Issue review after phase 12 #14

Merged
cliu merged 14 commits from docs/issue-review into main 2026-10-01 19:01:52 +10:00
5 changed files with 26 additions and 16 deletions
Showing only changes of commit 19b4113b37 - Show all commits

View file

@ -53,7 +53,9 @@ The Engineering Module also resets classes (class properties); not practiced.
accepted with 0 errors but nothing happens. accepted with 0 errors but nothing happens.
- `dssqld -m` on `OBJECT_DF` with `RESET` 1: refused with `OPC-E-OBJ_RSTREQ, The class needs to - `dssqld -m` on `OBJECT_DF` with `RESET` 1: refused with `OPC-E-OBJ_RSTREQ, The class needs to
be reset first`. be reset first`.
- `CLASS_RESET_COMMAND` (system-wide reset used by the Engineering Module) was not tried. - `CLASS_RESET_COMMAND` (system-wide reset, fields `RESET`, `GENERATE_REPORT`, `PROGRESS`,
`OBJECTS_RESET` …): the dataset allows only read and update, `dssqld -e` returns no record,
`dssqld -m` gives *Not found*, `dssqld -i` is refused (`DSS-E-NO_AUTH`). Verified 2026-10-01.
## 3. Changing prompts or signals ## 3. Changing prompts or signals

View file

@ -2,7 +2,7 @@
task: BUS Service utilities - process checks, stopping single processes, message tools, adaptive queues task: BUS Service utilities - process checks, stopping single processes, message tools, adaptive queues
version: R1.03 version: R1.03
source: IM 36K10L30-01EN §1, §5, §6, §10, §14; checked on the test system 2026-10-01 source: IM 36K10L30-01EN §1, §5, §6, §10, §14; checked on the test system 2026-10-01
status: verified for durwfp and the read-only setup file checks; umhman, umhtestprog, umhmsg fail on the test system (ISS-030) status: verified (durwfp, setup file checks, umhman, umhmsg, umhtestprog)
--- ---
# BUS Service utilities # BUS Service utilities
@ -28,10 +28,15 @@ then kills after 10 s. `*` wildcards stop many processes (`-p alm\*`). Never `du
- Message log: `%TLS_LOG_PATH%\umhlog.log` (`--> From: <PROCESS> (<node>) on <time>`, then - Message log: `%TLS_LOG_PATH%\umhlog.log` (`--> From: <PROCESS> (<node>) on <time>`, then
`FAC-S-CODE, text` lines). `UMH Message Text Error: Message number <hex> (…)` = the text `FAC-S-CODE, text` lines). `UMH Message Text Error: Message number <hex> (…)` = the text
could not be formatted (e.g. `%` in a PRINT text, ISS-025). could not be formatted (e.g. `%` in a PRINT text, ISS-025).
- `umhman` (hex code → text), `umhtestprog` (test the log path) and `umhmsg <hex> [<var> - `umhman` (hex code → text): answers can be piped, e.g. `printf '8010008
<value>]` (log a message from a script) **did not work on the test system**: `umhman`
crashes with redirected input (run it interactively), `umhtestprog` crashes, `umhmsg` stops ' | umhman` →
with `license expired` on the unlicensed node (ISS-030). `DUR-W-NO_MSG_FND, No selected message found`; parameters in the text stay empty.
- `umhmsg <hex> [<var> <value>]…` logs that message from a script: it prints nothing; the
message appears in `umhlog.log` from process `UMHMSG_<pid>`.
- `umhtestprog` runs its self-test (`TESTING UMH MESSAGES`, `TESTING ILLEGAL CODES`).
- On an **unlicensed** node these tools crash or stop with `license expired` once the licence
time is nearly used up, while `dssqld`/`itmval` still work; restart CI Server (ISS-030).
## Adaptive queues (read-only check) ## Adaptive queues (read-only check)

View file

@ -25,7 +25,7 @@ development system (see "Test system" in `progress.md`); they do not exist on ot
| ISS-004 | 2026-09-30 | ITEM (`itmval`) | `itmval -g -a <1..5>` returns `ITM-E-WRONG_ATT` on `AID.WRPS.*` items, so reading limits is unproven. | closed | Closed 2026-09-30 (confirmed by user). On `CI-Eng-Sample.TANK1.LEVEL` (limits set) `-a 1..5` returned deadband 0, low 20, high 80, low-low 10, high-high 90. The error only occurs on items without limits. | `.claude/skills/system-management/tasks/read-write-item.md` (limits section); `knowledge/progress.md` row "Read an item with `itmval -g`" | | ISS-004 | 2026-09-30 | ITEM (`itmval`) | `itmval -g -a <1..5>` returns `ITM-E-WRONG_ATT` on `AID.WRPS.*` items, so reading limits is unproven. | closed | Closed 2026-09-30 (confirmed by user). On `CI-Eng-Sample.TANK1.LEVEL` (limits set) `-a 1..5` returned deadband 0, low 20, high 80, low-low 10, high-high 90. The error only occurs on items without limits. | `.claude/skills/system-management/tasks/read-write-item.md` (limits section); `knowledge/progress.md` row "Read an item with `itmval -g`" |
| ISS-005 | 2026-09-30 | DATABASE (`dssqld`) | Loading `04_item_his_df.qli` straight after creating the storage group gave 2 errors once; three other runs were clean. Error text not captured. | open | Added a 5 s pause in `load.cmd`. If it happens again, capture `04_item_his_df.qlo`. | `examples/CI-Eng-Sample/load.cmd`; `.claude/skills/system-management/tasks/load-remove-records.md` | | ISS-005 | 2026-09-30 | DATABASE (`dssqld`) | Loading `04_item_his_df.qli` straight after creating the storage group gave 2 errors once; three other runs were clean. Error text not captured. | open | Added a 5 s pause in `load.cmd`. If it happens again, capture `04_item_his_df.qlo`. | `examples/CI-Eng-Sample/load.cmd`; `.claude/skills/system-management/tasks/load-remove-records.md` |
