Phase 14: Trend settings (desktop and web) and the HTML trend fix #16
1 changed files with 2 additions and 2 deletions
|
|
@ -60,7 +60,7 @@ development system (see "Test system" in `progress.md`); they do not exist on ot
|
||||||
| ISS-038 | 2026-10-01 | HISTORY (`ithloahis` + rollover) | An `ithloahis` sample that was dropped (dated 11:50, before the active unit) still became the **initial value** of the next unit: after a forced rollover at 12:05:26 `ITEM_HISTORY` shows `CI-Eng-Sample.TANK1.INFLOW` = 95 (`INITIAL_VALUE` 1) although the item's value was 112. History after loading old samples can therefore show a wrong value at the next rollover. | closed | Retested 2026-10-01 after a CI Server restart (first unit 18:05:46). (a) Sample dated one day earlier (95), live value 112, forced rollover: initial value 112 — correct. (b) Sample dated 18:00 (96, a few minutes before the first unit), live value 113, forced rollover: initial value **96** — wrong again; the live item value stayed 113. So a dropped sample dated shortly before the first unit (same day) becomes the next unit's initial value; a much older one did not. Also found: a forced rollover within 2 minutes of the previous one is refused (`DSI-E-ROLLDONE`). Documented as a caution; behaviour confirmed, ready to close. Closed 2026-10-01 (confirmed by user). | `.claude/skills/system-management/tasks/load-history.md`; `knowledge/manuals/IM36K10C40-01EN.md` §3 |
|
| ISS-038 | 2026-10-01 | HISTORY (`ithloahis` + rollover) | An `ithloahis` sample that was dropped (dated 11:50, before the active unit) still became the **initial value** of the next unit: after a forced rollover at 12:05:26 `ITEM_HISTORY` shows `CI-Eng-Sample.TANK1.INFLOW` = 95 (`INITIAL_VALUE` 1) although the item's value was 112. History after loading old samples can therefore show a wrong value at the next rollover. | closed | Retested 2026-10-01 after a CI Server restart (first unit 18:05:46). (a) Sample dated one day earlier (95), live value 112, forced rollover: initial value 112 — correct. (b) Sample dated 18:00 (96, a few minutes before the first unit), live value 113, forced rollover: initial value **96** — wrong again; the live item value stayed 113. So a dropped sample dated shortly before the first unit (same day) becomes the next unit's initial value; a much older one did not. Also found: a forced rollover within 2 minutes of the previous one is refused (`DSI-E-ROLLDONE`). Documented as a caution; behaviour confirmed, ready to close. Closed 2026-10-01 (confirmed by user). | `.claude/skills/system-management/tasks/load-history.md`; `knowledge/manuals/IM36K10C40-01EN.md` §3 |
|
||||||
| ISS-039 | 2026-10-01 | HISTORY (setup) | Installed vs manuals: `hisdbg` menu runs to option 22 (manual text: `-1 - 10`, list to 22) and lists history types 4 (`STATION_STAT`) and 36 (`SYS_LOG`) not in IM 36K10L20 §3.1; `ithsag.sup` keyword `run_interval` (manual: *Heartbeat*) and `queue_size` 500 KB (manual default 200); the option-type table in IM 36K10L20 §3.1 is garbled in the PDF (observed: Scan/Time `1 1`, Event/Item `2 2`, Aggregation `4 4`). | closed | Installed software is the reference (standing user decision). Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10L20-01EN.md` §3; `knowledge/manuals/IM36K10C40-01EN.md` §2 |
|
| ISS-039 | 2026-10-01 | HISTORY (setup) | Installed vs manuals: `hisdbg` menu runs to option 22 (manual text: `-1 - 10`, list to 22) and lists history types 4 (`STATION_STAT`) and 36 (`SYS_LOG`) not in IM 36K10L20 §3.1; `ithsag.sup` keyword `run_interval` (manual: *Heartbeat*) and `queue_size` 500 KB (manual default 200); the option-type table in IM 36K10L20 §3.1 is garbled in the PDF (observed: Scan/Time `1 1`, Event/Item `2 2`, Aggregation `4 4`). | closed | Installed software is the reference (standing user decision). Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10L20-01EN.md` §3; `knowledge/manuals/IM36K10C40-01EN.md` §2 |
