CI Server tools cut paths at 79 characters, ISS-020). Ready to close. | `.claude/skills/system-management/tasks/monitoring-processes.md`; `knowledge/manuals/IM36K10J10-01EN.md` §4.1.6; `examples/CI-Eng-Sample/monitoring/` | | ISS-007 | 2026-09-30 | INTEGRATION (monitoring) | `intdskmon` wrote 61.9 for a C: drive that is 61.9 % used / 38.1 % free, although the manual says it monitors the disk free space rate. `intspawn` did nothing when the command path was ~130 characters; a short path worked (limit unknown). | open | Confirm the disk value meaning and the path limit. | `.claude/skills/system-management/tasks/monitoring-processes.md`; `knowledge/manuals/IM36K10J10-01EN.md` §4.1.6; `examples/CI-Eng-Sample/monitoring/` |
| ISS-008 | 2026-09-30 | ACCESS (ODBC server `odbsrv`) | `ci_start.log` on the test system shows `CppServerAPI::Run() failed: InitializeSslCtx(): SSL_CTX_use_certificate_chain_file() failed.` right after ACCESS Service starts. Which component and certificate is not known. | closed | Closed 2026-10-01 (confirmed by user): cause known, ODBC server left as is (not licensed/used on the test system). Identify in phase 7. 2026-10-01 (phase 7): cause found. The message comes from the ODBC server `odbsrv` (ACCESS Service, Simba): `odbsrv.sup` has `USESSL = YES` and `access_start.cmd` points it at `%TLS_ROOT_PATH%\tls\pki\odbsrv\SampleServerCertificate.pem` / `SampleServerKey.pem`, but that folder does not exist and no sample certificate is installed. `odbsrv` exits right after start (`DUR-W-REM_PROC, Process ODBSRV exited unexpectedly`), port 1583 does not listen. Fix (admin, only if ODBC is licensed and wanted): install a certificate + key there, or set `USESSL = NO`. Not applied. Close when the user confirms. | `.claude/skills/installation-security/tasks/setup-check.md`; `knowledge/manuals/IM36K10L45-01EN.md` §1 (done); `.claude/skills/data-access/tasks/access-checks.md` (done) | | ISS-008 | 2026-09-30 | ACCESS (ODBC server `odbsrv`) | `ci_start.log` on the test system shows `CppServerAPI::Run() failed: InitializeSslCtx(): SSL_CTX_use_certificate_chain_file() failed.` right after ACCESS Service starts. Which component and certificate is not known. | closed | Closed 2026-10-01 (confirmed by user): cause known, ODBC server left as is (not licensed/used on the test system). Identify in phase 7. 2026-10-01 (phase 7): cause found. The message comes from the ODBC server `odbsrv` (ACCESS Service, Simba): `odbsrv.sup` has `USESSL = YES` and `access_start.cmd` points it at `%TLS_ROOT_PATH%\tls\pki\odbsrv\SampleServerCertificate.pem` / `SampleServerKey.pem`, but that folder does not exist and no sample certificate is installed. `odbsrv` exits right after start (`DUR-W-REM_PROC, Process ODBSRV exited unexpectedly`), port 1583 does not listen. Fix (admin, only if ODBC is licensed and wanted): install a certificate + key there, or set `USESSL = NO`. Not applied. Close when the user confirms. | `.claude/skills/installation-security/tasks/setup-check.md`; `knowledge/manuals/IM36K10L45-01EN.md` §1 (done); `.claude/skills/data-access/tasks/access-checks.md` (done) |
| ISS-009 | 2026-09-30 | Security Guide | DCOM port range printed as 20500–20550 in the firewall table but "2500–20550" in the OPC configuration table. Taken as a typo for 20500–20550. | closed | Confirm on a system with IT security applied. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K01C30-01EN.md` §4 | | ISS-009 | 2026-09-30 | Security Guide | DCOM port range printed as 20500–20550 in the firewall table but "2500–20550" in the OPC configuration table. Taken as a typo for 20500–20550. | closed | Confirm on a system with IT security applied. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K01C30-01EN.md` §4 |
@ -40,35 +40,34 @@ development system (see "Test system" in `progress.md`); they do not exist on ot
| ISS-018 | 2026-09-30 | Authorization (`dssana.sup`) | IM 36K10C10 §2.2 says the *No* login method applies the user profile `FT_NO_LOGIN`; the installed `dssana.sup` names `CI_NO_LOGIN` (and `CI_NO_LOGIN_OPCUAS` for anonymous OPC UA) as the no-login profile. `USER_DF` on the test system has `CI_NO_LOGIN_OPCUAS` but no `CI_NO_LOGIN`. | open | Installed software is the reference: use `CI_NO_LOGIN`. Still to check: behaviour of a *No* login when that user does not exist (manual: no profile applied). Covered again in phase 13 (IM 36K10J40). | `knowledge/manuals/IM36K10C10-01EN.md` §2 | | ISS-018 | 2026-09-30 | Authorization (`dssana.sup`) | IM 36K10C10 §2.2 says the *No* login method applies the user profile `FT_NO_LOGIN`; the installed `dssana.sup` names `CI_NO_LOGIN` (and `CI_NO_LOGIN_OPCUAS` for anonymous OPC UA) as the no-login profile. `USER_DF` on the test system has `CI_NO_LOGIN_OPCUAS` but no `CI_NO_LOGIN`. | open | Installed software is the reference: use `CI_NO_LOGIN`. Still to check: behaviour of a *No* login when that user does not exist (manual: no profile applied). Covered again in phase 13 (IM 36K10J40). | `knowledge/manuals/IM36K10C10-01EN.md` §2 |
| ISS-019 | 2026-09-30 | ITEM (string items) | Maximum string item length differs by source: IM 36K10C10 §3.3.4 says default 80, max 100; the Tutorial summary says up to 168 without audit; the data dictionary (`dssqld -f`) gives `ITEM_DF.STRING_LENGTH` range 1–200, default 80. | closed | Tested 2026-09-30 on CI-Eng-Sample (`dssqld -i`, `itmval -p/-g`, non-elevated): `STRING_LENGTH` 100, 168 and 200 load with or without `AUDIT_INFO`; 201 fails with `DSS-E-VAL_RANGE`. An item holds **length − 1** characters: a 99-character value in a length-100 item is stored with status 9 NORMAL; longer values are cut to length − 1 with status **12 OVERRANGED** (100 → 99, 200 → 199, 201 → 199). So the data dictionary (1–200) is right. Test items removed. Closed 2026-09-30 (confirmed by user). | `knowledge/manuals/IM36K10C10-01EN.md` §3; `knowledge/manuals/IM36K10G10-01EN.md` (items); `.claude/skills/item-engineering/SKILL.md` | | ISS-019 | 2026-09-30 | ITEM (string items) | Maximum string item length differs by source: IM 36K10C10 §3.3.4 says default 80, max 100; the Tutorial summary says up to 168 without audit; the data dictionary (`dssqld -f`) gives `ITEM_DF.STRING_LENGTH` range 1–200, default 80. | closed | Tested 2026-09-30 on CI-Eng-Sample (`dssqld -i`, `itmval -p/-g`, non-elevated): `STRING_LENGTH` 100, 168 and 200 load with or without `AUDIT_INFO`; 201 fails with `DSS-E-VAL_RANGE`. An item holds **length − 1** characters: a 99-character value in a length-100 item is stored with status 9 NORMAL; longer values are cut to length − 1 with status **12 OVERRANGED** (100 → 99, 200 → 199, 201 → 199). So the data dictionary (1–200) is right. Test items removed. Closed 2026-09-30 (confirmed by user). | `knowledge/manuals/IM36K10C10-01EN.md` §3; `knowledge/manuals/IM36K10G10-01EN.md` (items); `.claude/skills/item-engineering/SKILL.md` |
| ISS-020 | 2026-09-30 | DATABASE (`dssqld`) | `dssqld -i "<long absolute path>\user.qli"` failed with `CRL-E-ENOENT` / `DSSQ-E-QLD_FILOPN`: the path in the message was cut after 79 characters (`…\73b3559a-12.`). A relative file name from the same folder works. Similar to the `intspawn` path limit (ISS-007). | closed | Tested 2026-10-01: the limit is **79 characters** for the whole path. An input file of 80–81 characters gives `DSSQ-E-Q_QLIEXT` (the name is cut, e.g. `….ql`), 85+ gives `CRL-E-ENOENT`. An `-e` output path of 80+ characters gives **no error**, but no file appears under the given name. Documented: keep paths ≤ 79 characters, or `cd` to the folder and use relative names. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/system-management/tasks/load-remove-records.md`; `.claude/skills/system-management/tasks/export-dataset.md` | | ISS-020 | 2026-09-30 | DATABASE (`dssqld`) | `dssqld -i "<long absolute path>\user.qli"` failed with `CRL-E-ENOENT` / `DSSQ-E-QLD_FILOPN`: the path in the message was cut after 79 characters (`…\73b3559a-12.`). A relative file name from the same folder works. Similar to the `intspawn` path limit (ISS-007). | closed | Tested 2026-10-01: the limit is **79 characters** for the whole path. An input file of 80–81 characters gives `DSSQ-E-Q_QLIEXT` (the name is cut, e.g. `….ql`), 85+ gives `CRL-E-ENOENT`. An `-e` output path of 80+ characters gives **no error**, but no file appears under the given name. Documented: keep paths ≤ 79 characters, or `cd` to the folder and use relative names. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/system-management/tasks/load-remove-records.md`; `.claude/skills/system-management/tasks/export-dataset.md` |