| ISS-006 | 2026-09-30 | HISTORY (`ithloahis`) | Samples dated before the start of the current storage unit were not stored (no error shown); samples after it were. Also, a new storage group stored nothing until CI Server was restarted. | closed | Closed 2026-10-01 (confirmed by user). Confirm with History Management (IM 36K10L20) in phase 9: how to load into older units, and whether a restart is really required. 2026-09-30 (phase 5): IM 36K10L35 §1.3/§5 explains the first part: event storage picks the unit by time stamp, never older than 60 units, and within the storage process's `gap_time` (ITHEEX/ITHEIX 2880 min) and, for EVENT/ITEM, `max_sample_delay` (ITHEIX 14400 min); older data needs earlier unit files (`hisdbg`, `hisrecover`, `isfrename`), `ithrecover <group> -p` and a restart. Practice in phase 9. 2026-10-01 (phase 9, verified): (1) restart **is** required — `CIENG_SCAN10S` / `CIENG_AGG` loaded at 11:54 and `CIENG_EVENT` reloaded at 11:32 stored nothing until the 12:00 restart, then stored at once. (2) The first unit of a new Event/Item or Aggregation group is dated 2 days back (= `gap_time` 2880 min), but samples loaded into that pre-restart unit (11:50, 30-Sep) were still dropped; samples inside the active unit (12:02) and inside a unit closed by a forced rollover (12:03 into unit 3,1) were stored. So: samples older than the first unit opened since the restart are dropped silently. Loading older data would need `hisrecover` / `isfrename` / `ithrecover` (not practiced). Proposed close: documented in `load-history.md` and skill `history-management`. | `.claude/skills/system-management/tasks/load-history.md`; `examples/CI-Eng-Sample/README.md`; `knowledge/manuals/IM36K10J10-01EN.md` command-line tools | | ISS-006 | 2026-09-30 | HISTORY (`ithloahis`) | Samples dated before the start of the current storage unit were not stored (no error shown); samples after it were. Also, a new storage group stored nothing until CI Server was restarted. | closed | Closed 2026-10-01 (confirmed by user). Confirm with History Management (IM 36K10L20) in phase 9: how to load into older units, and whether a restart is really required. 2026-09-30 (phase 5): IM 36K10L35 §1.3/§5 explains the first part: event storage picks the unit by time stamp, never older than 60 units, and within the storage process's `gap_time` (ITHEEX/ITHEIX 2880 min) and, for EVENT/ITEM, `max_sample_delay` (ITHEIX 14400 min); older data needs earlier unit files (`hisdbg`, `hisrecover`, `isfrename`), `ithrecover <group> -p` and a restart. Practice in phase 9. 2026-10-01 (phase 9, verified): (1) restart **is** required — `CIENG_SCAN10S` / `CIENG_AGG` loaded at 11:54 and `CIENG_EVENT` reloaded at 11:32 stored nothing until the 12:00 restart, then stored at once. (2) The first unit of a new Event/Item or Aggregation group is dated 2 days back (= `gap_time` 2880 min), but samples loaded into that pre-restart unit (11:50, 30-Sep) were still dropped; samples inside the active unit (12:02) and inside a unit closed by a forced rollover (12:03 into unit 3,1) were stored. So: samples older than the first unit opened since the restart are dropped silently. Loading older data would need `hisrecover` / `isfrename` / `ithrecover` (not practiced). Proposed close: documented in `load-history.md` and skill `history-management`. | `.claude/skills/system-management/tasks/load-history.md`; `examples/CI-Eng-Sample/README.md`; `knowledge/manuals/IM36K10J10-01EN.md` command-line tools |
| ISS-007 | 2026-09-30 | INTEGRATION (monitoring) | `intdskmon` wrote 61.9 for a C: drive that is 61.9 % used / 38.1 % free, although the manual says it monitors the disk free space rate. `intspawn` did nothing when the command path was ~130 characters; a short path worked (limit unknown). | open | Confirm the disk value meaning and the path limit. | `.claude/skills/system-management/tasks/monitoring-processes.md`; `knowledge/manuals/IM36K10J10-01EN.md` §4.1.6; `examples/CI-Eng-Sample/monitoring/` | | ISS-007 | 2026-09-30 | INTEGRATION (monitoring) | `intdskmon` wrote 61.9 for a C: drive that is 61.9 % used / 38.1 % free, although the manual says it monitors the disk free space rate. `intspawn` did nothing when the command path was ~130 characters; a short path worked (limit unknown). | open | Disk value: the test showed **used** % (61.9 on a 61.9 % used disk), and the task file says so; installed behaviour is the reference. `intspawn` path limit: not measured (needs admin edits of `tls\sup\<name>.sup` and restarts for each length); guidance kept: put the command in a `.cmd` with a short path (other CI Server tools cut paths at 79 characters, ISS-020). Ready to close. | `.claude/skills/system-management/tasks/monitoring-processes.md`; `knowledge/manuals/IM36K10J10-01EN.md` §4.1.6; `examples/CI-Eng-Sample/monitoring/` |