|
||||||
| ISS-040 | 2026-10-01 | HISTORY (aggregation) | Aggregation group `CIENG_AGG` (30 min + hour, `TANK1.LEVEL` max/min/avg) ran (`ithsag.log`: *Aggregation Completed*) but stored no values: retrieval gave `0x09 = ITM error` per period. `TANK1.LEVEL` was in `CIENG_EVENT` and `CIENG_SCAN10S`, both priority 0. Also `INTERPOLATION = "30 minutes"` is refused by `dssqld`; the installed name is `30Minutes`. | closed | Closed 2026-10-01 (confirmed by user). 2026-10-01 14:02: after `CIENG_SCAN10S` got `PRIORITY` 10, the 13:30–14:00 period stored max 77, min 33, avg 52.7, quality 1000 (`ithdbg` 20 and `dssqld` with `INTERPOLATION = "30Minutes"`). Cause: equal source priorities (C40 §2.1 says the highest-priority group is the source, but not that a tie gives nothing). Sample fixed (priority 10). The hourly value for 13:00–14:00 was not stored (first half had no source); not rechecked. Proposed close. | `.claude/skills/history-management/tasks/storage-groups.md` §4 (done); `knowledge/manuals/IM36K10C40-01EN.md` §3 (done); `examples/CI-Eng-Sample/03_his_group_df.qli`, `README.md` (done) |
|
| ISS-040 | 2026-10-01 | HISTORY (aggregation) | Aggregation group `CIENG_AGG` (30 min + hour, `TANK1.LEVEL` max/min/avg) ran (`ithsag.log`: *Aggregation Completed*) but stored no values: retrieval gave `0x09 = ITM error` per period. `TANK1.LEVEL` was in `CIENG_EVENT` and `CIENG_SCAN10S`, both priority 0. Also `INTERPOLATION = "30 minutes"` is refused by `dssqld`; the installed name is `30Minutes`. | closed | Closed 2026-10-01 (confirmed by user). 2026-10-01 14:02: after `CIENG_SCAN10S` got `PRIORITY` 10, the 13:30–14:00 period stored max 77, min 33, avg 52.7, quality 1000 (`ithdbg` 20 and `dssqld` with `INTERPOLATION = "30Minutes"`). Cause: equal source priorities (C40 §2.1 says the highest-priority group is the source, but not that a tie gives nothing). Sample fixed (priority 10). The hourly value for 13:00–14:00 was not stored (first half had no source); not rechecked. Proposed close. | `.claude/skills/history-management/tasks/storage-groups.md` §4 (done); `knowledge/manuals/IM36K10C40-01EN.md` §3 (done); `examples/CI-Eng-Sample/03_his_group_df.qli`, `README.md` (done) |
|
||||||
| ISS-041 | 2026-10-01 | GRAPHICS (HTML trend) | In the HTML display (`localhost:8080/mobileoperator/?d=CIENG_Tank`) the trend shows the pen legend `CI-Eng-Sample.TANK1.LEVEL [CIENG_SCAN10S]` and time axis but draws no line, although `ITEM_HISTORY` has 420 samples in the shown hour. Browser console: `Mismatch between number of labels (Time,CI-Eng-Sample.TANK1.LEVEL [CIENG_SCAN10S]) and number of columns in array (51)`. The trend has 4 further empty pens. 2026-10-01 later: the trend also had the property `chart.attribute[00]` connected to `TANK1.LEVEL` (added by mistake with the pen); the Operator Interface (desktop) showed *Short attribute name ( 61.0) is invalid*. After removing it the desktop trend draws the line, but the HTML trend still logs the mismatch error. | open | Tried 2026-10-01 (fresh session after a restart, 283 history samples in the hour): removing the 4 empty pens, and `updating` true / `updateInterval` 10 like the factory `AOG_TrendOpen` — the mismatch error and the empty trend stayed in both cases (changes reverted). Still to try: a Micro Trend, the HTML-supported trend properties (IM 36K10R30 §4.8.7), clearing the browser/`MO_CACHE_DISPLAYS` cache (the console shows `CIENG_Tank.xml` *loaded (from cache)*), and adding the pen to the factory *Open Trend* display in the HTML client. **Cause found 2026-10-02** (trend lab `CIENG_TrendLab`): a web-client defect, not a display setting. `DataSource.refresh()` in the web trend code (`mobileoperator\src\…\charts\trend\datasources\DataSource.js`, same in the served `src\lib\fasttools.min.js`) numbers **all 50** internal pen slots (`PEN_COUNT_LIMIT`; the filter for empty/hidden pens is commented out), so each data