| ISS-021 | 2026-09-30 | EQUIPMENT (`eqpiostat`) | IM 36K10L40 §2 says `eqpiostat` stores hourly I/O statistics per station line in "history group STATION_STAT". On the test system `eqpiostat` runs (started by `equipment_start.cmd` on the host node) and `STATION_STAT` is a dataset, but `dssqld -e` returned 0 records, also with filters on `TIME_STAMP` and `STATION` (AID Modbus stations, which send requests). | open | Answered 2026-10-01: with `CIENG_PLC` communicating (Modbus slave mirror running), `STATION_STAT` holds one record per hour per station line (10 records since 30-09-2026 18:00; e.g. `TIMESPAN` 831 s, `SENDS`/`GOODANS` 1560/1560, no errors). The earlier empty export had no communicating station. Ready to close. | `knowledge/manuals/IM36K10L40-01EN.md` §2 | | ISS-021 | 2026-09-30 | EQUIPMENT (`eqpiostat`) | IM 36K10L40 §2 says `eqpiostat` stores hourly I/O statistics per station line in "history group STATION_STAT". On the test system `eqpiostat` runs (started by `equipment_start.cmd` on the host node) and `STATION_STAT` is a dataset, but `dssqld -e` returned 0 records, also with filters on `TIME_STAMP` and `STATION` (AID Modbus stations, which send requests). | open | Check whether records appear after a full hour with a communicating station, or whether the dataset is read another way (e.g. Engineering Module, report). | `knowledge/manuals/IM36K10L40-01EN.md` §2 |
| ISS-022 | 2026-09-30 | ITEM (`itmval -f`) | `itmval -f <file> vs -n CI-Eng-Sample.TANK1.LEVEL` (IM 36K10L36 §1.4, write a restore command) crashes with a segmentation fault (bash) / access violation 0xC0000005 (PowerShell) and writes no file; also with `-l`. The manual's space-separated form `-n <inst> <unit> <tag>` is rejected with `FSL-E-NARG_ALL`. `itmval -g`/`-p` work. | open | Workaround: build restore lines from `itmval -g` output. Report to Yokogawa support if needed. Retested 2026-10-01 with the documented syntax `itmval -f <file> <opts> -n <item>` (`<opts>` = letters from `vsqo`, e.g. `vs`): still a segmentation fault from bash and from `cmd`, in a short and a long folder, relative or absolute file name; `cmd` leaves an **empty** file. Also crashes right after a CI Server restart (so not the licence-time effect of ISS-030). Treat `-f` as broken on R1.03.00; report to Yokogawa support if needed. | `knowledge/manuals/IM36K10L36-01EN.md` §3; `.claude/skills/system-management/tasks/read-write-item.md` | | ISS-022 | 2026-09-30 | ITEM (`itmval -f`) | `itmval -f <file> vs -n CI-Eng-Sample.TANK1.LEVEL` (IM 36K10L36 §1.4, write a restore command) crashes with a segmentation fault (bash) / access violation 0xC0000005 (PowerShell) and writes no file; also with `-l`. The manual's space-separated form `-n <inst> <unit> <tag>` is rejected with `FSL-E-NARG_ALL`. `itmval -g`/`-p` work. | open | Workaround: build restore lines from `itmval -g` output. Report to Yokogawa support if needed. Retested 2026-10-01 with the documented syntax `itmval -f <file> <opts> -n <item>` (`<opts>` = letters from `vsqo`, e.g. `vs`): still a segmentation fault from bash and from `cmd`, in a short and a long folder, relative or absolute file name; `cmd` leaves an **empty** file. Treat `-f` as broken on R1.03.00. | `knowledge/manuals/IM36K10L36-01EN.md` §3; `.claude/skills/system-management/tasks/read-write-item.md` |
| ISS-023 | 2026-09-30 | ITEM / ITH (manual vs install) | Installed ITEM Service differs from IM 36K10L35/L36: `item_start.cmd` starts `itheix` (EVENT/ITEM storage, not described), aggregation `ithsag`/`ithrag`, two instances of each retrieve process, and `itmtim 100 1000 1 200 1` (five arguments, three documented); `itm.sup` item pool is 650000 KB (manual default 50000) and has `not_regained` (not described); `itheix.sup` has `max_sample_delay`, `max_samples_queued`, `max_open_files`. | closed | Closed 2026-09-30 (user decision: the installed software is the reference). Summaries describe the installed values. | `knowledge/manuals/IM36K10L35-01EN.md`; `knowledge/manuals/IM36K10L36-01EN.md` | | ISS-023 | 2026-09-30 | ITEM / ITH (manual vs install) | Installed ITEM Service differs from IM 36K10L35/L36: `item_start.cmd` starts `itheix` (EVENT/ITEM storage, not described), aggregation `ithsag`/`ithrag`, two instances of each retrieve process, and `itmtim 100 1000 1 200 1` (five arguments, three documented); `itm.sup` item pool is 650000 KB (manual default 50000) and has `not_regained` (not described); `itheix.sup` has `max_sample_delay`, `max_samples_queued`, `max_open_files`. | closed | Closed 2026-09-30 (user decision: the installed software is the reference). Summaries describe the installed values. | `knowledge/manuals/IM36K10L35-01EN.md`; `knowledge/manuals/IM36K10L36-01EN.md` |
| ISS-024 | 2026-09-30 | EQUIPMENT (Modbus slave) | IM 36K10L41 §3.7 says `EQPMDCSLVTCP` waits for "MODBUS RTU requests via TCP/IP" and the CI Server master should use "MODBUS RTU via TCP/IP". A Modbus master station with `PROTOCOL = RTU` to `eqpmdcslvtcp` (port 5020) got no answer (`EQP-E-TCPRCVTMO`, 4 requests, 0 valid); with `Open Modbus/TCP` it worked at once. | closed | Closed 2026-09-30 (user decision: installed software is the reference). Use `Open Modbus/TCP` towards `eqpmdcslvtcp`. | `knowledge/manuals/IM36K10L41-01EN.md` §3.7; `.claude/skills/equipment/tasks/modbus-station.md` | | ISS-024 | 2026-09-30 | EQUIPMENT (Modbus slave) | IM 36K10L41 §3.7 says `EQPMDCSLVTCP` waits for "MODBUS RTU requests via TCP/IP" and the CI Server master should use "MODBUS RTU via TCP/IP". A Modbus master station with `PROTOCOL = RTU` to `eqpmdcslvtcp` (port 5020) got no answer (`EQP-E-TCPRCVTMO`, 4 requests, 0 valid); with `Open Modbus/TCP` it worked at once. | closed | Closed 2026-09-30 (user decision: installed software is the reference). Use `Open Modbus/TCP` towards `eqpmdcslvtcp`. | `knowledge/manuals/IM36K10L41-01EN.md` §3.7; `.claude/skills/equipment/tasks/modbus-station.md` |
| ISS-025 | 2026-09-30 | PROCESS (PRINT) | A Traditional `PRINT "… 80 %, volume ", VOLUME;` logged `OPC-I-INFO, UMH Message Text Error: Message number 083A001B (… level reached 80 )`: the text is cut at the `%` and the rest is lost. Without `%` the full text is logged. | closed | Tested 2026-10-01 with a temporary class (removed): `PRINT "… 50 %% …"` logs `50 % …` correctly; `\%` and `%c` with 37 both give the *Message Text Error* and cut the text. Documented: write `%%`. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10P10-01EN.md` §4; `.claude/skills/class-object-engineering/tasks/traditional-class.md` | | ISS-025 | 2026-09-30 | PROCESS (PRINT) | A Traditional `PRINT "… 80 %, volume ", VOLUME;` logged `OPC-I-INFO, UMH Message Text Error: Message number 083A001B (… level reached 80 )`: the text is cut at the `%` and the rest is lost. Without `%` the full text is logged. | closed | Tested 2026-10-01 with a temporary class (removed): `PRINT "… 50 %% …"` logs `50 % …` correctly; `\%` and `%c` with 37 both give the *Message Text Error* and cut the text. Documented: write `%%`. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10P10-01EN.md` §4; `.claude/skills/class-object-engineering/tasks/traditional-class.md` |
| ISS-026 | 2026-09-30 | PROCESS (`opc.sup`) | Installed PROCESS setup differs from IM 36K10L10 §2: `IMMED-EVENTS = NO` (manual: default on); `FLOW-CONTROL = 30,60` (manual 300/360 s); four executors `OPCEXE1`–`4` with fixed priority ranges (manual examples `OPCEXE01`…) and `opcdbg` still defaults to `OPCEXE`; keyword `VARTAB-SIZE` (manual `VARITAB-SIZE`); hidden keywords `FLDSEP`, `IGNEXI` not described; `ALARM-ITEMS` not set; class source file `opc_clssrc.dat` (manual `opc_clasrc.dat`); `opcini.sup` (licence line) not described. | closed | Installed software is the reference (standing user decision); summary written from the installed files. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10L10-01EN.md` §2, §5 | | ISS-026 | 2026-09-30 | PROCESS (`opc.sup`) | Installed PROCESS setup differs from IM 36K10L10 §2: `IMMED-EVENTS = NO` (manual: default on); `FLOW-CONTROL = 30,60` (manual 300/360 s); four executors `OPCEXE1`–`4` with fixed priority ranges (manual examples `OPCEXE01`…) and `opcdbg` still defaults to `OPCEXE`; keyword `VARTAB-SIZE` (manual `VARITAB-SIZE`); hidden keywords `FLDSEP`, `IGNEXI` not described; `ALARM-ITEMS` not set; class source file `opc_clssrc.dat` (manual `opc_clasrc.dat`); `opcini.sup` (licence line) not described. | closed | Installed software is the reference (standing user decision); summary written from the installed files. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10L10-01EN.md` §2, §5 |