| ISS-008 | 2026-09-30 | ACCESS (ODBC server `odbsrv`) | `ci_start.log` on the test system shows `CppServerAPI::Run() failed: InitializeSslCtx(): SSL_CTX_use_certificate_chain_file() failed.` right after ACCESS Service starts. Which component and certificate is not known. | closed | Closed 2026-10-01 (confirmed by user): cause known, ODBC server left as is (not licensed/used on the test system). Identify in phase 7. 2026-10-01 (phase 7): cause found. The message comes from the ODBC server `odbsrv` (ACCESS Service, Simba): `odbsrv.sup` has `USESSL = YES` and `access_start.cmd` points it at `%TLS_ROOT_PATH%\tls\pki\odbsrv\SampleServerCertificate.pem` / `SampleServerKey.pem`, but that folder does not exist and no sample certificate is installed. `odbsrv` exits right after start (`DUR-W-REM_PROC, Process ODBSRV exited unexpectedly`), port 1583 does not listen. Fix (admin, only if ODBC is licensed and wanted): install a certificate + key there, or set `USESSL = NO`. Not applied. Close when the user confirms. | `.claude/skills/installation-security/tasks/setup-check.md`; `knowledge/manuals/IM36K10L45-01EN.md` §1 (done); `.claude/skills/data-access/tasks/access-checks.md` (done) | | ISS-008 | 2026-09-30 | ACCESS (ODBC server `odbsrv`) | `ci_start.log` on the test system shows `CppServerAPI::Run() failed: InitializeSslCtx(): SSL_CTX_use_certificate_chain_file() failed.` right after ACCESS Service starts. Which component and certificate is not known. | closed | Closed 2026-10-01 (confirmed by user): cause known, ODBC server left as is (not licensed/used on the test system). Identify in phase 7. 2026-10-01 (phase 7): cause found. The message comes from the ODBC server `odbsrv` (ACCESS Service, Simba): `odbsrv.sup` has `USESSL = YES` and `access_start.cmd` points it at `%TLS_ROOT_PATH%\tls\pki\odbsrv\SampleServerCertificate.pem` / `SampleServerKey.pem`, but that folder does not exist and no sample certificate is installed. `odbsrv` exits right after start (`DUR-W-REM_PROC, Process ODBSRV exited unexpectedly`), port 1583 does not listen. Fix (admin, only if ODBC is licensed and wanted): install a certificate + key there, or set `USESSL = NO`. Not applied. Close when the user confirms. | `.claude/skills/installation-security/tasks/setup-check.md`; `knowledge/manuals/IM36K10L45-01EN.md` §1 (done); `.claude/skills/data-access/tasks/access-checks.md` (done) |
| ISS-009 | 2026-09-30 | Security Guide | DCOM port range printed as 20500–20550 in the firewall table but "2500–20550" in the OPC configuration table. Taken as a typo for 20500–20550. | closed | Confirm on a system with IT security applied. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K01C30-01EN.md` §4 | | ISS-009 | 2026-09-30 | Security Guide | DCOM port range printed as 20500–20550 in the firewall table but "2500–20550" in the OPC configuration table. Taken as a typo for 20500–20550. | closed | Confirm on a system with IT security applied. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K01C30-01EN.md` §4 |
@ -40,16 +40,16 @@ development system (see "Test system" in `progress.md`); they do not exist on ot
| ISS-018 | 2026-09-30 | Authorization (`dssana.sup`) | IM 36K10C10 §2.2 says the *No* login method applies the user profile `FT_NO_LOGIN`; the installed `dssana.sup` names `CI_NO_LOGIN` (and `CI_NO_LOGIN_OPCUAS` for anonymous OPC UA) as the no-login profile. `USER_DF` on the test system has `CI_NO_LOGIN_OPCUAS` but no `CI_NO_LOGIN`. | open | Installed software is the reference: use `CI_NO_LOGIN`. Still to check: behaviour of a *No* login when that user does not exist (manual: no profile applied). Covered again in phase 13 (IM 36K10J40). | `knowledge/manuals/IM36K10C10-01EN.md` §2 | | ISS-018 | 2026-09-30 | Authorization (`dssana.sup`) | IM 36K10C10 §2.2 says the *No* login method applies the user profile `FT_NO_LOGIN`; the installed `dssana.sup` names `CI_NO_LOGIN` (and `CI_NO_LOGIN_OPCUAS` for anonymous OPC UA) as the no-login profile. `USER_DF` on the test system has `CI_NO_LOGIN_OPCUAS` but no `CI_NO_LOGIN`. | open | Installed software is the reference: use `CI_NO_LOGIN`. Still to check: behaviour of a *No* login when that user does not exist (manual: no profile applied). Covered again in phase 13 (IM 36K10J40). | `knowledge/manuals/IM36K10C10-01EN.md` §2 |
| ISS-019 | 2026-09-30 | ITEM (string items) | Maximum string item length differs by source: IM 36K10C10 §3.3.4 says default 80, max 100; the Tutorial summary says up to 168 without audit; the data dictionary (`dssqld -f`) gives `ITEM_DF.STRING_LENGTH` range 1–200, default 80. | closed | Tested 2026-09-30 on CI-Eng-Sample (`dssqld -i`, `itmval -p/-g`, non-elevated): `STRING_LENGTH` 100, 168 and 200 load with or without `AUDIT_INFO`; 201 fails with `DSS-E-VAL_RANGE`. An item holds **length − 1** characters: a 99-character value in a length-100 item is stored with status 9 NORMAL; longer values are cut to length − 1 with status **12 OVERRANGED** (100 → 99, 200 → 199, 201 → 199). So the data dictionary (1–200) is right. Test items removed. Closed 2026-09-30 (confirmed by