Commit graph

3 commits

Author SHA1 Message Date
Claude
5e0984b2cf Open the operator console to cicore1 only, without Authelia
An operator standing at the SCADA console should not complete a Duo push to
ask a question, and nobody outside the plant should reach the assistant at
all. The ai.yokogawa.tech Caddy block now admits remote_ip 10.0.0.21
(yau-poc-cicore1, static) and returns 403 to everything else. Applied on
lin001 2026-08-28; snapshot at ~/Caddyfile.bak-ai-scadaonly-20260828.

This also settles why the console could not reach the assistant at all:
auth.yokogawa.tech has no pinpoint record on the DC, so a LAN browser got a
correct 302 to the portal and then died on DNS. It went unnoticed because the
device agents write to Influx over the /api/v2/write MFA bypass and never
touch the portal - no browser had ever hit Authelia from inside the VNet.

Verified before applying that an IP matcher can work here: Caddy sees real
client addresses, and WireGuard peers arrive masqueraded as 172.19.0.6 so
they do not match and are refused along with the internet.

What this costs, recorded in section 14 as a shortcut and not as a security
control: it is an IP allowlist on a flat network with no OT/IT boundary, so
anything that can take 10.0.0.21 inherits unauthenticated access; Langfuse
traces are now anonymous, so there is no record of who asked what; and the
assistant is out of browser reach over the VPN. It is in scope for the
section 2 OT/safety review, which is still outstanding.

api.yokogawa.tech is unchanged and still fully gated - Phase 9 publishing
depends on Remote-User/Remote-Groups and stays there. The now-inert
ai.yokogawa.tech entry in the Authelia rule is deliberately left in place so
restoring the gate is a Caddy reload rather than an Authelia restart that
logs out every user on the host.

verify.sh treats 403-from-lin001 as the pass for the deny arm and states
plainly that the allow arm can only be proved from cicore1.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
2026-08-28 11:44:04 +10:00
Claude
76af3156fa Serve the operator page and /ask from one origin
api.yokogawa.tech has a public A record but no pinpoint record on the DC, so
it does not resolve from inside the VNet at all. The browser called it by
hostname, which means an operator on cicore1 would have loaded the page and
had every question fail on DNS - the exact gap Phase 7's gate exists to catch,
and one an engineer's laptop cannot see.

Caddy now routes /ask under ai.yokogawa.tech to ai-api, inside a route block
so import authelia still runs first: forward_auth sorts after handle in the
default directive order, and outside a route the handles would be terminal and
the gate would never run. Only /ask is routed - the Phase 9 publisher rule is
scoped to api.yokogawa.tech and a wider route here would leave it inert.

Also fixes the fallback it replaces. The build arg defaults to "", and
`?? "https://api.yokogawa.tech"` does not catch an empty string, so the
documented real-deployment build resolved the API base to "" and posted /ask
at ai-web, which 404s it. verify.sh and deploy.sh now check both the route and
whether the built bundle carries the hostname.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
2026-08-27 14:48:22 +10:00
Claude
34d2ccc576 Scaffold the WRPS plant operations assistant repository
Build spec and host brief carried in from C:\Claude and WRPS/02-env; the
plant model (equipment, tags, alarm bitmask, enums, unit conversions) is
derived from WRPS/04-plc/register-map.csv, WRPS/05-scada/modbus/scada-points.csv
and WRPS-CTL-003.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
2026-08-20 13:56:32 +10:00