Build spec and host brief carried in from C:\Claude and WRPS/02-env; the plant model (equipment, tags, alarm bitmask, enums, unit conversions) is derived from WRPS/04-plc/register-map.csv, WRPS/05-scada/modbus/scada-points.csv and WRPS-CTL-003. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
9 lines
2 KiB
CSV
9 lines
2 KiB
CSV
equipment_id,display_name,aliases,equipment_type,unit_name,description
|
|
STN-001,Waterloo Road Pump Station,Waterloo Road|Waterloo Rd|WRPS|the station|pump station|the pump station|station|Waterloo Road PS,station,WRPS,"Three-pump wastewater pump station. Duty/assist/assist on a common VSD speed reference. Controlled by openplc-runtime; historised by CI Server on cicore1."
|
|
WW-101,Wet Well,wet well|wetwell|the well|the wet well|well|sump|the sump|WW101|WW-101,vessel,WRPS,"Wet well. 0-7000 mm working range, 120 m3 per metre of level. Spill weir crest 6000 mm; LSHH 5500 mm; stop-all 1000 mm."
|
|
PU-301,Pump 01,Pump 01|Pump 1|pump one|pump1|P1|P-301|PU301|PU-301|number 1 pump|no 1 pump|first pump,pump,WRPS,"Submersible wastewater pump 1 of 3. Approx 120 L/s at duty against 22 m static lift. VSD driven from the common station speed reference."
|
|
PU-302,Pump 02,Pump 02|Pump 2|pump two|pump2|P2|P-302|PU302|PU-302|number 2 pump|no 2 pump|second pump,pump,WRPS,"Submersible wastewater pump 2 of 3. Approx 120 L/s at duty against 22 m static lift. VSD driven from the common station speed reference."
|
|
PU-303,Pump 03,Pump 03|Pump 3|pump three|pump3|P3|P-303|PU303|PU-303|number 3 pump|no 3 pump|third pump,pump,WRPS,"Submersible wastewater pump 3 of 3. Approx 120 L/s at duty against 22 m static lift. VSD driven from the common station speed reference."
|
|
MAN-301,Discharge Manifold,manifold|the manifold|discharge manifold|common manifold|rising main|MAN301|MAN-301,piping,WRPS,"Common discharge manifold collecting all three pumps into the rising main. 22 m static lift to the receiving point."
|
|
WEIR-105,Spill Weir,weir|the weir|spill weir|overflow|overflow weir|spill point|WEIR105,structure,WRPS,"Overflow weir. Crest at 6000 mm wet well level. A spill is an environmental reportable event - LSH-104 detects it."
|
|
MCC-501,Main Switchboard,switchboard|the switchboard|MCC|main switchboard|mains|mains supply|MCC501|MCC-501,electrical,WRPS,"Station main switchboard and mains supply. Healthy status monitored by XA-502."
|