user). | `knowledge/manuals/IM36K10C10-01EN.md` §3; `knowledge/manuals/IM36K10G10-01EN.md` (items); `.claude/skills/item-engineering/SKILL.md` | | ISS-019 | 2026-09-30 | ITEM (string items) | Maximum string item length differs by source: IM 36K10C10 §3.3.4 says default 80, max 100; the Tutorial summary says up to 168 without audit; the data dictionary (`dssqld -f`) gives `ITEM_DF.STRING_LENGTH` range 1–200, default 80. | closed | Tested 2026-09-30 on CI-Eng-Sample (`dssqld -i`, `itmval -p/-g`, non-elevated): `STRING_LENGTH` 100, 168 and 200 load with or without `AUDIT_INFO`; 201 fails with `DSS-E-VAL_RANGE`. An item holds **length − 1** characters: a 99-character value in a length-100 item is stored with status 9 NORMAL; longer values are cut to length − 1 with status **12 OVERRANGED** (100 → 99, 200 → 199, 201 → 199). So the data dictionary (1–200) is right. Test items removed. Closed 2026-09-30 (confirmed by user). | `knowledge/manuals/IM36K10C10-01EN.md` §3; `knowledge/manuals/IM36K10G10-01EN.md` (items); `.claude/skills/item-engineering/SKILL.md` |
| ISS-020 | 2026-09-30 | DATABASE (`dssqld`) | `dssqld -i "<long absolute path>\user.qli"` failed with `CRL-E-ENOENT` / `DSSQ-E-QLD_FILOPN`: the path in the message was cut after 79 characters (`…\73b3559a-12.`). A relative file name from the same folder works. Similar to the `intspawn` path limit (ISS-007). | closed | Tested 2026-10-01: the limit is **79 characters** for the whole path. An input file of 80–81 characters gives `DSSQ-E-Q_QLIEXT` (the name is cut, e.g. `….ql`), 85+ gives `CRL-E-ENOENT`. An `-e` output path of 80+ characters gives **no error**, but no file appears under the given name. Documented: keep paths ≤ 79 characters, or `cd` to the folder and use relative names. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/system-management/tasks/load-remove-records.md`; `.claude/skills/system-management/tasks/export-dataset.md` | | ISS-020 | 2026-09-30 | DATABASE (`dssqld`) | `dssqld -i "<long absolute path>\user.qli"` failed with `CRL-E-ENOENT` / `DSSQ-E-QLD_FILOPN`: the path in the message was cut after 79 characters (`…\73b3559a-12.`). A relative file name from the same folder works. Similar to the `intspawn` path limit (ISS-007). | closed | Tested 2026-10-01: the limit is **79 characters** for the whole path. An input file of 80–81 characters gives `DSSQ-E-Q_QLIEXT` (the name is cut, e.g. `….ql`), 85+ gives `CRL-E-ENOENT`. An `-e` output path of 80+ characters gives **no error**, but no file appears under the given name. Documented: keep paths ≤ 79 characters, or `cd` to the folder and use relative names. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/system-management/tasks/load-remove-records.md`; `.claude/skills/system-management/tasks/export-dataset.md` |
| ISS-021 | 2026-09-30 | EQUIPMENT (`eqpiostat`) | IM 36K10L40 §2 says `eqpiostat` stores hourly I/O statistics per station line in "history group STATION_STAT". On the test system `eqpiostat` runs (started by `equipment_start.cmd` on the host node) and `STATION_STAT` is a dataset, but `dssqld -e` returned 0 records, also with filters on `TIME_STAMP` and `STATION` (AID Modbus stations, which send requests). | open | Check whether records appear after a full hour with a communicating station, or whether the dataset is read another way (e.g. Engineering Module, report). | `knowledge/manuals/IM36K10L40-01EN.md` §2 | | ISS-021 | 2026-09-30 | EQUIPMENT (`eqpiostat`) | IM 36K10L40 §2 says `eqpiostat` stores hourly I/O statistics per station line in "history group STATION_STAT". On the test system `eqpiostat` runs (started by `equipment_start.cmd` on the host node) and `STATION_STAT` is a dataset, but `dssqld -e` returned 0 records, also with filters on `TIME_STAMP` and `STATION` (AID Modbus stations, which send requests). | open | Answered 2026-10-01: with `CIENG_PLC` communicating (Modbus slave mirror running), `STATION_STAT` holds one record per hour per station line (10 records since 30-09-2026 18:00; e.g. `TIMESPAN` 831 s, `SENDS`/`GOODANS` 1560/1560, no errors). The earlier empty export had no communicating station. Ready to close. | `knowledge/manuals/IM36K10L40-01EN.md` §2 |
| ISS-022 | 2026-09-30 | ITEM (`itmval -f`) | `itmval -f <file> vs -n CI-Eng-Sample.TANK1.LEVEL` (IM 36K10L36 §1.4, write a restore command) crashes with a segmentation fault (bash) / access violation 0xC0000005 (PowerShell) and writes no file; also with `-l`. The manual's space-separated form `-n <inst> <unit> <tag>` is rejected with `FSL-E-NARG_ALL`. `itmval -g`/`-p` work. | open | Workaround: build restore lines from `itmval -g` output. Report to Yokogawa support if needed. Retested 2026-10-01 with the documented syntax `itmval -f <file> <opts> -n <item>` (`<opts>` = letters from `vsqo`, e.g. `vs`): still a segmentation fault from bash and from `cmd`, in a short and a long folder, relative or absolute file name; `cmd` leaves an **empty** file. Treat `-f` as broken on R1.03.00. | `knowledge/manuals/IM36K10L36-01EN.md` §3; `.claude/skills/system-management/tasks/read-write-item.md` | | ISS-022 | 2026-09-30 | ITEM (`itmval -f`) | `itmval -f <file> vs -n CI-Eng-Sample.TANK1.LEVEL` (IM 36K10L36 §1.4, write a restore command) crashes with a segmentation fault (bash) / access violation 0xC0000005 (PowerShell) and writes no file; also with `-l`. The manual's space-separated form `-n <inst> <unit> <tag>` is rejected with `FSL-E-NARG_ALL`. `itmval -g`/`-p` work. | open | Workaround: build restore lines from `itmval -g` output. Report to Yokogawa support if needed. Retested 2026-10-01 with the documented syntax `itmval -f <file> <opts> -n <item>` (`<opts>` = letters from `vsqo`, e.g. `vs`): still a segmentation fault from bash and from `cmd`, in a short and a long folder, relative or absolute file name; `cmd` leaves an **empty** file. Also crashes right after a CI Server restart (so not the licence-time effect of ISS-030). Treat `-f` as broken on R1.03.00; report to Yokogawa support if needed. | `knowledge/manuals/IM36K10L36-01EN.md` §3; `.claude/skills/system-management/tasks/read-write-item.md` |
| ISS-023 | 2026-09-30 | ITEM / ITH (manual vs install) | Installed ITEM Service differs from IM 36K10L35/L36: `item_start.cmd` starts `itheix` (EVENT/ITEM storage, not described), aggregation `ithsag`/`ithrag`, two instances of each retrieve process, and `itmtim 100 1000 1 200 1` (five arguments, three documented); `itm.sup` item pool is 650000 KB (manual default 50000) and has `not_regained` (not described); `itheix.sup` has `max_sample_delay`, `max_samples_queued`, `max_open_files`. | closed | Closed 2026-09-30 (user decision: the installed software is the reference). Summaries describe the installed values. | `knowledge/manuals/IM36K10L35-01EN.md`; `knowledge/manuals/IM36K10L36-01EN.md` | | ISS-023 | 2026-09-30 | ITEM / ITH (manual vs install) | Installed ITEM Service differs from IM 36K10L35/L36: `item_start.cmd` starts `itheix` (EVENT/ITEM storage, not described), aggregation `ithsag`/`ithrag`, two instances of each retrieve process, and `itmtim 100 1000 1 200 1` (five arguments, three documented); `itm.sup` item pool is 650000 KB (manual default 50000) and has `not_regained` (not described); `itheix.sup` has `max_sample_delay`, `max_samples_queued`, `max_open_files`. | closed | Closed 2026-09-30 (user decision: the installed software is the reference). Summaries describe the installed values. | `knowledge/manuals/IM36K10L35-01EN.md`; `knowledge/manuals/IM36K10L36-01EN.md` |
| ISS-024 | 2026-09-30 | EQUIPMENT (Modbus slave) | IM 36K10L41 §3.7 says `EQPMDCSLVTCP` waits for "MODBUS RTU requests via TCP/IP" and the CI Server master should use "MODBUS RTU via TCP/IP". A Modbus master station with `PROTOCOL = RTU` to `eqpmdcslvtcp` (port 5020) got no answer (`EQP-E-TCPRCVTMO`, 4 requests, 0 valid); with `Open Modbus/TCP` it worked at once. | closed | Closed 2026-09-30 (user decision: installed software is the reference). Use `Open Modbus/TCP` towards `eqpmdcslvtcp`. | `knowledge/manuals/IM36K10L41-01EN.md` §3.7; `.claude/skills/equipment/tasks/modbus-station.md` | | ISS-024 | 2026-09-30 | EQUIPMENT (Modbus slave) | IM 36K10L41 §3.7 says `EQPMDCSLVTCP` waits for "MODBUS RTU requests via TCP/IP" and the CI Server master should use "MODBUS RTU via TCP/IP". A Modbus master station with `PROTOCOL = RTU` to `eqpmdcslvtcp` (port 5020) got no answer (`EQP-E-TCPRCVTMO`, 4 requests, 0 valid); with `Open Modbus/TCP` it worked at once. | closed | Closed 2026-09-30 (user decision: installed software is the reference). Use `Open Modbus/TCP` towards `eqpmdcslvtcp`. | `knowledge/manuals/IM36K10L41-01EN.md` §3.7; `.claude/skills/equipment/tasks/modbus-station.md` |
| ISS-025 | 2026-09-30 | PROCESS (PRINT) | A Traditional `PRINT "… 80 %, volume ", VOLUME;` logged `OPC-I-INFO, UMH Message Text Error: Message number 083A001B (… level reached 80 )`: the text is cut at the `%` and the rest is lost. Without `%` the full text is logged. | closed | Tested 2026-10-01 with a temporary class (removed): `PRINT "… 50 %% …"` logs `50 % …` correctly; `\%` and `%c` with 37 both give the *Message Text Error* and cut the text. Documented: write `%%`. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10P10-01EN.md` §4; `.claude/skills/class-object-engineering/tasks/traditional-class.md` | | ISS-025 | 2026-09-30 | PROCESS (PRINT) | A Traditional `PRINT "… 80 %, volume ", VOLUME;` logged `OPC-I-INFO, UMH Message Text Error: Message number 083A001B (… level reached 80 )`: the text is cut at the `%` and the rest is lost. Without `%` the full text is logged. | closed | Tested 2026-10-01 with a temporary class (removed): `PRINT "… 50 %% …"` logs `50 % …` correctly; `\%` and `%c` with 37 both give the *Message Text Error* and cut the text. Documented: write `%%`. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10P10-01EN.md` §4; `.claude/skills/class-object-engineering/tasks/traditional-class.md` |
