@LANGUAGE ENGLISH @VERSION 1.03.00 ! Alarm definitions used by TANK1.LEVEL (16_item_alarm_df.qli). Load before the items refer to them. ! Acknowledgement type: every alarm needs a manual acknowledgement; a return to normal is ! acknowledged automatically only if the alarm was acknowledged (same matrix as MANUAL). ! Field _: from state N/A1/A2/A3 with Ack/Nack, to state N/A1/A2/A3; 1 = automatic. ! Unlisted matrix fields default to 0 (manual). @FIELDS NAME,DESCRIPTION,EAL_ACK,NA_N,NN_N,A1A_N,A2A_N,A3A_N @ALARM_ACK_DF "CIENG_ACK","CI-Eng-Sample: manual ack; auto ack on return to normal if acked",0,1,1,1,1,1 ! Area of interest (alarm grouping for displays and destinations) @FIELDS NAME,DESCRIPTION @ALARM_AOI_DF "CIENG_TANKS","CI-Eng-Sample tank items" ! Alarm selection area, compiled on load (COMPILE = 1). Keywords and operators need spaces. @FIELDS NAME,DESCRIPTION,COMPILE,EXPRESSION @ALARM_ASA_DF "CIENG_TANK1","Alarms of section CI-Eng-Sample.TANK1",1,\ @" /* Alarm selection area : CIENG_TANK1 */ SECTION = "CI-Eng-Sample.TANK1""@