| ISS-027 | 2026-09-30 | PROCESS (`opcdbg`) | IM 36K10L10 §4 says the `opcdbg` *Dump classes/objects* files can be read by `dssqld`. The files have no `@LANGUAGE`/`@FIELDS`/`@<dataset>` headers (`NAME,"desc",prio` + source lines prefixed `- `); `dssqld -i` on the object dump gave `DSS-E-UNK_DS_NM, Unknown data set name`. | open | Use `dssqld -e CLASS_DF` / `OBJECT_DF` for transfers (documented in `opcdbg-checks.md`). No installed tool that reads the dump format was found. Ready to close. | `knowledge/manuals/IM36K10L10-01EN.md` §4; `.claude/skills/class-object-engineering/tasks/opcdbg-checks.md` | | ISS-027 | 2026-09-30 | PROCESS (`opcdbg`) | IM 36K10L10 §4 says the `opcdbg` *Dump classes/objects* files can be read by `dssqld`. The files have no `@LANGUAGE`/`@FIELDS`/`@<dataset>` headers (`NAME,"desc",prio` + source lines prefixed `- `); `dssqld -i` on the object dump gave `DSS-E-UNK_DS_NM, Unknown data set name`. | open | Use `dssqld -e CLASS_DF` / `OBJECT_DF` for transfers. Maybe an old tool reads the dump format; not found. | `knowledge/manuals/IM36K10L10-01EN.md` §4; `.claude/skills/class-object-engineering/tasks/opcdbg-checks.md` |
| ISS-028 | 2026-09-30 | PROCESS (class reset) | After recompiling a class with objects (`RESET_REQUIRED` 1), `dssqld -m` with `CLASS_DF` `RESET` = 1 (also with `RESET_NODE` = host node name) is accepted with 0 errors but does not reset; `OBJECT_DF` `RESET` = 1 is refused (`OPC-E-OBJ_RSTREQ`). `opcdbg` Classes → 8 *Reset class* works; it asks for a reset report file, which the manual does not list. | open | Use `opcdbg`. 2026-10-01: `CLASS_RESET_COMMAND` cannot be driven by `dssqld` (read/update only; no record to update — *Not found*; insert `DSS-E-NO_AUTH`). Test class `CIENG_INCR` was recompiled and reset again with `opcdbg` (`RESET_REQUIRED` back to 0). Engineering Module reset verified by the user 2026-10-01: *Configuration › I/O processing › Classes* › right-click the class › *Reset* opens *Class - reset* (reset node, *Force extended reset*, *Abort after first failure*, progress, reset report) — the GUI for `CLASS_RESET_COMMAND`; *Reset* reset 1 of 1 object, `RESET_REQUIRED` back to 0, object running. Ready to close. | `.claude/skills/class-object-engineering/tasks/change-reset-class.md`; `knowledge/manuals/IM36K10L10-01EN.md` §4 | | ISS-028 | 2026-09-30 | PROCESS (class reset) | After recompiling a class with objects (`RESET_REQUIRED` 1), `dssqld -m` with `CLASS_DF` `RESET` = 1 (also with `RESET_NODE` = host node name) is accepted with 0 errors but does not reset; `OBJECT_DF` `RESET` = 1 is refused (`OPC-E-OBJ_RSTREQ`). `opcdbg` Classes → 8 *Reset class* works; it asks for a reset report file, which the manual does not list. | open | Use `opcdbg`. Still to try: `CLASS_RESET_COMMAND` (system-wide) and the Engineering Module's reset. | `.claude/skills/class-object-engineering/tasks/change-reset-class.md`; `knowledge/manuals/IM36K10L10-01EN.md` §4 |
| ISS-029 | 2026-09-30 | PROCESS (Java) | IM 36K10P11 §10.4 says a new Java class must be reset before objects are added, otherwise the code does not take effect. A Java class inserted with `COMPILE` 1 by `dssqld` ran its first object correctly without any reset (twice, including a full sample reload). | open | Installed behaviour is the reference; keep "reset after changing a class that has objects". Check whether the Engineering Module path (compile without quick load) behaves differently. | `knowledge/manuals/IM36K10P11-01EN.md` §7; `.claude/skills/class-object-engineering/tasks/java-class.md` | | ISS-029 | 2026-09-30 | PROCESS (Java) | IM 36K10P11 §10.4 says a new Java class must be reset before objects are added, otherwise the code does not take effect. A Java class inserted with `COMPILE` 1 by `dssqld` ran its first object correctly without any reset (twice, including a full sample reload). | open | Installed behaviour is the reference; keep "reset after changing a class that has objects". Check whether the Engineering Module path (compile without quick load) behaves differently. | `knowledge/manuals/IM36K10P11-01EN.md` §7; `.claude/skills/class-object-engineering/tasks/java-class.md` |
| ISS-030 | 2026-10-01 | BUS (UMH tools) | `umhman` (hex code → text) crashes with redirected input (bash: segmentation fault 139 with CRLF input; PowerShell `Start-Process -RedirectStandardInput`: 0xC0000005); with an argument it only prompts. `umhtestprog` prints `UMH TEST UTILITY` and crashes (segmentation fault). `umhmsg 8010008` stops with `umh_panic: …umhmsg.exe, license expired` although other tools (`dssqld`, `itmval`) still worked at that time. | open | Retested 2026-10-01 right after a CI Server restart: all three work — `umhman` with piped input (bash, LF or CRLF; via `cmd <` too), `umhmsg 083A001B text "…"` writes the message to `umhlog.log` (process `UMHMSG_<pid>`, prints nothing), `umhtestprog` runs its self-test. The earlier failures came late in an unlicensed session (licence nearly expired). `itmval -f` (ISS-022) still crashes on a fresh start, so it is a separate fault. Ready to close. | `.claude/skills/system-management/tasks/bus-utilities.md`; `knowledge/manuals/IM36K10L30-01EN.md` §3 | | ISS-030 | 2026-10-01 | BUS (UMH tools) | `umhman` (hex code → text) crashes with redirected input (bash: segmentation fault 139 with CRLF input; PowerShell `Start-Process -RedirectStandardInput`: 0xC0000005); with an argument it only prompts. `umhtestprog` prints `UMH TEST UTILITY` and crashes (segmentation fault). `umhmsg 8010008` stops with `umh_panic: …umhmsg.exe, license expired` although other tools (`dssqld`, `itmval`) still worked at that time. | open | Try `umhman` interactively in a console; check `umhmsg` on a licensed system. Similar to ISS-022 (`itmval -f`). | `.claude/skills/system-management/tasks/bus-utilities.md`; `knowledge/manuals/IM36K10L30-01EN.md` §3 |
| ISS-031 | 2026-10-01 | LICENCE (unlicensed node) | The unlicensed test node counts down about 1 hour of run time per CI Server start (`License time left` in `smd_<node>_LOW_smdsnp_general.log`, 3600 s → `*** license problem : 3 ***`); then `dssqld`/`itmval` stop with `license expired` and `ISF-F-LIC_PROB, DATABASE Service is not licensed`. A PC sleep pauses the count (start 17:25, ran out 09:52 next day). Restart of the CI Service resets it (verified 2026-10-01, back after ~45 s). | closed | Closed 2026-10-01 (confirmed by user): known limitation of the unlicensed test system, documented in system-check. Known limitation of the test system, documented in `system-check`. Plan tests in ≤ 1 h blocks. Close when the user confirms. | `.claude/skills/system-check/SKILL.md` §3 (done) | | ISS-031 | 2026-10-01 | LICENCE (unlicensed node) | The unlicensed test node counts down about 1 hour of run time per CI Server start (`License time left` in `smd_<node>_LOW_smdsnp_general.log`, 3600 s → `*** license problem : 3 ***`); then `dssqld`/`itmval` stop with `license expired` and `ISF-F-LIC_PROB, DATABASE Service is not licensed`. A PC sleep pauses the count (start 17:25, ran out 09:52 next day). Restart of the CI Service resets it (verified 2026-10-01, back after ~45 s). | closed | Closed 2026-10-01 (confirmed by user): known limitation of the unlicensed test system, documented in system-check. Known limitation of the test system, documented in `system-check`. Plan tests in ≤ 1 h blocks. Close when the user confirms. | `.claude/skills/system-check/SKILL.md` §3 (done) |
| ISS-032 | 2026-10-01 | ACCESS (OPC UA server node IDs) | IM 36K10L45 §10.3 shows CI Server node IDs (`{"nsid":"32"}`, `{"0":"Value","itnm":"ITEM1"}`) and the CI Server namespace `http://www.yokogawa.com/CI_Server/` (ns 3) but not which namespace the **entities** use. With that URI (or `urn:<host>:Yokogawa:CI_SERVER_OPC_UA_SERVER`) the client point was silently not monitored. Browsing (`OPCUAC_TAG_DF`) shows sections/items in **`urn:Yokogawa:CI_SERVER_OPC_UA_SERVER`**; with it `{"0":"Value","itnm":"<item>"}` and `{"0":"Value","nsid":"<n>"}` both work. IM 36K10E20 §2.2.6 also asks to enable `OPXUAS_USE_NAME_NODEIDS` and restart for CI client ↔ CI server; not needed on the test system. | closed | Closed 2026-10-01 (user decision: installed software is the reference). Installed software is the reference (standing user decision). Close when the user confirms. | `knowledge/manuals/IM36K10L45-01EN.md` §7 (done); `knowledge/manuals/IM36K10E20-01EN.md` §3 (done); `.claude/skills/data-access/tasks/opcua-client.md` (done) | | ISS-032 | 2026-10-01 | ACCESS (OPC UA server node IDs) | IM 36K10L45 §10.3 shows CI Server node IDs (`{"nsid":"32"}`, `{"0":"Value","itnm":"ITEM1"}`) and the CI Server namespace `http://www.yokogawa.com/CI_Server/` (ns 3) but not which namespace the **entities** use. With that URI (or `urn:<host>:Yokogawa:CI_SERVER_OPC_UA_SERVER`) the client point was silently not monitored. Browsing (`OPCUAC_TAG_DF`) shows sections/items in **`urn:Yokogawa:CI_SERVER_OPC_UA_SERVER`**; with it `{"0":"Value","itnm":"<item>"}` and `{"0":"Value","nsid":"<n>"}` both work. IM 36K10E20 §2.2.6 also asks to enable `OPXUAS_USE_NAME_NODEIDS` and restart for CI client ↔ CI server; not needed on the test system. | closed | Closed 2026-10-01 (user decision: installed software is the reference). Installed software is the reference (standing user decision). Close when the user confirms. | `knowledge/manuals/IM36K10L45-01EN.md` §7 (done); `knowledge/manuals/IM36K10E20-01EN.md` §3 (done); `.claude/skills/data-access/tasks/opcua-client.md` (done) |
