yau-plant-assistant/db/seed/equipment.csv
Claude 34d2ccc576 Scaffold the WRPS plant operations assistant repository
Build spec and host brief carried in from C:\Claude and WRPS/02-env; the
plant model (equipment, tags, alarm bitmask, enums, unit conversions) is
derived from WRPS/04-plc/register-map.csv, WRPS/05-scada/modbus/scada-points.csv
and WRPS-CTL-003.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
2026-08-20 13:56:32 +10:00

2 KiB

1equipment_iddisplay_namealiasesequipment_typeunit_namedescription
2STN-001Waterloo Road Pump StationWaterloo Road|Waterloo Rd|WRPS|the station|pump station|the pump station|station|Waterloo Road PSstationWRPSThree-pump wastewater pump station. Duty/assist/assist on a common VSD speed reference. Controlled by openplc-runtime; historised by CI Server on cicore1.
3WW-101Wet Wellwet well|wetwell|the well|the wet well|well|sump|the sump|WW101|WW-101vesselWRPSWet well. 0-7000 mm working range, 120 m3 per metre of level. Spill weir crest 6000 mm; LSHH 5500 mm; stop-all 1000 mm.
4PU-301Pump 01Pump 01|Pump 1|pump one|pump1|P1|P-301|PU301|PU-301|number 1 pump|no 1 pump|first pumppumpWRPSSubmersible wastewater pump 1 of 3. Approx 120 L/s at duty against 22 m static lift. VSD driven from the common station speed reference.
5PU-302Pump 02Pump 02|Pump 2|pump two|pump2|P2|P-302|PU302|PU-302|number 2 pump|no 2 pump|second pumppumpWRPSSubmersible wastewater pump 2 of 3. Approx 120 L/s at duty against 22 m static lift. VSD driven from the common station speed reference.
6PU-303Pump 03Pump 03|Pump 3|pump three|pump3|P3|P-303|PU303|PU-303|number 3 pump|no 3 pump|third pumppumpWRPSSubmersible wastewater pump 3 of 3. Approx 120 L/s at duty against 22 m static lift. VSD driven from the common station speed reference.
7MAN-301Discharge Manifoldmanifold|the manifold|discharge manifold|common manifold|rising main|MAN301|MAN-301pipingWRPSCommon discharge manifold collecting all three pumps into the rising main. 22 m static lift to the receiving point.
8WEIR-105Spill Weirweir|the weir|spill weir|overflow|overflow weir|spill point|WEIR105structureWRPSOverflow weir. Crest at 6000 mm wet well level. A spill is an environmental reportable event - LSH-104 detects it.
9MCC-501Main Switchboardswitchboard|the switchboard|MCC|main switchboard|mains|mains supply|MCC501|MCC-501electricalWRPSStation main switchboard and mains supply. Healthy status monitored by XA-502.