--- manual: IM 36K10C60-01EN title: Advanced Operating Graphics edition: 5th Edition, Feb. 2026 (R1.05); first summarised from the 3rd Edition, Sep. 2023 (R1.03) version: R1.05 (first written for R1.03) status: from docs; R1.05 full text diff reviewed 2026-10-08 (only §1.2.2 changed); installed AOG displays checked read-only on R1.03 (DEPLOY\displays, mobileoperator) 2026-10-01; R1.05 AOG display/symbol lists awaiting user verification (ISS-097) --- # Advanced Operating Graphics — AOG library (R1.05) A ready-made library of symbols and displays in a consistent, high-performance HMI style, used from the Edit Module's Visualization sheet. Section numbers refer to the manual. ## 1. Symbols (§1.1) | Kind | Purpose | Palettes / examples | |---|---|---| | Equipment symbols | Static equipment, no live data | `AOG_ContainersAndVessels` (AOG_Tank, AOG_Vessel, AOG_Reactor, …), `AOG_HeatTransfer`, `AOG_Indicator`, `AOG_MaterialHandling`, `AOG_Mixing`, `AOG_Rotating` (pumps, compressors, turbine), `AOG_Separators`, `AOG_ValvesAndActuators`, `AOG_Electrical`, `AOG_Filters`, `AOG_Others` (Yokogawa systems such as AOG_CentumFCS, AOG_ProsafeRS, AOG_StardomFCN, AOG_FAM3, AOG_DTS; field devices; stations) | | Item symbols | Show and change one or more item attributes | indicators (bar, needle, circular, radial, number, text, on/off, manual, alarm, trend), valves (2-way, 3-way, on/off), selection box, name/info | | Object symbols (`AOG_O…`) | Same, driven by PROCESS Service object signals | e.g. `AOG_ONumberIndicator`, `AOG_OHorizontalBarIndicator` | | Navigation symbol, components | Navigation between displays | | ## 2. Displays (§1.2) Standard displays: `AOG_Default`, `AOG_DisplayTemplate` (start for new displays), `AOG_Style` (global style parameters), `AOG_MenuMain`, alarm displays (`AOG_AlarmBanner`, `AOG_AlarmCurrent`, `AOG_AlarmHistory`, `AOG_AlarmShelved`), `AOG_AuditTrail`, `AOG_ItemFaceplate`, `AOG_ItemTuningPanel`, `AOG_ObjectFaceplate`, `AOG_ObjectTuningPanel`, `AOG_SetItemMode`, `AOG_SetObjectMode`, `AOG_SetNumberPV/SV/SL/SH/SLL/SHH`, `AOG_LockStatus`, `AOG_TrendOpen`, OPC UA method call displays; plus demo displays. R1.04 (§1.2.2) documents the demo displays `AOG_UAC_Method_Demo` (already installed on R1.03), `AOG_UAC_MethodArg_Call2` and `AOG_OPCUA_Methods` (not on the R1.03 machine, which has `AOG_UAC_MethodArg_Call` and `AOG_UAC_Method_Call`; R1.05 names not checked, ISS-097): a list of OPC UA client methods and a display to set input arguments, call a method and read the outputs, last call time and result. The CI Server method object (made from `UAC_MTD_JBASE`) must have at least as many input/output arguments as the external method; fewer give the errors *incorrect method key* / *incorrect input/output parameters* (skill `data-access`, OPC UA methods; from docs). **Installed (R1.03)**: these are in `DEPLOY\displays`, and the alarm, audit, default, menu, style, trend and UA method displays also exist as HTML displays. ## 3. Global style parameters (§1.1, §2.1.1) Defined once on the `AOG_Style` display (*Parameters* tab) and used by all AOG symbols: colours (`AOG_C…`: alarm high/medium/low/diagnostic/off, display background, equipment running/off/not running, fluid and gas lines, indicator background/limit/normal/outline/signal, manual control, selector, text 1–4), strokes (`AOG_S…`), fonts (`AOG_FT1–4`), engineering unit texts (`AOG_EF1` flow, `AOG_EL1` level, `AOG_EP1` pressure, `AOG_ET1/2` temperature), on/off texts, `AOG_BlinkOnNotAcknowledged`. Changing a value changes every symbol that uses it. ## 4. Building an HMI (§2) Edit Module → (optionally) adjust `AOG_Style` and save → *New display* or start from `AOG_DisplayTemplate` → place AOG symbols from the Visualization sheet → connect them to items or objects → save → open in the operator interface. New symbols can be made in the same style. ## 5. Enterprise (§3) Enterprise displays and AOG item/object symbols for enterprise engineering (items/objects on several servers; locations chosen per symbol). Not practiced: the sample display uses plain components; AOG symbols need the Edit Module GUI. ## R1.05 installed AOG displays (V5, 2026-10-09) The R1.05 test server has the same `AOG_*` displays as R1.03 plus `AOG_UAC_MethodArg_Call2` (display and HTML export). `AOG_OPCUA_Methods`, named in the 5th Edition §1.2.2, is **not** installed (ISS-097). OPC UA method demo displays installed: `AOG_UAC_Method_Demo`, `AOG_UAC_Method_Call`, `AOG_UAC_MethodArg_Call`, `AOG_UAC_MethodArg_Call2`.