row has 51 columns, while the dygraph labels only list visible pens with an item. Proof: a 50-pen test display drew normally in the browser. Ruled out on the way: the `?historygroup` suffix, empty pens, `optimised`. **Workaround** (verified on the web): pad each trend to 50 visible pens with `displays/add_trend_spares.ps1` (spares scaled out of view, blank unique legend texts); sample `CIENG_TrendLab` uses it. Alternatively a Micro Trend (ISS-055). Report to Yokogawa. Close when the user confirms. | `.claude/skills/graphics/tasks/trend.md` (done); `create-display.md`, `deploy-displays.md` (done); `knowledge/manuals/IM36K10R30-01EN.md` §4 (done) |
|
| ISS-041 | 2026-10-01 | GRAPHICS (HTML trend) | In the HTML display (`localhost:8080/mobileoperator/?d=CIENG_Tank`) the trend shows the pen legend `CI-Eng-Sample.TANK1.LEVEL [CIENG_SCAN10S]` and time axis but draws no line, although `ITEM_HISTORY` has 420 samples in the shown hour. Browser console: `Mismatch between number of labels (Time,CI-Eng-Sample.TANK1.LEVEL [CIENG_SCAN10S]) and number of columns in array (51)`. The trend has 4 further empty pens. 2026-10-01 later: the trend also had the property `chart.attribute[00]` connected to `TANK1.LEVEL` (added by mistake with the pen); the Operator Interface (desktop) showed *Short attribute name ( 61.0) is invalid*. After removing it the desktop trend draws the line, but the HTML trend still logs the mismatch error. | closed | Tried 2026-10-01 (fresh session after a restart, 283 history samples in the hour): removing the 4 empty pens, and `updating` true / `updateInterval` 10 like the factory `AOG_TrendOpen` — the mismatch error and the empty trend stayed in both cases (changes reverted). Still to try: a Micro Trend, the HTML-supported trend properties (IM 36K10R30 §4.8.7), clearing the browser/`MO_CACHE_DISPLAYS` cache (the console shows `CIENG_Tank.xml` *loaded (from cache)*), and adding the pen to the factory *Open Trend* display in the HTML client. **Cause found 2026-10-02** (trend lab `CIENG_TrendLab`): a web-client defect, not a display setting. `DataSource.refresh()` in the web trend code (`mobileoperator\src\…\charts\trend\datasources\DataSource.js`, same in the served `src\lib\fasttools.min.js`) numbers **all 50** internal pen slots (`PEN_COUNT_LIMIT`; the filter for empty/hidden pens is commented out), so each data row has 51 columns, while the dygraph labels only list visible pens with an item. Proof: a 50-pen test display drew normally in the browser. Ruled out on the way: the `?historygroup` suffix, empty pens, `optimised`. **Workaround** (verified on the web): pad each trend to 50 visible pens with `displays/add_trend_spares.ps1` (spares scaled out of view, blank unique legend texts); sample `CIENG_TrendLab` uses it. Alternatively a Micro Trend (ISS-055). Report to Yokogawa. Close when the user confirms. Closed 2026-10-02 (confirmed by user). | `.claude/skills/graphics/tasks/trend.md` (done); `create-display.md`, `deploy-displays.md` (done); `knowledge/manuals/IM36K10R30-01EN.md` §4 (done) |
|
||||||
| ISS-042 | 2026-10-01 | GRAPHICS (layouts) | Installed vs `Layouts.readme`: the factory layouts use status line item types `displayName`, `playbackIndicator` and `dateTime` and the commands `reload <frame>` / `reload all`, none of which the readme lists (readme: `statusText`, `userName`, `progresBar`, `graphicsQueueLevel`, `connectionState`); the readme also writes `zooom` for the zoom command (factory files use `zoom`). | closed | Installed software is the reference (standing user decision). Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/graphics/tasks/layouts.md` §2 |
|