| ISS-033 | 2026-10-01 | ACCESS (Engineering Module OPC UA point) | Tested by the user: the point form's *Browse path* stops at the item (`Objects/CI-Eng-Sample/TANK1/INFLOW`) and stores the item **object** `{"nsid":"548"}`; the point is not monitored (revised sampling interval 0, connected item status 13, *Last value*/*Data type* empty). Typing `{"0":"Value","itnm":"CI-Eng-Sample.TANK1.INFLOW"}` in *Node Id* fixed it (values followed at once). Browsing into an item that is OPC visible but not *Read* fails (`UncertainNotAllNodesAvailable`, `OPXC-E-BRW_NODE`). | open | Answered 2026-10-01 by the user: the browse dialog can expand the item; picking `…/LEVEL/Value` stored `{"0":"Value","nsid":"713"}` with *Last value* 85, *Data type* Double. So: pick the `Value` node, not the item. The `itnm` form stays the choice for quick load (`nsid` changes on reload). Ready to close. | `knowledge/manuals/IM36K10E20-01EN.md` §2 (done); `.claude/skills/data-access/tasks/opcua-client.md` §3 (done) | | ISS-033 | 2026-10-01 | ACCESS (Engineering Module OPC UA point) | Tested by the user: the point form's *Browse path* stops at the item (`Objects/CI-Eng-Sample/TANK1/INFLOW`) and stores the item **object** `{"nsid":"548"}`; the point is not monitored (revised sampling interval 0, connected item status 13, *Last value*/*Data type* empty). Typing `{"0":"Value","itnm":"CI-Eng-Sample.TANK1.INFLOW"}` in *Node Id* fixed it (values followed at once). Browsing into an item that is OPC visible but not *Read* fails (`UncertainNotAllNodesAvailable`, `OPXC-E-BRW_NODE`). | open | Check whether the browse dialog can expand an item to `Value` (e.g. double-click); otherwise type the node ID. | `knowledge/manuals/IM36K10E20-01EN.md` §2 (done); `.claude/skills/data-access/tasks/opcua-client.md` §3 (done) |
| ISS-034 | 2026-10-01 | ACCESS (OPC UA server setup) | Installed vs IM 36K10L45 §10.5–10.6: `ServerConfig.xml` enables certificate user tokens (`EnableCertificate true`, manual false) and offers no `None` endpoint (only Basic256Sha256 / Aes128_Sha256_RsaOaep / Aes256_Sha256_RsaPss with Sign or SignAndEncrypt); the `rejected` folder is created only at the first rejection; `opxuas.sup` uses `OPXUAS_DYNAMIC_SCANRATE` (manual `OPXUAS_USE_DYNAMIC_SCANRATE`) and has `OPXUAS_SET_HIGH_PRIO_15` (not described); `opxsys.sup` has `OPXDAS_SET_LOG_LEVEL` (not described). Also `dur.sup` adaptive queue entry `OPCEXE` while the installed executors are `OPCEXE1`–`4`. | closed | Closed 2026-10-01 (user decision: installed software is the reference). Installed software is the reference (standing user decision). Close when the user confirms. | `knowledge/manuals/IM36K10L45-01EN.md` §4, §7 (done); `knowledge/manuals/IM36K10L30-01EN.md` §8 (done) | | ISS-034 | 2026-10-01 | ACCESS (OPC UA server setup) | Installed vs IM 36K10L45 §10.5–10.6: `ServerConfig.xml` enables certificate user tokens (`EnableCertificate true`, manual false) and offers no `None` endpoint (only Basic256Sha256 / Aes128_Sha256_RsaOaep / Aes256_Sha256_RsaPss with Sign or SignAndEncrypt); the `rejected` folder is created only at the first rejection; `opxuas.sup` uses `OPXUAS_DYNAMIC_SCANRATE` (manual `OPXUAS_USE_DYNAMIC_SCANRATE`) and has `OPXUAS_SET_HIGH_PRIO_15` (not described); `opxsys.sup` has `OPXDAS_SET_LOG_LEVEL` (not described). Also `dur.sup` adaptive queue entry `OPCEXE` while the installed executors are `OPCEXE1`–`4`. | closed | Closed 2026-10-01 (user decision: installed software is the reference). Installed software is the reference (standing user decision). Close when the user confirms. | `knowledge/manuals/IM36K10L45-01EN.md` §4, §7 (done); `knowledge/manuals/IM36K10L30-01EN.md` §8 (done) |
| ISS-035 | 2026-10-01 | ALARM (`ALDPRT`) | `ALDPRT` is running and connected (`almdbg` 1 shows `Events-send-to` rising with each alarm), `aldprt.sup` sets no log destination (so per IM 36K10L15 §4.3 it should log via UMH) and `EVENTS` includes `alarm`/`ackn`, but no alarm line appears in `tls\log\umhlog.log` for the CI-Eng-Sample HIGH / HIGH HIGH / acknowledge events. No other log file changed. Cause unknown (UMH filtering? output only with `LOGUMH` set explicitly?). | open | Rechecked 2026-10-01 after a restart: `aldprt.exe` runs; `umhlog.log` still has no alarm lines for the new `TANK1.LEVEL` HIGH alarm (only `ALD-I-ALDPRT_EXIT` at each licence shutdown). `fmfprt.sup` assigns printer function `ALARMS` to `ALDPRT`; destination `ALARMS` (policy *Automatic*) has **no device**, and `PRINTER_JOB_OVV` has no `ALDPRT` jobs. The `aldprt.sup` help says UMH is used only when no destination is enabled — the printer function may count as one. Next: test `LOGUMH` in `aldprt.sup` (admin, restart). Low priority: history and overviews are not affected. | `.claude/skills/alarm-management/tasks/item-alarming.md` (last line); `knowledge/manuals/IM36K10L15-01EN.md` §8 | | ISS-035 | 2026-10-01 | ALARM (`ALDPRT`) | `ALDPRT` is running and connected (`almdbg` 1 shows `Events-send-to` rising with each alarm), `aldprt.sup` sets no log destination (so per IM 36K10L15 §4.3 it should log via UMH) and `EVENTS` includes `alarm`/`ackn`, but no alarm line appears in `tls\log\umhlog.log` for the CI-Eng-Sample HIGH / HIGH HIGH / acknowledge events. No other log file changed. Cause unknown (UMH filtering? output only with `LOGUMH` set explicitly?). | open | Ask the user whether alarm lines were ever seen in the message log; possibly test `LOGUMH` (or `LOGSCN`) in `aldprt.sup` (admin, restart) in a later session. Low priority: history and overviews are not affected. | `.claude/skills/alarm-management/tasks/item-alarming.md` (last line); `knowledge/manuals/IM36K10L15-01EN.md` §8 |
| ISS-036 | 2026-10-01 | ALARM (setup) | Installed vs manuals: `alh.sup` has `DB-JRNL = WAL` and `DB-SYNC = OFF`, not described in IM 36K10L15 §3.4; storage group `ALH` has lifetime **52 weeks** while IM 36K10C20 §A7 says the default is 2 days (may have been changed on this system earlier — unknown); `aldprt.sup` uses `TIMEFMT` where the manual text also writes `TIMFMT`. | closed | Installed software is the reference (standing user decision). Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10L15-01EN.md` §7, §8; `knowledge/manuals/IM36K10C20-01EN.md` §A7 | | ISS-036 | 2026-10-01 | ALARM (setup) | Installed vs manuals: `alh.sup` has `DB-JRNL = WAL` and `DB-SYNC = OFF`, not described in IM 36K10L15 §3.4; storage group `ALH` has lifetime **52 weeks** while IM 36K10C20 §A7 says the default is 2 days (may have been changed on this system earlier — unknown); `aldprt.sup` uses `TIMEFMT` where the manual text also writes `TIMFMT`. | closed | Installed software is the reference (standing user decision). Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10L15-01EN.md` §7, §8; `knowledge/manuals/IM36K10C20-01EN.md` §A7 |
| ISS-037 | 2026-10-01 | ALARM (history fields) | `ALARM_CHRONO` records contain leftover or unreadable text: INFO events generated with `almdbg` 16 carry `INSTALL`/`UNIT`/`TAG`/`SUB` values from earlier events and non-ASCII bytes in `SOURCE`, `CATEGORY`, `CONDITION`; item events of `CI-Eng-Sample.TANK1.LEVEL` show `SUB` = `RoC` although the item has only the sub-item `MAX`. | open | Rechecked 2026-10-01 after a restart: a new HIGH alarm on `CI-Eng-Sample.TANK1.LEVEL` (raised with `itmval -p`) gave a clean `ALARM_CHRONO` record (`INSTALL`/`UNIT`/`TAG` correct, `SUB` empty, `SOURCE`/`CATEGORY`/`CONDITION` empty), and the user's Current Alarm Overview showed correct columns. The leftover/garbled values are limited to the older records (INFO events made with the `almdbg` 16 test function and events from that session). Documented: treat `SUB`/`SOURCE`/`CATEGORY`/`CONDITION` as reliable only for normal item and OPC events. Ready to close. | `.claude/skills/alarm-management/tasks/alarm-checks.md` §4 | | ISS-037 | 2026-10-01 | ALARM (history fields) | `ALARM_CHRONO` records contain leftover or unreadable text: INFO events generated with `almdbg` 16 carry `INSTALL`/`UNIT`/`TAG`/`SUB` values from earlier events and non-ASCII bytes in `SOURCE`, `CATEGORY`, `CONDITION`; item events of `CI-Eng-Sample.TANK1.LEVEL` show `SUB` = `RoC` although the item has only the sub-item `MAX`. | open | Check whether the alarm overview shows the same (phase 10, needs a display). Treat these columns as unreliable for non-OPC events until then. | `.claude/skills/alarm-management/tasks/alarm-checks.md` §4 |
