61ddce808f Split the root: spec/ for the design, status/ for the as-built
The root held five documents of two different kinds with nothing to tell
them apart. This repo is being handed over as both design spec and
as-built record, so the two are now separated by lifetime:

  spec/    BUILD-AI-CONTAINERS.md, YAU_Linux_Host_Onboarding.md
           normative and durable - what we agreed to build
  status/  workflow-map.html, current-state.html, REQUESTS.md
           snapshots that go stale and get edited constantly

Nothing mechanical moved. The twelve code folders are deployment
interface - compose builds from /home/azureuser/ai/api, /web, /ingest and
deploy.sh copies from $HOME/ai/compose, /cube/model, /db - so they stay
where they are. CLAUDE.md stays at root because Claude Code loads it from
there, as do .gitignore and .gitattributes, which only apply repo-wide
from the root.

All 26 references to the build spec were bare filenames in prose, so the
move broke no mechanism. The seven markdown links in README.md and the
two pointers at the top of CLAUDE.md are repointed.

docs/ is deleted. It only ever held .gitkeep - nothing mounted or read
it, and ingest reads the host path /datadisk/ai-docs mounted at /docs
inside the container. An empty docs/ invites the misreading "project
documentation goes here". The ignore rule stays, now covering the whole
folder, so a controlled document dropped there still cannot be committed.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
2026-09-01 15:59:26 +10:00
Claude
5de16ea4bb Prove the Phase 7 allow arm from the ai-web access log
Caddy forwards the real client address and ai-web's nginx log records it
as the last field, so the host can prove what a curl from here cannot:
10.0.0.21 loaded the page on 28 August, the day the SCADA-only rule was
applied, and asked three questions on 31 August, each answered 200.

verify.sh now reads that log instead of printing "somebody go and look",
and checks the deny arm from the other direction as well - any non-console
client in the log got past a matcher that should have refused it. A clean
miss is a warning, not a failure: docker logs are ephemeral and a recreate
of ai-web wipes the evidence.

That ephemerality is why a working operator path sat unnoticed for three
days. Access logging at the Caddy block was considered and declined on
1 September; the confirmation lives in the Phase 7 gate instead.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
2026-09-01 15:41:09 +10:00
Claude
8aba1f7f5c Rebuild the stand-in historian on CI Server item names
The three open Phase 5 findings were one defect: the stand-in was keyed on
CI Server POINT names (PS_STN_WET_WELL_LEVEL) when the historian is keyed on
CI Server ITEM names (AID.WRPS.STN.LEVEL). Modbus carries register numbers,
not names, so those two layers are free to differ - and do. Reconciling
against the register map, as planned, would only have proved the first three
namespaces agreed with each other.

Rebuilt from WRPS/05-scada/modbus, so item names, sample rates, retention and
timestamp semantics come from the machine rather than from a guess.

(a) Level tag does not join. PS_STN_WET_WELL_LEVEL becomes a tag row in its
    own right; LIT-101 is marked NOT HISTORISED - a field input on %IW0 that
    never reaches SCADA. It was the only seed row carrying two addresses.
    public.historian_items holds the item-to-tag mapping, generated by
    scripts/gen_historian_items.py and enforced non-empty at generate, at
    deploy and at verify.

(b) first_alarm/last_alarm returned UTC. Converted inside the measure, so it
    stays in Cube and happens once. Aggregate first, convert after - the other
    order picks the wrong row across a DST fall-back. Returned as a formatted
    string with a companion site_timezone measure. Storage being UTC is now
    confirmed, not assumed: all 49 points carry TIME_ZONE "Date+time GMT" and
    every history group CORRECT_DAYLIGHT=0. This answers Phase 4 task 4.

(c) High level alarm filed against the wrong equipment. Both sides were right
    about different things; the defect was asserting equipment twice. The
    history now carries no equipment column at all - faithful, since CI
    Server's section tree stops at the station and three pumps. Equipment is
    reached bit -> tag -> equipment via public.alarm_bits.

Alarms are derived, not stored: CI Server's ALARM_HISTORY group is empty
because every item imports with alarming off. Decomposing the alarm word needs
no configuration that does not exist.

Three things the SCADA config changed that were never filed as faults:
  - retention is 7 days, not 30. The advisory path was reporting a month of
    evidence drawn from a week of data
  - the analogue rate is 5 s, not 60. Two measures multiplied sample counts by
    a hardcoded 60 - a twelvefold overstatement that read as plausible
  - the deadband warning in process_values.yml was wrong and was steering
    people away from the correct measure

db/002_fixtures.sql now asserts its own counts at load and cross-checks the
alarm derivation against two independent signals. Those prove the pipeline,
not the plant.

db/README-standin-historian.md documents removal: the seam between generation
and contract, and twelve assumptions about imh that are NOT confirmed. Two of
them fail silently.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
2026-08-31 11:42:02 +10:00