| ISS-026 | 2026-09-30 | PROCESS (`opc.sup`) | Installed PROCESS setup differs from IM 36K10L10 §2: `IMMED-EVENTS = NO` (manual: default on); `FLOW-CONTROL = 30,60` (manual 300/360 s); four executors `OPCEXE1`–`4` with fixed priority ranges (manual examples `OPCEXE01`…) and `opcdbg` still defaults to `OPCEXE`; keyword `VARTAB-SIZE` (manual `VARITAB-SIZE`); hidden keywords `FLDSEP`, `IGNEXI` not described; `ALARM-ITEMS` not set; class source file `opc_clssrc.dat` (manual `opc_clasrc.dat`); `opcini.sup` (licence line) not described. | closed | Installed software is the reference (standing user decision); summary written from the installed files. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10L10-01EN.md` §2, §5 | | ISS-026 | 2026-09-30 | PROCESS (`opc.sup`) | Installed PROCESS setup differs from IM 36K10L10 §2: `IMMED-EVENTS = NO` (manual: default on); `FLOW-CONTROL = 30,60` (manual 300/360 s); four executors `OPCEXE1`–`4` with fixed priority ranges (manual examples `OPCEXE01`…) and `opcdbg` still defaults to `OPCEXE`; keyword `VARTAB-SIZE` (manual `VARITAB-SIZE`); hidden keywords `FLDSEP`, `IGNEXI` not described; `ALARM-ITEMS` not set; class source file `opc_clssrc.dat` (manual `opc_clasrc.dat`); `opcini.sup` (licence line) not described. | closed | Installed software is the reference (standing user decision); summary written from the installed files. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10L10-01EN.md` §2, §5 |
| ISS-027 | 2026-09-30 | PROCESS (`opcdbg`) | IM 36K10L10 §4 says the `opcdbg` *Dump classes/objects* files can be read by `dssqld`. The files have no `@LANGUAGE`/`@FIELDS`/`@<dataset>` headers (`NAME,"desc",prio` + source lines prefixed `- `); `dssqld -i` on the object dump gave `DSS-E-UNK_DS_NM, Unknown data set name`. | open | Use `dssqld -e CLASS_DF` / `OBJECT_DF` for transfers. Maybe an old tool reads the dump format; not found. | `knowledge/manuals/IM36K10L10-01EN.md` §4; `.claude/skills/class-object-engineering/tasks/opcdbg-checks.md` | | ISS-027 | 2026-09-30 | PROCESS (`opcdbg`) | IM 36K10L10 §4 says the `opcdbg` *Dump classes/objects* files can be read by `dssqld`. The files have no `@LANGUAGE`/`@FIELDS`/`@<dataset>` headers (`NAME,"desc",prio` + source lines prefixed `- `); `dssqld -i` on the object dump gave `DSS-E-UNK_DS_NM, Unknown data set name`. | open | Use `dssqld -e CLASS_DF` / `OBJECT_DF` for transfers. Maybe an old tool reads the dump format; not found. | `knowledge/manuals/IM36K10L10-01EN.md` §4; `.claude/skills/class-object-engineering/tasks/opcdbg-checks.md` |
| ISS-028 | 2026-09-30 | PROCESS (class reset) | After recompiling a class with objects (`RESET_REQUIRED` 1), `dssqld -m` with `CLASS_DF` `RESET` = 1 (also with `RESET_NODE` = host node name) is accepted with 0 errors but does not reset; `OBJECT_DF` `RESET` = 1 is refused (`OPC-E-OBJ_RSTREQ`). `opcdbg` Classes → 8 *Reset class* works; it asks for a reset report file, which the manual does not list. | open | Use `opcdbg`. Still to try: `CLASS_RESET_COMMAND` (system-wide) and the Engineering Module's reset. | `.claude/skills/class-object-engineering/tasks/change-reset-class.md`; `knowledge/manuals/IM36K10L10-01EN.md` §4 | | ISS-028 | 2026-09-30 | PROCESS (class reset) | After recompiling a class with objects (`RESET_REQUIRED` 1), `dssqld -m` with `CLASS_DF` `RESET` = 1 (also with `RESET_NODE` = host node name) is accepted with 0 errors but does not reset; `OBJECT_DF` `RESET` = 1 is refused (`OPC-E-OBJ_RSTREQ`). `opcdbg` Classes → 8 *Reset class* works; it asks for a reset report file, which the manual does not list. | open | Use `opcdbg`. 2026-10-01: `CLASS_RESET_COMMAND` cannot be driven by `dssqld` (read/update only; no record to update — *Not found*; insert `DSS-E-NO_AUTH`). Test class `CIENG_INCR` was recompiled and reset again with `opcdbg` (`RESET_REQUIRED` back to 0). Still to try: the Engineering Module's reset (user). | `.claude/skills/class-object-engineering/tasks/change-reset-class.md`; `knowledge/manuals/IM36K10L10-01EN.md` §4 |
| ISS-029 | 2026-09-30 | PROCESS (Java) | IM 36K10P11 §10.4 says a new Java class must be reset before objects are added, otherwise the code does not take effect. A Java class inserted with `COMPILE` 1 by `dssqld` ran its first object correctly without any reset (twice, including a full sample reload). | open | Installed behaviour is the reference; keep "reset after changing a class that has objects". Check whether the Engineering Module path (compile without quick load) behaves differently. | `knowledge/manuals/IM36K10P11-01EN.md` §7; `.claude/skills/class-object-engineering/tasks/java-class.md` | | ISS-029 | 2026-09-30 | PROCESS (Java) | IM 36K10P11 §10.4 says a new Java class must be reset before objects are added, otherwise the code does not take effect. A Java class inserted with `COMPILE` 1 by `dssqld` ran its first object correctly without any reset (twice, including a full sample reload). | open | Installed behaviour is the reference; keep "reset after changing a class that has objects". Check whether the Engineering Module path (compile without quick load) behaves differently. | `knowledge/manuals/IM36K10P11-01EN.md` §7; `.claude/skills/class-object-engineering/tasks/java-class.md` |
