- Group CIENG_OPERATOR dropped (08, 85, load.cmd, README): the live-data Start also works for a user in the factory group OPERATOR (tested 2026-10-06 as OPER), so EXECUTE_GENERAL_COMMANDS is not needed; 08b_user_df.qli gives CIENG the group OPERATOR - remove.cmd / README: open CIENG session note reworded - Generator README / cixml.py: arc angles run clockwise from 3 o'clock on desktop and web (fixed and connected; the earlier "mirrored on the desktop" note was wrong); rounding above 1 draws an ellipse on both clients - Tested on CI Server R1.03.00 2026-10-06: CIENG logon (empty password) and Start with group OPERATOR; test display with static and connected arcs on both clients Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
15 lines
611 B
Text
15 lines
611 B
Text
@LANGUAGE
|
|
ENGLISH
|
|
|
|
@VERSION
|
|
1.03.00
|
|
|
|
! CI-Eng-Sample demo user CIENG (IM 36K10C10-01EN 2.5), CI Server R1.03.00: factory group OPERATOR,
|
|
! logs on to layout CIENG_Operator with display CIENG_Overview (Operator Interface and web).
|
|
! Empty password: PASSWORD "" must be given explicitly (tested 2026-10-06: without the field the
|
|
! user has no password set and every logon fails with DSS-E-UNK_USER).
|
|
@FIELDS
|
|
NAME,DESCRIPTION,AUTH_GROUP,PROCESS_AREAS,LOGOFF_TIMEOUT,LAYOUT,INITIAL_DISPLAY,PASSWORD
|
|
|
|
@USER_DF
|
|
"CIENG","CI-Eng-Sample demo user (no password)","OPERATOR","1-999",0,"CIENG_Operator","CIENG_Overview",""
|