The three open Phase 5 findings were one defect: the stand-in was keyed on
CI Server POINT names (PS_STN_WET_WELL_LEVEL) when the historian is keyed on
CI Server ITEM names (AID.WRPS.STN.LEVEL). Modbus carries register numbers,
not names, so those two layers are free to differ - and do. Reconciling
against the register map, as planned, would only have proved the first three
namespaces agreed with each other.
Rebuilt from WRPS/05-scada/modbus, so item names, sample rates, retention and
timestamp semantics come from the machine rather than from a guess.
(a) Level tag does not join. PS_STN_WET_WELL_LEVEL becomes a tag row in its
own right; LIT-101 is marked NOT HISTORISED - a field input on %IW0 that
never reaches SCADA. It was the only seed row carrying two addresses.
public.historian_items holds the item-to-tag mapping, generated by
scripts/gen_historian_items.py and enforced non-empty at generate, at
deploy and at verify.
(b) first_alarm/last_alarm returned UTC. Converted inside the measure, so it
stays in Cube and happens once. Aggregate first, convert after - the other
order picks the wrong row across a DST fall-back. Returned as a formatted
string with a companion site_timezone measure. Storage being UTC is now
confirmed, not assumed: all 49 points carry TIME_ZONE "Date+time GMT" and
every history group CORRECT_DAYLIGHT=0. This answers Phase 4 task 4.
(c) High level alarm filed against the wrong equipment. Both sides were right
about different things; the defect was asserting equipment twice. The
history now carries no equipment column at all - faithful, since CI
Server's section tree stops at the station and three pumps. Equipment is
reached bit -> tag -> equipment via public.alarm_bits.
Alarms are derived, not stored: CI Server's ALARM_HISTORY group is empty
because every item imports with alarming off. Decomposing the alarm word needs
no configuration that does not exist.
Three things the SCADA config changed that were never filed as faults:
- retention is 7 days, not 30. The advisory path was reporting a month of
evidence drawn from a week of data
- the analogue rate is 5 s, not 60. Two measures multiplied sample counts by
a hardcoded 60 - a twelvefold overstatement that read as plausible
- the deadband warning in process_values.yml was wrong and was steering
people away from the correct measure
db/002_fixtures.sql now asserts its own counts at load and cross-checks the
alarm derivation against two independent signals. Those prove the pipeline,
not the plant.
db/README-standin-historian.md documents removal: the seam between generation
and contract, and twelve assumptions about imh that are NOT confirmed. Two of
them fail silently.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
An operator standing at the SCADA console should not complete a Duo push to
ask a question, and nobody outside the plant should reach the assistant at
all. The ai.yokogawa.tech Caddy block now admits remote_ip 10.0.0.21
(yau-poc-cicore1, static) and returns 403 to everything else. Applied on
lin001 2026-08-28; snapshot at ~/Caddyfile.bak-ai-scadaonly-20260828.
This also settles why the console could not reach the assistant at all:
auth.yokogawa.tech has no pinpoint record on the DC, so a LAN browser got a
correct 302 to the portal and then died on DNS. It went unnoticed because the
device agents write to Influx over the /api/v2/write MFA bypass and never
touch the portal - no browser had ever hit Authelia from inside the VNet.
Verified before applying that an IP matcher can work here: Caddy sees real
client addresses, and WireGuard peers arrive masqueraded as 172.19.0.6 so
they do not match and are refused along with the internet.
What this costs, recorded in section 14 as a shortcut and not as a security
control: it is an IP allowlist on a flat network with no OT/IT boundary, so
anything that can take 10.0.0.21 inherits unauthenticated access; Langfuse
traces are now anonymous, so there is no record of who asked what; and the
assistant is out of browser reach over the VPN. It is in scope for the
section 2 OT/safety review, which is still outstanding.
api.yokogawa.tech is unchanged and still fully gated - Phase 9 publishing
depends on Remote-User/Remote-Groups and stays there. The now-inert
ai.yokogawa.tech entry in the Authelia rule is deliberately left in place so
restoring the gate is a Caddy reload rather than an Authelia restart that
logs out every user on the host.
verify.sh treats 403-from-lin001 as the pass for the deny arm and states
plainly that the allow arm can only be proved from cicore1.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
api.yokogawa.tech has a public A record but no pinpoint record on the DC, so
it does not resolve from inside the VNet at all. The browser called it by
hostname, which means an operator on cicore1 would have loaded the page and
had every question fail on DNS - the exact gap Phase 7's gate exists to catch,
and one an engineer's laptop cannot see.
Caddy now routes /ask under ai.yokogawa.tech to ai-api, inside a route block
so import authelia still runs first: forward_auth sorts after handle in the
default directive order, and outside a route the handles would be terminal and
the gate would never run. Only /ask is routed - the Phase 9 publisher rule is
scoped to api.yokogawa.tech and a wider route here would leave it inert.
Also fixes the fallback it replaces. The build arg defaults to "", and
`?? "https://api.yokogawa.tech"` does not catch an empty string, so the
documented real-deployment build resolved the API base to "" and posted /ask
at ai-web, which 404s it. verify.sh and deploy.sh now check both the route and
whether the built bundle carries the hostname.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Build spec and host brief carried in from C:\Claude and WRPS/02-env; the
plant model (equipment, tags, alarm bitmask, enums, unit conversions) is
derived from WRPS/04-plc/register-map.csv, WRPS/05-scada/modbus/scada-points.csv
and WRPS-CTL-003.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>