| ISS-038 | 2026-10-01 | HISTORY (`ithloahis` + rollover) | An `ithloahis` sample that was dropped (dated 11:50, before the active unit) still became the **initial value** of the next unit: after a forced rollover at 12:05:26 `ITEM_HISTORY` shows `CI-Eng-Sample.TANK1.INFLOW` = 95 (`INITIAL_VALUE` 1) although the item's value was 112. History after loading old samples can therefore show a wrong value at the next rollover. | open | Retested 2026-10-01 after a CI Server restart (first unit 18:05:46). (a) Sample dated one day earlier (95), live value 112, forced rollover: initial value 112 — correct. (b) Sample dated 18:00 (96, a few minutes before the first unit), live value 113, forced rollover: initial value **96** — wrong again; the live item value stayed 113. So a dropped sample dated shortly before the first unit (same day) becomes the next unit's initial value; a much older one did not. Also found: a forced rollover within 2 minutes of the previous one is refused (`DSI-E-ROLLDONE`). Documented as a caution; behaviour confirmed, ready to close. | `.claude/skills/system-management/tasks/load-history.md`; `knowledge/manuals/IM36K10C40-01EN.md` §3 | | ISS-038 | 2026-10-01 | HISTORY (`ithloahis` + rollover) | An `ithloahis` sample that was dropped (dated 11:50, before the active unit) still became the **initial value** of the next unit: after a forced rollover at 12:05:26 `ITEM_HISTORY` shows `CI-Eng-Sample.TANK1.INFLOW` = 95 (`INITIAL_VALUE` 1) although the item's value was 112. History after loading old samples can therefore show a wrong value at the next rollover. | open | Accept as a caution (documented in `load-history.md`), or retest after a CI Server restart to see whether the wrong initial value persists. | `.claude/skills/system-management/tasks/load-history.md`; `knowledge/manuals/IM36K10C40-01EN.md` §3 |
| ISS-039 | 2026-10-01 | HISTORY (setup) | Installed vs manuals: `hisdbg` menu runs to option 22 (manual text: `-1 - 10`, list to 22) and lists history types 4 (`STATION_STAT`) and 36 (`SYS_LOG`) not in IM 36K10L20 §3.1; `ithsag.sup` keyword `run_interval` (manual: *Heartbeat*) and `queue_size` 500 KB (manual default 200); the option-type table in IM 36K10L20 §3.1 is garbled in the PDF (observed: Scan/Time `1 1`, Event/Item `2 2`, Aggregation `4 4`). | closed | Installed software is the reference (standing user decision). Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10L20-01EN.md` §3; `knowledge/manuals/IM36K10C40-01EN.md` §2 | | ISS-039 | 2026-10-01 | HISTORY (setup) | Installed vs manuals: `hisdbg` menu runs to option 22 (manual text: `-1 - 10`, list to 22) and lists history types 4 (`STATION_STAT`) and 36 (`SYS_LOG`) not in IM 36K10L20 §3.1; `ithsag.sup` keyword `run_interval` (manual: *Heartbeat*) and `queue_size` 500 KB (manual default 200); the option-type table in IM 36K10L20 §3.1 is garbled in the PDF (observed: Scan/Time `1 1`, Event/Item `2 2`, Aggregation `4 4`). | closed | Installed software is the reference (standing user decision). Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10L20-01EN.md` §3; `knowledge/manuals/IM36K10C40-01EN.md` §2 |
| ISS-040 | 2026-10-01 | HISTORY (aggregation) | Aggregation group `CIENG_AGG` (30 min + hour, `TANK1.LEVEL` max/min/avg) ran (`ithsag.log`: *Aggregation Completed*) but stored no values: retrieval gave `0x09 = ITM error` per period. `TANK1.LEVEL` was in `CIENG_EVENT` and `CIENG_SCAN10S`, both priority 0. Also `INTERPOLATION = "30 minutes"` is refused by `dssqld`; the installed name is `30Minutes`. | closed | Closed 2026-10-01 (confirmed by user). 2026-10-01 14:02: after `CIENG_SCAN10S` got `PRIORITY` 10, the 13:30–14:00 period stored max 77, min 33, avg 52.7, quality 1000 (`ithdbg` 20 and `dssqld` with `INTERPOLATION = "30Minutes"`). Cause: equal source priorities (C40 §2.1 says the highest-priority group is the source, but not that a tie gives nothing). Sample fixed (priority 10). The hourly value for 13:00–14:00 was not stored (first half had no source); not rechecked. Proposed close. | `.claude/skills/history-management/tasks/storage-groups.md` §4 (done); `knowledge/manuals/IM36K10C40-01EN.md` §3 (done); `examples/CI-Eng-Sample/03_his_group_df.qli`, `README.md` (done) | | ISS-040 | 2026-10-01 | HISTORY (aggregation) | Aggregation group `CIENG_AGG` (30 min + hour, `TANK1.LEVEL` max/min/avg) ran (`ithsag.log`: *Aggregation Completed*) but stored no values: retrieval gave `0x09 = ITM error` per period. `TANK1.LEVEL` was in `CIENG_EVENT` and `CIENG_SCAN10S`, both priority 0. Also `INTERPOLATION = "30 minutes"` is refused by `dssqld`; the installed name is `30Minutes`. | closed | Closed 2026-10-01 (confirmed by user). 2026-10-01 14:02: after `CIENG_SCAN10S` got `PRIORITY` 10, the 13:30–14:00 period stored max 77, min 33, avg 52.7, quality 1000 (`ithdbg` 20 and `dssqld` with `INTERPOLATION = "30Minutes"`). Cause: equal source priorities (C40 §2.1 says the highest-priority group is the source, but not that a tie gives nothing). Sample fixed (priority 10). The hourly value for 13:00–14:00 was not stored (first half had no source); not rechecked. Proposed close. | `.claude/skills/history-management/tasks/storage-groups.md` §4 (done); `knowledge/manuals/IM36K10C40-01EN.md` §3 (done); `examples/CI-Eng-Sample/03_his_group_df.qli`, `README.md` (done) |
| ISS-041 | 2026-10-01 | GRAPHICS (HTML trend) | In the HTML display (`localhost:8080/mobileoperator/?d=CIENG_Tank`) the trend shows the pen legend `CI-Eng-Sample.TANK1.LEVEL [CIENG_SCAN10S]` and time axis but draws no line, although `ITEM_HISTORY` has 420 samples in the shown hour. Browser console: `Mismatch between number of labels (Time,CI-Eng-Sample.TANK1.LEVEL [CIENG_SCAN10S]) and number of columns in array (51)`. The trend has 4 further empty pens. 2026-10-01 later: the trend also had the property `chart.attribute[00]` connected to `TANK1.LEVEL` (added by mistake with the pen); the Operator Interface (desktop) showed *Short attribute name ( 61.0) is invalid*. After removing it the desktop trend draws the line, but the HTML trend still logs the mismatch error. | open | Tried 2026-10-01 (fresh session after a restart, 283 history samples in the hour): removing the 4 empty pens, and `updating` true / `updateInterval` 10 like the factory `AOG_TrendOpen` — the mismatch error and the empty trend stayed in both cases (changes reverted). Still to try: a Micro Trend, the HTML-supported trend properties (IM 36K10R30 §4.8.7), clearing the browser/`MO_CACHE_DISPLAYS` cache (the console shows `CIENG_Tank.xml` *loaded (from cache)*), and adding the pen to the factory *Open Trend* display in the HTML client. | `.claude/skills/graphics/tasks/create-display.md`; `knowledge/manuals/IM36K10R30-01EN.md` §4 | | ISS-041 | 2026-10-01 | GRAPHICS (HTML trend) | In the HTML display (`localhost:8080/mobileoperator/?d=CIENG_Tank`) the trend shows the pen legend `CI-Eng-Sample.TANK1.LEVEL [CIENG_SCAN10S]` and time axis but draws no line, although `ITEM_HISTORY` has 420 samples in the shown hour. Browser console: `Mismatch between number of labels (Time,CI-Eng-Sample.TANK1.LEVEL [CIENG_SCAN10S]) and number of columns in array (51)`. The trend has 4 further empty pens. 2026-10-01 later: the trend also had the property `chart.attribute[00]` connected to `TANK1.LEVEL` (added by mistake with the pen); the Operator Interface (desktop) showed *Short attribute name ( 61.0) is invalid*. After removing it the desktop trend draws the line, but the HTML trend still logs the mismatch error. | open | HTML only: try a trend with one pen (remove the empty ones) or a Micro Trend; check the HTML-supported trend properties (IM 36K10R30 §4.8.7); check whether the browser still uses a cached copy (`MO_CACHE_DISPLAYS` in `jwuiisg.sup`). | `.claude/skills/graphics/tasks/create-display.md`; `knowledge/manuals/IM36K10R30-01EN.md` §4 |