| ISS-030 | 2026-10-01 | BUS (UMH tools) | `umhman` (hex code → text) crashes with redirected input (bash: segmentation fault 139 with CRLF input; PowerShell `Start-Process -RedirectStandardInput`: 0xC0000005); with an argument it only prompts. `umhtestprog` prints `UMH TEST UTILITY` and crashes (segmentation fault). `umhmsg 8010008` stops with `umh_panic: …umhmsg.exe, license expired` although other tools (`dssqld`, `itmval`) still worked at that time. | open | Try `umhman` interactively in a console; check `umhmsg` on a licensed system. Similar to ISS-022 (`itmval -f`). | `.claude/skills/system-management/tasks/bus-utilities.md`; `knowledge/manuals/IM36K10L30-01EN.md` §3 | | ISS-030 | 2026-10-01 | BUS (UMH tools) | `umhman` (hex code → text) crashes with redirected input (bash: segmentation fault 139 with CRLF input; PowerShell `Start-Process -RedirectStandardInput`: 0xC0000005); with an argument it only prompts. `umhtestprog` prints `UMH TEST UTILITY` and crashes (segmentation fault). `umhmsg 8010008` stops with `umh_panic: …umhmsg.exe, license expired` although other tools (`dssqld`, `itmval`) still worked at that time. | open | Retested 2026-10-01 right after a CI Server restart: all three work — `umhman` with piped input (bash, LF or CRLF; via `cmd <` too), `umhmsg 083A001B text "…"` writes the message to `umhlog.log` (process `UMHMSG_<pid>`, prints nothing), `umhtestprog` runs its self-test. The earlier failures came late in an unlicensed session (licence nearly expired). `itmval -f` (ISS-022) still crashes on a fresh start, so it is a separate fault. Ready to close. | `.claude/skills/system-management/tasks/bus-utilities.md`; `knowledge/manuals/IM36K10L30-01EN.md` §3 |
| ISS-031 | 2026-10-01 | LICENCE (unlicensed node) | The unlicensed test node counts down about 1 hour of run time per CI Server start (`License time left` in `smd_<node>_LOW_smdsnp_general.log`, 3600 s → `*** license problem : 3 ***`); then `dssqld`/`itmval` stop with `license expired` and `ISF-F-LIC_PROB, DATABASE Service is not licensed`. A PC sleep pauses the count (start 17:25, ran out 09:52 next day). Restart of the CI Service resets it (verified 2026-10-01, back after ~45 s). | closed | Closed 2026-10-01 (confirmed by user): known limitation of the unlicensed test system, documented in system-check. Known limitation of the test system, documented in `system-check`. Plan tests in ≤ 1 h blocks. Close when the user confirms. | `.claude/skills/system-check/SKILL.md` §3 (done) | | ISS-031 | 2026-10-01 | LICENCE (unlicensed node) | The unlicensed test node counts down about 1 hour of run time per CI Server start (`License time left` in `smd_<node>_LOW_smdsnp_general.log`, 3600 s → `*** license problem : 3 ***`); then `dssqld`/`itmval` stop with `license expired` and `ISF-F-LIC_PROB, DATABASE Service is not licensed`. A PC sleep pauses the count (start 17:25, ran out 09:52 next day). Restart of the CI Service resets it (verified 2026-10-01, back after ~45 s). | closed | Closed 2026-10-01 (confirmed by user): known limitation of the unlicensed test system, documented in system-check. Known limitation of the test system, documented in `system-check`. Plan tests in ≤ 1 h blocks. Close when the user confirms. | `.claude/skills/system-check/SKILL.md` §3 (done) |
| ISS-032 | 2026-10-01 | ACCESS (OPC UA server node IDs) | IM 36K10L45 §10.3 shows CI Server node IDs (`{"nsid":"32"}`, `{"0":"Value","itnm":"ITEM1"}`) and the CI Server namespace `http://www.yokogawa.com/CI_Server/` (ns 3) but not which namespace the **entities** use. With that URI (or `urn:<host>:Yokogawa:CI_SERVER_OPC_UA_SERVER`) the client point was silently not monitored. Browsing (`OPCUAC_TAG_DF`) shows sections/items in **`urn:Yokogawa:CI_SERVER_OPC_UA_SERVER`**; with it `{"0":"Value","itnm":"<item>"}` and `{"0":"Value","nsid":"<n>"}` both work. IM 36K10E20 §2.2.6 also asks to enable `OPXUAS_USE_NAME_NODEIDS` and restart for CI client ↔ CI server; not needed on the test system. | closed | Closed 2026-10-01 (user decision: installed software is the reference). Installed software is the reference (standing user decision). Close when the user confirms. | `knowledge/manuals/IM36K10L45-01EN.md` §7 (done); `knowledge/manuals/IM36K10E20-01EN.md` §3 (done); `.claude/skills/data-access/tasks/opcua-client.md` (done) | | ISS-032 | 2026-10-01 | ACCESS (OPC UA server node IDs) | IM 36K10L45 §10.3 shows CI Server node IDs (`{"nsid":"32"}`, `{"0":"Value","itnm":"ITEM1"}`) and the CI Server namespace `http://www.yokogawa.com/CI_Server/` (ns 3) but not which namespace the **entities** use. With that URI (or `urn:<host>:Yokogawa:CI_SERVER_OPC_UA_SERVER`) the client point was silently not monitored. Browsing (`OPCUAC_TAG_DF`) shows sections/items in **`urn:Yokogawa:CI_SERVER_OPC_UA_SERVER`**; with it `{"0":"Value","itnm":"<item>"}` and `{"0":"Value","nsid":"<n>"}` both work. IM 36K10E20 §2.2.6 also asks to enable `OPXUAS_USE_NAME_NODEIDS` and restart for CI client ↔ CI server; not needed on the test system. | closed | Closed 2026-10-01 (user decision: installed software is the reference). Installed software is the reference (standing user decision). Close when the user confirms. | `knowledge/manuals/IM36K10L45-01EN.md` §7 (done); `knowledge/manuals/IM36K10E20-01EN.md` §3 (done); `.claude/skills/data-access/tasks/opcua-client.md` (done) |
