- Deleted the three old displays; add_trend_spares.ps1 kept as a documented tool - 19b_audit_item_df.qli: operator writes now come from the Manual / Auto buttons on CIENG_Control - Tested on CI Server R1.03.00 2026-10-06: remove_displays / deploy_displays cycle leaves exactly the 8 new displays; Manual / Auto on CIENG_Control audited as ITEM.VALUE.MODIFY.OPER-INTERFACE (user, old/new value) Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
15 lines
474 B
Text
15 lines
474 B
Text
@LANGUAGE
|
|
ENGLISH
|
|
|
|
@VERSION
|
|
1.03.00
|
|
|
|
! CI-Eng-Sample: switch on "Audit trailing wanted" (AUDIT_INFO) for PUMP1.MODE (loaded with
|
|
! dssqld -m). Operator writes from a display (buttons Manual / Auto on CIENG_Control) are
|
|
! then stored as ITEM.VALUE.MODIFY.OPER-INTERFACE with old and new value; with AUDIT_INFO 0 they
|
|
! are not audited at all. Changes through DSS (dssqld, Engineering Module) are audited anyway.
|
|
@FIELDS
|
|
NAME,AUDIT_INFO
|
|
|
|
@ITEM_DF
|
|
"CI-Eng-Sample.PUMP1.MODE",1
|