| ISS-042 | 2026-10-01 | GRAPHICS (layouts) | Installed vs `Layouts.readme`: the factory layouts use status line item types `displayName`, `playbackIndicator` and `dateTime` and the commands `reload <frame>` / `reload all`, none of which the readme lists (readme: `statusText`, `userName`, `progresBar`, `graphicsQueueLevel`, `connectionState`); the readme also writes `zooom` for the zoom command (factory files use `zoom`). | closed | Installed software is the reference (standing user decision). Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/graphics/tasks/layouts.md` §2 |
|
||||||
| ISS-043 | 2026-10-01 | REPORT (system reports) | IM 36K10C30 App. 1.3 names two system reports `ALM_ATTS_CUR` and `ALM_ATRS_HIS`; the installed reports are `ALM_ATTRS_CUR` and `ALM_ATTRS_HIS`. The other 26 names match. | closed | Installed software is the reference (standing user decision). Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10C30-01EN.md` §8 (done) |
|
| ISS-043 | 2026-10-01 | REPORT (system reports) | IM 36K10C30 App. 1.3 names two system reports `ALM_ATTS_CUR` and `ALM_ATRS_HIS`; the installed reports are `ALM_ATTRS_CUR` and `ALM_ATTRS_HIS`. The other 26 names match. | closed | Installed software is the reference (standing user decision). Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10C30-01EN.md` §8 (done) |
|
||||||
| ISS-044 | 2026-10-01 | REPORT (scheduling) | Behaviour not in the manuals, found by quick load: a generation interval below 10 minutes is refused (`HIS-E-ROLLTOFAST`, the interval is the rollover of the report's storage group); a scheduled report cannot be deleted (`RPT-E-ACTIVE`) until `ACTIVATION_TIME` and `GENERATION_INTERVAL` are cleared; `CORRECT_DAYLIGHT` 0 counts intervals in UTC (06:00 set for January ran at 05:00 in October); a past activation time moves to the next slot - once (modify, past time within the lifetime) a single report labelled with the old time was generated, at insert with an older time none. | closed | Documented as verified behaviour; the one-off generation for a past activation time is not fully understood. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/reporting/tasks/define-reports.md` §1, §5, §6; `knowledge/manuals/IM36K10C30-01EN.md` §2; `examples/CI-Eng-Sample/83a_stop_report_df.qli`, `18_report_df.qli` |
|
| ISS-044 | 2026-10-01 | REPORT (scheduling) | Behaviour not in the manuals, found by quick load: a generation interval below 10 minutes is refused (`HIS-E-ROLLTOFAST`, the interval is the rollover of the report's storage group); a scheduled report cannot be deleted (`RPT-E-ACTIVE`) until `ACTIVATION_TIME` and `GENERATION_INTERVAL` are cleared; `CORRECT_DAYLIGHT` 0 counts intervals in UTC (06:00 set for January ran at 05:00 in October); a past activation time moves to the next slot - once (modify, past time within the lifetime) a single report labelled with the old time was generated, at insert with an older time none. | closed | Documented as verified behaviour; the one-off generation for a past activation time is not fully understood. Close when the user confirms. Closed 2026-10-01 (confirmed by user). | `.claude/skills/reporting/tasks/define-reports.md` §1, §5, §6; `knowledge/manuals/IM36K10C30-01EN.md` §2; `examples/CI-Eng-Sample/83a_stop_report_df.qli`, `18_report_df.qli` |
|
||||||
|
|
@ -75,4 +75,4 @@ development system (see "Test system" in `progress.md`); they do not exist on ot
|
||||||
| ISS-053 | 2026-10-01 | HAC (manual vs installed) | IM 36K10J20 vs the installed `hac.sup`/scripts: (1) *Start in manual mode*: §1.3 says HAC starts in manual by default, §1.5 and the `hac.sup` help say automatic; the installed template sets `START_MANUAL = YES`. (2) `MAXOPNDB` default: help 500, manual 50 (§1.5) and 5 (§4.8). (3) `QUESIZE` default: help 100 K, manual 2000 K (file sets 2000). (4) §4.5 says `tls\com` and `tls\exe` cannot be mirrored, but the template mirrors `12 COM` (excluding `ci_command.cmd`). (5) §4.4 says the critical processes are already in the queue/CPU check lists; the installed file has no `MAX_QUEUE`/`MAX_CPU`/`INACTIVE` lines. (6) `hacw_standby` uses `TLS_LST_PATH` when `TLS_BACKUP_PATH` is unset (manual: `TLS_ALLUSERS_PATH`). (7) The template `IP_DEVICE` is `localhost` (priority 0), which §1.3 says to remove after testing. (8) HMI properties have `communicationInterval`/`Timeout`/`RetryCount`, not in the manual. | closed | Installed software is the reference (standing user decision); documented in the J20 summary §5 and the `high-availability` skill. Not testable on one server. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10J20-01EN.md`; `.claude/skills/high-availability/tasks/*.md` |