| ISS-033 | 2026-10-01 | ACCESS (Engineering Module OPC UA point) | Tested by the user: the point form's *Browse path* stops at the item (`Objects/CI-Eng-Sample/TANK1/INFLOW`) and stores the item **object** `{"nsid":"548"}`; the point is not monitored (revised sampling interval 0, connected item status 13, *Last value*/*Data type* empty). Typing `{"0":"Value","itnm":"CI-Eng-Sample.TANK1.INFLOW"}` in *Node Id* fixed it (values followed at once). Browsing into an item that is OPC visible but not *Read* fails (`UncertainNotAllNodesAvailable`, `OPXC-E-BRW_NODE`). | open | Check whether the browse dialog can expand an item to `Value` (e.g. double-click); otherwise type the node ID. | `knowledge/manuals/IM36K10E20-01EN.md` §2 (done); `.claude/skills/data-access/tasks/opcua-client.md` §3 (done) | | ISS-033 | 2026-10-01 | ACCESS (Engineering Module OPC UA point) | Tested by the user: the point form's *Browse path* stops at the item (`Objects/CI-Eng-Sample/TANK1/INFLOW`) and stores the item **object** `{"nsid":"548"}`; the point is not monitored (revised sampling interval 0, connected item status 13, *Last value*/*Data type* empty). Typing `{"0":"Value","itnm":"CI-Eng-Sample.TANK1.INFLOW"}` in *Node Id* fixed it (values followed at once). Browsing into an item that is OPC visible but not *Read* fails (`UncertainNotAllNodesAvailable`, `OPXC-E-BRW_NODE`). | open | Check whether the browse dialog can expand an item to `Value` (e.g. double-click); otherwise type the node ID. | `knowledge/manuals/IM36K10E20-01EN.md` §2 (done); `.claude/skills/data-access/tasks/opcua-client.md` §3 (done) |

View file

@ -3,7 +3,7 @@ manual: IM 36K10L30-01EN
title: BUS Service Engineering title: BUS Service Engineering
edition: 3rd Edition, Sep. 2023 edition: 3rd Edition, Sep. 2023
version: R1.03 version: R1.03
status: from docs; installed tools, setup files (dur.sup, durm_1_udp.sup, time_table.sup, fmfprt.sup, durutl.sup) and durm_start.cmd checked read-only 2026-10-01; durwfp verified; umhman, umhtestprog, umhmsg fail on the test system (ISS-030) status: from docs; installed tools, setup files (dur.sup, durm_1_udp.sup, time_table.sup, fmfprt.sup, durutl.sup) and durm_start.cmd checked read-only 2026-10-01; durwfp verified; umhman, umhtestprog, umhmsg verified after a fresh start (ISS-030)
--- ---
# BUS Service Engineering (R1.03) # BUS Service Engineering (R1.03)
@ -57,9 +57,9 @@ second node; `durutl.sup` has no active lines.
`-q <printer queue>` prints too. `-q <printer queue>` prints too.
- Tools: `umhtestprog` (tests the message path), `umhmsg <hex code> [<var> <value>]…` - Tools: `umhtestprog` (tests the message path), `umhmsg <hex code> [<var> <value>]…`
(issue a message from a script), `umhman` (look up a hex code, interactive), (issue a message from a script), `umhman` (look up a hex code, interactive),
`umhlogtoo` (copy of all messages to a terminal). **On the test system** `umhman` crashes `umhlogtoo` (copy of all messages to a terminal). **Verified** after a fresh start: `umhman`
with redirected input, `umhtestprog` crashes, and `umhmsg` ends with "license expired" with piped input, `umhmsg` (message appears in `umhlog.log`) and `umhtestprog` work; late in an
(ISS-030). unlicensed session they crashed or reported "license expired" (ISS-030).
- A message shown as `UMH Message Text Error: Message number <hex> (…)` means the text could - A message shown as `UMH Message Text Error: Message number <hex> (…)` means the text could
not be formatted (e.g. a `%` in a PRINT text, ISS-025). not be formatted (e.g. a `%` in a PRINT text, ISS-025).

View file

@ -48,7 +48,10 @@ No setup file, no parameters. On the test system `equipment_start.cmd` starts it
automatically on the host node, and it was running. The manual calls the target a history automatically on the host node, and it was running. The manual calls the target a history
group; it is the dataset **`STATION_STAT`** (fields: time stamp, station, line, time span, group; it is the dataset **`STATION_STAT`** (fields: time stamp, station, line, time span,
sends, good answers, bad return code, timeouts, frame errors, bad CRC, retries, line bad). sends, good answers, bad return code, timeouts, frame errors, bad CRC, retries, line bad).
An export returned no records on the test system (ISS-021). **Verified:** `dssqld -e st.qlo -d STATION_STAT` lists one record per station line per hour
(`NAME` = `<DD-MON-YY hh:00>/<station>/<line>`), e.g. `CIENG_PLC` with `TIMESPAN` (seconds
counted in that hour), `SENDS` and `GOODANS` 1560/1560. Only stations that actually sent requests
appear; the first export (no communicating station) was empty (ISS-021). History type 4.
## 3. Debugger: `eqpdbg` (§3) ## 3. Debugger: `eqpdbg` (§3)