| ISS-042 | 2026-10-01 | GRAPHICS (layouts) | Installed vs `Layouts.readme`: the factory layouts use status line item types `displayName`, `playbackIndicator` and `dateTime` and the commands `reload <frame>` / `reload all`, none of which the readme lists (readme: `statusText`, `userName`, `progresBar`, `graphicsQueueLevel`, `connectionState`); the readme also writes `zooom` for the zoom command (factory files use `zoom`). | closed | Installed software is the reference (standing user decision). Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/graphics/tasks/layouts.md` §2 | | ISS-042 | 2026-10-01 | GRAPHICS (layouts) | Installed vs `Layouts.readme`: the factory layouts use status line item types `displayName`, `playbackIndicator` and `dateTime` and the commands `reload <frame>` / `reload all`, none of which the readme lists (readme: `statusText`, `userName`, `progresBar`, `graphicsQueueLevel`, `connectionState`); the readme also writes `zooom` for the zoom command (factory files use `zoom`). | closed | Installed software is the reference (standing user decision). Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/graphics/tasks/layouts.md` §2 |
| ISS-043 | 2026-10-01 | REPORT (system reports) | IM 36K10C30 App. 1.3 names two system reports `ALM_ATTS_CUR` and `ALM_ATRS_HIS`; the installed reports are `ALM_ATTRS_CUR` and `ALM_ATTRS_HIS`. The other 26 names match. | closed | Installed software is the reference (standing user decision). Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10C30-01EN.md` §8 (done) | | ISS-043 | 2026-10-01 | REPORT (system reports) | IM 36K10C30 App. 1.3 names two system reports `ALM_ATTS_CUR` and `ALM_ATRS_HIS`; the installed reports are `ALM_ATTRS_CUR` and `ALM_ATTRS_HIS`. The other 26 names match. | closed | Installed software is the reference (standing user decision). Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10C30-01EN.md` §8 (done) |
| ISS-044 | 2026-10-01 | REPORT (scheduling) | Behaviour not in the manuals, found by quick load: a generation interval below 10 minutes is refused (`HIS-E-ROLLTOFAST`, the interval is the rollover of the report's storage group); a scheduled report cannot be deleted (`RPT-E-ACTIVE`) until `ACTIVATION_TIME` and `GENERATION_INTERVAL` are cleared; `CORRECT_DAYLIGHT` 0 counts intervals in UTC (06:00 set for January ran at 05:00 in October); a past activation time moves to the next slot - once (modify, past time within the lifetime) a single report labelled with the old time was generated, at insert with an older time none. | closed | Documented as verified behaviour; the one-off generation for a past activation time is not fully understood. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/reporting/tasks/define-reports.md` §1, §5, §6; `knowledge/manuals/IM36K10C30-01EN.md` §2; `examples/CI-Eng-Sample/83a_stop_report_df.qli`, `18_report_df.qli` | | ISS-044 | 2026-10-01 | REPORT (scheduling) | Behaviour not in the manuals, found by quick load: a generation interval below 10 minutes is refused (`HIS-E-ROLLTOFAST`, the interval is the rollover of the report's storage group); a scheduled report cannot be deleted (`RPT-E-ACTIVE`) until `ACTIVATION_TIME` and `GENERATION_INTERVAL` are cleared; `CORRECT_DAYLIGHT` 0 counts intervals in UTC (06:00 set for January ran at 05:00 in October); a past activation time moves to the next slot - once (modify, past time within the lifetime) a single report labelled with the old time was generated, at insert with an older time none. | closed | Documented as verified behaviour; the one-off generation for a past activation time is not fully understood. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/reporting/tasks/define-reports.md` §1, §5, §6; `knowledge/manuals/IM36K10C30-01EN.md` §2; `examples/CI-Eng-Sample/83a_stop_report_df.qli`, `18_report_df.qli` |
| ISS-045 | 2026-10-01 | REPORT (ad hoc from `dssqld`) | Generating ad hoc with `REPORT_DF.GENERATE` = 1 from `dssqld` (user `FULL AUTHORIZATION`) on a report without `ADHOC_DEST` logs `FSL-E-PRT_UNKUSER, Job submitted by unknown user (FULL AUTHORIZATION)` and `RPT-I-TRYPRINT` in `umhlog.log`; the generated report is stored normally. Phase 12 correction (2026-10-01): with `ADHOC_DEST` set the same error appears and nothing is printed (`CIENG_AUDIT`, `CIENG_TANK1` after a sample reload); the same report generated from the Engineering Module as `ADMIN` printed to `CIENG_FILE`. Related to the R1.03 known issue on report generation and default printers (IM 36K01A50, REPORT 1.11). | closed | Workaround documented: generate from the Engineering Module when printed output is needed (as `ADMIN` with destination `CIENG_FILE` it printed without errors, phases 11 and 12); runs from `dssqld` are stored but never printed, `ADHOC_DEST` does not help. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/reporting/tasks/define-reports.md` §2; `knowledge/manuals/IM36K10C30-01EN.md` §6 | | ISS-045 | 2026-10-01 | REPORT (ad hoc from `dssqld`) | Generating ad hoc with `REPORT_DF.GENERATE` = 1 from `dssqld` (user `FULL AUTHORIZATION`) on a report without `ADHOC_DEST` logs `FSL-E-PRT_UNKUSER, Job submitted by unknown user (FULL AUTHORIZATION)` and `RPT-I-TRYPRINT` in `umhlog.log`; the generated report is stored normally. Phase 12 correction (2026-10-01): with `ADHOC_DEST` set the same error appears and nothing is printed (`CIENG_AUDIT`, `CIENG_TANK1` after a sample reload); the same report generated from the Engineering Module as `ADMIN` printed to `CIENG_FILE`. Related to the R1.03 known issue on report generation and default printers (IM 36K01A50, REPORT 1.11). | closed | Workaround documented: generate from the Engineering Module when printed output is needed (as `ADMIN` with destination `CIENG_FILE` it printed without errors, phases 11 and 12); runs from `dssqld` are stored but never printed, `ADHOC_DEST` does not help. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/reporting/tasks/define-reports.md` §2; `knowledge/manuals/IM36K10C30-01EN.md` §6 |
| ISS-046 | 2026-10-01 | DATABASE (`dssqld` memo) | A memo field loaded from a file (`@"<file>"@`, IM 36K10L50 §3.10) fails with a relative name (`CRL-E-ENOENT`, the file is read on the server side) and with a long absolute path (`DSSG-E-STRBUFSMAL`, buffer 83); a short absolute path works. The manual gives no limits. | closed | Documented: use inline memos, or an absolute path ≤ 82 characters. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/system-management/tasks/dss-tools.md` §2; `knowledge/manuals/IM36K10L50-01EN.md` §4 | | ISS-046 | 2026-10-01 | DATABASE (`dssqld` memo) | A memo field loaded from a file (`@"<file>"@`, IM 36K10L50 §3.10) fails with a relative name (`CRL-E-ENOENT`, the file is read on the server side) and with a long absolute path (`DSSG-E-STRBUFSMAL`, buffer 83); a short absolute path works. The manual gives no limits. | closed | Documented: use inline memos, or an absolute path ≤ 82 characters. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/system-management/tasks/dss-tools.md` §2; `knowledge/manuals/IM36K10L50-01EN.md` §4 |
| ISS-047 | 2026-10-01 | REPORT (RQL manuals) | The manuals disagree: default `@WORKSPACE` 500 KB (IM 36K10R40 §2.2.2) vs 16 KB (IM 36K10C30 table 2.1-1, IM 36K10P20 §9.6); maximum `@WIDTH` 512 (R40, P20 §4) vs 5000 (P20 §9.6); `@FORMFEED` described with opposite meanings (C30: not 1 = form feed; P20: 0 = blank lines, default 1). Installed set-up files set `@workspace` explicitly (500 in `rptge1.rpt`, 100 in `rptgen.rpt`) and `@formfeed 0` for the interactive generator. | closed | Not tested (no printer); the set-up files make the defaults irrelevant in practice. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10R40-01EN.md` §2; `knowledge/manuals/IM36K10P20-01EN.md` §3 | | ISS-047 | 2026-10-01 | REPORT (RQL manuals) | The manuals disagree: default `@WORKSPACE` 500 KB (IM 36K10R40 §2.2.2) vs 16 KB (IM 36K10C30 table 2.1-1, IM 36K10P20 §9.6); maximum `@WIDTH` 512 (R40, P20 §4) vs 5000 (P20 §9.6); `@FORMFEED` described with opposite meanings (C30: not 1 = form feed; P20: 0 = blank lines, default 1). Installed set-up files set `@workspace` explicitly (500 in `rptge1.rpt`, 100 in `rptgen.rpt`) and `@formfeed 0` for the interactive generator. | closed | Not tested (no printer); the set-up files make the defaults irrelevant in practice. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10R40-01EN.md` §2; `knowledge/manuals/IM36K10P20-01EN.md` §3 |