|
| ISS-053 | 2026-10-01 | HAC (manual vs installed) | IM 36K10J20 vs the installed `hac.sup`/scripts: (1) *Start in manual mode*: §1.3 says HAC starts in manual by default, §1.5 and the `hac.sup` help say automatic; the installed template sets `START_MANUAL = YES`. (2) `MAXOPNDB` default: help 500, manual 50 (§1.5) and 5 (§4.8). (3) `QUESIZE` default: help 100 K, manual 2000 K (file sets 2000). (4) §4.5 says `tls\com` and `tls\exe` cannot be mirrored, but the template mirrors `12 COM` (excluding `ci_command.cmd`). (5) §4.4 says the critical processes are already in the queue/CPU check lists; the installed file has no `MAX_QUEUE`/`MAX_CPU`/`INACTIVE` lines. (6) `hacw_standby` uses `TLS_LST_PATH` when `TLS_BACKUP_PATH` is unset (manual: `TLS_ALLUSERS_PATH`). (7) The template `IP_DEVICE` is `localhost` (priority 0), which §1.3 says to remove after testing. (8) HMI properties have `communicationInterval`/`Timeout`/`RetryCount`, not in the manual. | closed | Installed software is the reference (standing user decision); documented in the J20 summary §5 and the `high-availability` skill. Not testable on one server. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10J20-01EN.md`; `.claude/skills/high-availability/tasks/*.md` |
|
||||||
| ISS-054 | 2026-10-01 | AD (manual vs installed) | IM 36K10J40 vs the installed `dssana.sup`: the *Active Directory* tab has keywords the manual does not describe — `AD_SERVER`, `AD_SERVER_BACKUP` (host[:port], 389/636), `AD_SECURE` (LDAPS; installed `NO`, help says default yes), `AD_ACCESS_USER`/`AD_ACCESS_PASSWORD` (blank = the CI Server service account). The manual's *Profile priority* is `USER_DF.MERGE_PRIORITY`; *Directory group* is `DIRECTORY_GROUP` (68 characters). The SSO keytab path is given as `%TLS_WAP_PATH%\webapps\auth\WEB-INF` (§2.5.1) and `%TLS_ALLUSERS_PATH%\wap\webapps\auth\WEB-INF` (§3.4.3) — the same folder on the test system. | closed | Installed software is the reference; documented in the J40 summary §5 and `authorization/tasks/active-directory.md`. Not testable without a domain. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10J40-01EN.md`; `.claude/skills/authorization/tasks/active-directory.md` |
|
| ISS-054 | 2026-10-01 | AD (manual vs installed) | IM 36K10J40 vs the installed `dssana.sup`: the *Active Directory* tab has keywords the manual does not describe — `AD_SERVER`, `AD_SERVER_BACKUP` (host[:port], 389/636), `AD_SECURE` (LDAPS; installed `NO`, help says default yes), `AD_ACCESS_USER`/`AD_ACCESS_PASSWORD` (blank = the CI Server service account). The manual's *Profile priority* is `USER_DF.MERGE_PRIORITY`; *Directory group* is `DIRECTORY_GROUP` (68 characters). The SSO keytab path is given as `%TLS_WAP_PATH%\webapps\auth\WEB-INF` (§2.5.1) and `%TLS_ALLUSERS_PATH%\wap\webapps\auth\WEB-INF` (§3.4.3) — the same folder on the test system. | closed | Installed software is the reference; documented in the J40 summary §5 and `authorization/tasks/active-directory.md`. Not testable without a domain. Closed 2026-10-01 (confirmed by user). | `knowledge/manuals/IM36K10J40-01EN.md`; `.claude/skills/authorization/tasks/active-directory.md` |
|
||||||
| ISS-055 | 2026-10-02 | GRAPHICS (Micro Trend) | A Micro Trend written into `CIENG_TrendLab` (`itemName[0..1]` = `TANK1.LEVEL`/`INFLOW`, `numberOfPens` 2, `realTime`, `fillWithHistory`) drew both pens on the desktop and in the browser the first time (about 13:33), then stayed **blank** on every later open on both clients: with and without the 48 spare trend pens, and with explicit `timeRange` 600 / `sampleCount` 60. No console error; CI Server running. Code: `MicroTrend.js` only starts when all properties are set (`startTrendIfAllPropertiesAreSet`; it also compares `scaleMax[i]` with `scaleMin[1]`). | open | Later 2026-10-02 the clean sample file (no explicit `timeRange`/`sampleCount`, 48 spare trend pens) drew both pens on the desktop and in the browser after a fresh login; after a *View > Reload* in the browser only LEVEL showed fully, INFLOW only a short piece: the behaviour is intermittent. Still to try: build the Micro Trend in the Edit Module (compare the XML), connect `itemName[n]` instead of a fixed value (as in factory/test displays), a display with only the Micro Trend, a CI Server restart. | `.claude/skills/graphics/tasks/trend.md` §6; `examples/CI-Eng-Sample/displays/CIENG_TrendLab.xml` |
|
| ISS-055 | 2026-10-02 | GRAPHICS (Micro Trend) | A Micro Trend written into `CIENG_TrendLab` (`itemName[0..1]` = `TANK1.LEVEL`/`INFLOW`, `numberOfPens` 2, `realTime`, `fillWithHistory`) drew both pens on the desktop and in the browser the first time (about 13:33), then stayed **blank** on every later open on both clients: with and without the 48 spare trend pens, and with explicit `timeRange` 600 / `sampleCount` 60. No console error; CI Server running. Code: `MicroTrend.js` only starts when all properties are set (`startTrendIfAllPropertiesAreSet`; it also compares `scaleMax[i]` with `scaleMin[1]`). | open | Later 2026-10-02 the clean sample file (no explicit `timeRange`/`sampleCount`, 48 spare trend pens) drew both pens on the desktop and in the browser after a fresh login; after a *View > Reload* in the browser only LEVEL showed fully, INFLOW only a short piece: the behaviour is intermittent. Still to try: build the Micro Trend in the Edit Module (compare the XML), connect `itemName[n]` instead of a fixed value (as in factory/test displays), a display with only the Micro Trend, a CI Server restart. | `.claude/skills/graphics/tasks/trend.md` §6; `examples/CI-Eng-Sample/displays/CIENG_TrendLab.xml` |
|
||||||
| ISS-056 | 2026-10-02 | GRAPHICS (trend, manual vs installed) | (1) IM 36K10C50 Table 2.27-28 lists *Appearance - Show in Legend* as supported in the HTML display, but the web legend listed pens with `visibleLegend` false (the desktop hides them). (2) The legend position (`PositionSouthWest`) was not applied in the browser (not supported per the table). (3) The manual says a trend has up to 20 pens; the component property sheet has 20 slots, but the web code reserves 50 and `maximumPens` 50 works on the desktop. (4) Desktop: pen `title`/`titlePlacement`, pen limit values `lowLimit`… and chart `backgroundPaint` had no visible effect; time-axis minor ticks/grid showed nothing at a 10-minute range. | open | Documented in `trend.md`; installed software is the reference. Close when the user confirms. | `.claude/skills/graphics/tasks/trend.md` |
|
| ISS-056 | 2026-10-02 | GRAPHICS (trend, manual vs installed) | (1) IM 36K10C50 Table 2.27-28 lists *Appearance - Show in Legend* as supported in the HTML display, but the web legend listed pens with `visibleLegend` false (the desktop hides them). (2) The legend position (`PositionSouthWest`) was not applied in the browser (not supported per the table). (3) The manual says a trend has up to 20 pens; the component property sheet has 20 slots, but the web code reserves 50 and `maximumPens` 50 works on the desktop. (4) Desktop: pen `title`/`titlePlacement`, pen limit values `lowLimit`… and chart `backgroundPaint` had no visible effect; time-axis minor ticks/grid showed nothing at a 10-minute range. | closed | Documented in `trend.md`; installed software is the reference. Close when the user confirms. Closed 2026-10-02 (confirmed by user). | `.claude/skills/graphics/tasks/trend.md` |
|
||||||
|
|
|
||||||