| ISS-048 | 2026-10-01 | REPORT (ad-hoc parameters) | The prompt `[ITEM:NAME like "CI-Eng-Sample.TANK1.*"]Item for statistics:` (filter form as in IM 36K10C30 §2.1) gives an item tree browser in the Engineering Module generate dialog, but the tree shows all sections, not only `TANK1` items (checked by the user). | open | Answered 2026-10-01 with a temporary report (removed), checked by the user: the filter is an `ITEM_DF` filter joined with `AND` to each tree node. It **does** limit the items: with `NAME like "CI-Eng-Sample.TANK1.*"` only TANK1 items (incl. `CALC.VOLUME`, `JFLOW.sPerMin`, `LEVEL.MAX`) appear and can be picked; sections and objects always stay in the tree, which is what the first check saw. `NAME like "*.L*"` and `DESCRIPTION like "Tank 1*"` also work; `%` is not a wildcard, `NAME = "….*"` matches nothing, `SECTION = …` gives `DSS-E-FLT_SYN_ERR`. Ready to close. | `.claude/skills/reporting/tasks/define-reports.md`; `knowledge/manuals/IM36K10C30-01EN.md` §2; `examples/CI-Eng-Sample/18_report_df.qli` comment | | ISS-048 | 2026-10-01 | REPORT (ad-hoc parameters) | The prompt `[ITEM:NAME like "CI-Eng-Sample.TANK1.*"]Item for statistics:` (filter form as in IM 36K10C30 §2.1) gives an item tree browser in the Engineering Module generate dialog, but the tree shows all sections, not only `TANK1` items (checked by the user). | open | Try other filter forms (`%` wildcard, `SECTION = …`, `[ITEM:TAG="…"]`) and the display report component. | `.claude/skills/reporting/tasks/define-reports.md`; `knowledge/manuals/IM36K10C30-01EN.md` §2; `examples/CI-Eng-Sample/18_report_df.qli` comment |
| ISS-049 | 2026-10-01 | AUDIT (item option *Audit trailing wanted*) | IM 36K10G10 ch. 9 and the classifier list (IM 36K10L25 App. 1, `ITEM.VALUE.MODIFY.<source>`, `ITEM.HIGH-LIMIT…`) suggest item changes are audited per item when `AUDIT_INFO` = 1. On R1.03.00 none of the tested tools produced an `ITEM.*` event: `itmval -p` writes are not audited at all (with `AUDIT_INFO` 0 or 1); value writes through DSS (`dssqld -m ITEM_VAL`) and Engineering Module *Update value* are audited as dataset events (`ITEM_VAL`, `ITEM_VALUE` / `ITEM_VALUE_STR` / `STATUS`) for every item regardless of `AUDIT_INFO`. Operator-display writes and PROCESS writes (`opc.sup` `AUDIT = YES`, `COMPUTE` classifiers off by default) were not tested (no input field in the sample displays). | open | Answered 2026-10-01: buttons *Manual (0)* / *Auto (1)* added to `CIENG_Tank` (`actionSetItemAttribute`, `ItemValue`). With `AUDIT_INFO` 1 a click stored `ITEM.VALUE.MODIFY.OPER-INTERFACE` (user `ADMIN`, 0 → 1) and `ITEM.STATUS.MODIFY` (13 → 9); with `AUDIT_INFO` 0 the next click (1 → 0) stored nothing. So *Audit trailing wanted* controls operator-write audits; DSS changes are always audited, `itmval` never. Sample: `19b_audit_item_df.qli`. PROCESS with `AUDIT = YES` not tested. Ready to close. | `.claude/skills/audit-trail/tasks/configure-audit.md` §1; `.claude/skills/audit-trail/tasks/read-audit-trail.md` §2; `knowledge/manuals/IM36K10L25-01EN.md` §3 | | ISS-049 | 2026-10-01 | AUDIT (item option *Audit trailing wanted*) | IM 36K10G10 ch. 9 and the classifier list (IM 36K10L25 App. 1, `ITEM.VALUE.MODIFY.<source>`, `ITEM.HIGH-LIMIT…`) suggest item changes are audited per item when `AUDIT_INFO` = 1. On R1.03.00 none of the tested tools produced an `ITEM.*` event: `itmval -p` writes are not audited at all (with `AUDIT_INFO` 0 or 1); value writes through DSS (`dssqld -m ITEM_VAL`) and Engineering Module *Update value* are audited as dataset events (`ITEM_VAL`, `ITEM_VALUE` / `ITEM_VALUE_STR` / `STATUS`) for every item regardless of `AUDIT_INFO`. Operator-display writes and PROCESS writes (`opc.sup` `AUDIT = YES`, `COMPUTE` classifiers off by default) were not tested (no input field in the sample displays). | open | Test an operator value input on an item with `AUDIT_INFO` 1 (needs a display with an input field) and, if wanted, PROCESS with `AUDIT = YES`. | `.claude/skills/audit-trail/tasks/configure-audit.md` §1; `.claude/skills/audit-trail/tasks/read-audit-trail.md` §2; `knowledge/manuals/IM36K10L25-01EN.md` §3 |
| ISS-050 | 2026-10-01 | AUDIT (classifier `STORAGE`) | Setting `AUDIT_EVENT_CLAS_DF.STORAGE` = 0 for `DATASET.NULL-ATTR.MODIFY.ENT-ENG-MOD` at 17:01:12 did not stop the next `dssqld -m ITEM_VAL` change from being stored (17:01:12.573). IM 36K10L25 §3.2 explains a per-process cache refreshed every `ECL_REFRESH` s (default 1800); the notifier here is `DSSSDA`, so the change should apply within 30 minutes. | closed | Re-tested: at 17:32:18 (after the 30-minute refresh) the same change was **not** stored, so the flag works with a delay. Set back to 1 at 17:32; the next change was still not stored (the cache works in both directions). Documented: allow up to `ECL_REFRESH` (1800 s) or restart CI Server. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/audit-trail/tasks/configure-audit.md` §1; `knowledge/manuals/IM36K10L25-01EN.md` §3 | | ISS-050 | 2026-10-01 | AUDIT (classifier `STORAGE`) | Setting `AUDIT_EVENT_CLAS_DF.STORAGE` = 0 for `DATASET.NULL-ATTR.MODIFY.ENT-ENG-MOD` at 17:01:12 did not stop the next `dssqld -m ITEM_VAL` change from being stored (17:01:12.573). IM 36K10L25 §3.2 explains a per-process cache refreshed every `ECL_REFRESH` s (default 1800); the notifier here is `DSSSDA`, so the change should apply within 30 minutes. | closed | Re-tested: at 17:32:18 (after the 30-minute refresh) the same change was **not** stored, so the flag works with a delay. Set back to 1 at 17:32; the next change was still not stored (the cache works in both directions). Documented: allow up to `ECL_REFRESH` (1800 s) or restart CI Server. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/audit-trail/tasks/configure-audit.md` §1; `knowledge/manuals/IM36K10L25-01EN.md` §3 |
| ISS-051 | 2026-10-01 | AUDIT (manual vs installed) | Differences between IM 36K10L25 and R1.03.00: (1) App. 1 lists subject `F/T-SYSTEM`, the installed classifiers use `CI-SERVER` (logins) and also `EAL OPERATION` (subject and action) and source `VIA-OPC-UAS`, not in the manual; 463 classifiers installed. (2) App. 1 explanations of `SHELVE` and `UN-SHELVE` are swapped. (3) `QUESIZE`: manual default and maximum 200 kB, `adtsys.sup` help default 10 kB, minimum 10 (file sets 200). (4) `TIMEFMT` default: manual `DD/MM/YY hh:mm:ss.ppp`, `adtsys.sup` help without `.ppp`; `ADTLOG` output shows milliseconds (manual right). (5) `dssqld` changes are recorded with source `ENT-ENG-MOD`, not `QUICKLOAD`. (6) The selection expression language is not described in the manual; the compiler listing gives the words and operators (no `LIKE`). (7) `ADT` group lifetime 52 weeks on the test system vs 2 days default when `ADTSTO` creates it (§2.1.1). | closed | Documented in the L25 summary and the `audit-trail` skill. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10L25-01EN.md`; `.claude/skills/audit-trail/tasks/*.md` | | ISS-051 | 2026-10-01 | AUDIT (manual vs installed) | Differences between IM 36K10L25 and R1.03.00: (1) App. 1 lists subject `F/T-SYSTEM`, the installed classifiers use `CI-SERVER` (logins) and also `EAL OPERATION` (subject and action) and source `VIA-OPC-UAS`, not in the manual; 463 classifiers installed. (2) App. 1 explanations of `SHELVE` and `UN-SHELVE` are swapped. (3) `QUESIZE`: manual default and maximum 200 kB, `adtsys.sup` help default 10 kB, minimum 10 (file sets 200). (4) `TIMEFMT` default: manual `DD/MM/YY hh:mm:ss.ppp`, `adtsys.sup` help without `.ppp`; `ADTLOG` output shows milliseconds (manual right). (5) `dssqld` changes are recorded with source `ENT-ENG-MOD`, not `QUICKLOAD`. (6) The selection expression language is not described in the manual; the compiler listing gives the words and operators (no `LIKE`). (7) `ADT` group lifetime 52 weeks on the test system vs 2 days default when `ADTSTO` creates it (§2.1.1). | closed | Documented in the L25 summary and the `audit-trail` skill. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10L25-01EN.md`; `.claude/skills/audit-trail/tasks/*.md` |
| ISS-052 | 2026-10-01 | GRAPHICS (stale item id) | The HTML display `CIENG_Tank` showed **0** in its number field on `CI-Eng-Sample.TANK1.LEVEL` (live value 50) and the popup `ITM-E-NO_MAIN, No main item found`, in a fresh session after a CI Server restart. The display XML stores `<itemName>` **and** `<itemId>1.1.268.0.0.1.1.7</itemId>` from when it was built; after today's sample reloads the item has `ID_NUMBER` 357. Phase 10 had seen live values after a reload, so the id is not always used, but here it broke the field. | open | Fixed in the sample: removed the `<itemId>` line from `displays/CIENG_Tank.xml`, redeployed; the field shows 50 and the popup is gone (binding by name). Documented in `create-display.md`. Close when the user confirms. | `examples/CI-Eng-Sample/displays/CIENG_Tank.xml`; `.claude/skills/graphics/tasks/create-display.md`; `.claude/skills/graphics/tasks/deploy-displays.md` |

View file

@ -44,9 +44,8 @@ lifetime.
Parameter prompt meta-information (makes a pick list in the generate dialog): `[ITEM:<filter>]`, Parameter prompt meta-information (makes a pick list in the generate dialog): `[ITEM:<filter>]`,
`[OBJECT:<class>:<filter>]`, `[DATE]`, `[TIME]`, `[DATE:TIME]`, `[LIST:a:b:c]`, followed by the `[OBJECT:<class>:<filter>]`, `[DATE]`, `[TIME]`, `[DATE:TIME]`, `[LIST:a:b:c]`, followed by the
prompt text, e.g. `[ITEM:NAME like "CI-Eng-Sample.TANK1.*"]Item for statistics:`. **Installed:** the prompt text, e.g. `[ITEM:NAME like "CI-Eng-Sample.TANK1.*"]Item for statistics:`. **Installed:** the
`[ITEM:…]` prompt opens an item tree browser in the generate dialog; the filter (an `ITEM_DF` `[ITEM:…]` prompt opens an item tree browser in the generate dialog, but the filter did not limit
filter, `*` wildcard, `like`) limits the **items** shown, while sections and objects always stay the tree (ISS-048). The installed
in the tree (ISS-048, verified). The installed
system reports use lower case (`[item]`, `[date:time]`, `[list:Days:Hours:Minutes]`). system reports use lower case (`[item]`, `[date:time]`, `[list:Days:Hours:Minutes]`).
Query editor: *Ctrl+Space* lists keywords, datasets and fields. Basics of RQL (§2.1) are Query editor: *Ctrl+Space* lists keywords, datasets and fields. Basics of RQL (§2.1) are

View file

@ -37,11 +37,10 @@ until event nodes are configured).
| Point | external relation Input / Output / Input + Output; subscription; *Namespace*, *Node id type*, *Node Id* (or *Browse path*); read-only *Last value*, *Data type*, *Access level*, *Value rank*; array element; options (own sampling interval, monitoring mode, queue size); conversion (offset, step) | | Point | external relation Input / Output / Input + Output; subscription; *Namespace*, *Node id type*, *Node Id* (or *Browse path*); read-only *Last value*, *Data type*, *Access level*, *Value rank*; array element; options (own sampling interval, monitoring mode, queue size); conversion (offset, step) |
| Method | namespace, node ID or browse path, process areas | | Method | namespace, node ID or browse path, process areas |
**Observed (2026-10-01)**: in the point form's browse, picking the item itself **Observed (2026-10-01)**: browsing in the point form stops at the item itself
(`Objects/<section>/…/<item>`) stores the item **object** (`{"nsid":"<n>"}`), which has no (`Objects/<section>/…/<item>`) and stores the item **object** (`{"nsid":"<n>"}`), which has no
value: *Last value*/*Data type* stay empty and the point is never monitored (revised sampling value: *Last value*/*Data type* stay empty and the point is never monitored (revised sampling
interval 0, item status 13). Expanding the item and picking its `Value` node works interval 0, item status 13). Type the node ID of the value instead:
(`{"0":"Value","nsid":"<n>"}`, verified by the user). For quick load type the stable form:
`{"0":"Value","itnm":"<item>"}` (namespace `urn:Yokogawa:CI_SERVER_OPC_UA_SERVER`, type `{"0":"Value","itnm":"<item>"}` (namespace `urn:Yokogawa:CI_SERVER_OPC_UA_SERVER`, type
STRING). The form also fills `OPC_DISPLAY_NAME` and `OPC_TAG_INFO` (browse bookkeeping; STRING). The form also fills `OPC_DISPLAY_NAME` and `OPC_TAG_INFO` (browse bookkeeping;
not needed for quick load). ISS-033. not needed for quick load). ISS-033.

View file

@ -81,9 +81,8 @@ as *dataset* events — `SUBJECT_GROUP` = dataset name (`ITEM_DF`, `ITEM_VAL`, `
(not `QUICKLOAD`), `LOC-ENG-MOD` for the Engineering Module; every `dssqld` run also adds a (not `QUICKLOAD`), `LOC-ENG-MOD` for the Engineering Module; every `dssqld` run also adds a
`CI-SERVER` `LOGIN`/`LOGOUT` pair. `itmval -p` writes are not audited. The item option `CI-SERVER` `LOGIN`/`LOGOUT` pair. `itmval -p` writes are not audited. The item option
`AUDIT_INFO` (*Audit trailing wanted*, default 0; also on `SUB_ITEM_DF`, `EXTERNAL_ALARM_DF`) made `AUDIT_INFO` (*Audit trailing wanted*, default 0; also on `SUB_ITEM_DF`, `EXTERNAL_ALARM_DF`) made
no difference for these tools; it switches the `ITEM.*` events of **operator writes**: a button on no difference for these tools; it is meant for the `ITEM.*` classifiers from operator/PROCESS
display `CIENG_Tank` stored `ITEM.VALUE.MODIFY.OPER-INTERFACE` (old/new, user) with writes (not tested, ISS-049). A changed `STORAGE` flag takes effect only after the notifying process
`AUDIT_INFO` 1 and nothing with 0 (verified, ISS-049). A changed `STORAGE` flag takes effect only after the notifying process
re-reads it (`ECL_REFRESH`, up to 30 minutes, both directions; verified, ISS-050). re-reads it (`ECL_REFRESH`, up to 30 minutes, both directions; verified, ISS-050).
## 4. Setup files (§4.2) ## 4. Setup files (§4.2)

View file

@ -3,7 +3,7 @@ manual: IM 36K10L30-01EN
title: BUS Service Engineering title: BUS Service Engineering
edition: 3rd Edition, Sep. 2023 edition: 3rd Edition, Sep. 2023
version: R1.03 version: R1.03
status: from docs; installed tools, setup files (dur.sup, durm_1_udp.sup, time_table.sup, fmfprt.sup, durutl.sup) and durm_start.cmd checked read-only 2026-10-01; durwfp verified; umhman, umhtestprog, umhmsg verified after a fresh start (ISS-030) status: from docs; installed tools, setup files (dur.sup, durm_1_udp.sup, time_table.sup, fmfprt.sup, durutl.sup) and durm_start.cmd checked read-only 2026-10-01; durwfp verified; umhman, umhtestprog, umhmsg fail on the test system (ISS-030)
--- ---
# BUS Service Engineering (R1.03) # BUS Service Engineering (R1.03)
@ -57,9 +57,9 @@ second node; `durutl.sup` has no active lines.
`-q <printer queue>` prints too. `-q <printer queue>` prints too.
- Tools: `umhtestprog` (tests the message path), `umhmsg <hex code> [<var> <value>]…` - Tools: `umhtestprog` (tests the message path), `umhmsg <hex code> [<var> <value>]…`
(issue a message from a script), `umhman` (look up a hex code, interactive), (issue a message from a script), `umhman` (look up a hex code, interactive),
`umhlogtoo` (copy of all messages to a terminal). **Verified** after a fresh start: `umhman` `umhlogtoo` (copy of all messages to a terminal). **On the test system** `umhman` crashes
with piped input, `umhmsg` (message appears in `umhlog.log`) and `umhtestprog` work; late in an with redirected input, `umhtestprog` crashes, and `umhmsg` ends with "license expired"
unlicensed session they crashed or reported "license expired" (ISS-030). (ISS-030).
- A message shown as `UMH Message Text Error: Message number <hex> (…)` means the text could - A message shown as `UMH Message Text Error: Message number <hex> (…)` means the text could
not be formatted (e.g. a `%` in a PRINT text, ISS-025). not be formatted (e.g. a `%` in a PRINT text, ISS-025).

View file

@ -48,10 +48,7 @@ No setup file, no parameters. On the test system `equipment_start.cmd` starts it
automatically on the host node, and it was running. The manual calls the target a history automatically on the host node, and it was running. The manual calls the target a history
group; it is the dataset **`STATION_STAT`** (fields: time stamp, station, line, time span, group; it is the dataset **`STATION_STAT`** (fields: time stamp, station, line, time span,
sends, good answers, bad return code, timeouts, frame errors, bad CRC, retries, line bad). sends, good answers, bad return code, timeouts, frame errors, bad CRC, retries, line bad).
**Verified:** `dssqld -e st.qlo -d STATION_STAT` lists one record per station line per hour An export returned no records on the test system (ISS-021).
(`NAME` = `<DD-MON-YY hh:00>/<station>/<line>`), e.g. `CIENG_PLC` with `TIMESPAN` (seconds
counted in that hour), `SENDS` and `GOODANS` 1560/1560. Only stations that actually sent requests
appear; the first export (no communicating station) was empty (ISS-021). History type 4.
## 3. Debugger: `eqpdbg` (§3) ## 3. Debugger: `eqpdbg` (§3)