The point list handed over in August named the points PS_STN_WET_WELL_LEVEL and the like. Those were never CI Server names. They came from gen_scada_points.py on the PLC side, which describes its own output as "a starting point for CI Server configuration, not a CI Server import file", and the CI Server generator ignored them entirely - it names points from its own address-keyed table. The names appear in no .qli export, and nowhere else in the WRPS project at all. This is the corrected delivery. ci-server-points.csv is keyed on the CI Server ITEM each point feeds, with the Modbus station and the point name beside it, so all four namespaces are visible in one row: LIT-101 instrument tag %QW0 PLC symbol and address WRPS_PLC:STN_LEVEL CI Server point - station, colon, point name AID.WRPS.STN.LEVEL CI Server item - what the historian is keyed on The 49 rows were joined onto the .qli exports by function code and Modbus address: 49 matched, 0 unmatched. The item and point names are read from the exports, not invented here. The six .qli files come too, unchanged. gen_historian_items.py needs them, and until now they existed only on one laptop behind a --wrps path - so the one file the rules say must never be hand-edited could be regenerated by exactly one person. 84 KB buys the team that back. These are uncontrolled documents: no revision, no effective date, no approval. The README says so, says how to ask for a fresh set, and records the two things that bite - that PS_ survives legitimately as four poll group names, and that his_group.qli and the live export disagree about the sample rates, with the live one winning. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
50 lines
7 KiB
CSV
50 lines
7 KiB
CSV
ci_item,ci_station,ci_point,description,poll_group,function_code,modbus_address,data_type,access,eng_units,raw_to_eng,eng_gain,format_mask,iec_address,plc_tag,notes
|
|
AID.WRPS.PU301.RUN_CMD,WRPS_PLC,PU301_RUN_CMD,Run command,PS_STATUS_BITS,FC01,0,Boolean,Read,,value,1.0,99999,%QX0.0,PU-301,
|
|
AID.WRPS.PU302.RUN_CMD,WRPS_PLC,PU302_RUN_CMD,Run command,PS_STATUS_BITS,FC01,1,Boolean,Read,,value,1.0,99999,%QX0.1,PU-302,
|
|
AID.WRPS.PU303.RUN_CMD,WRPS_PLC,PU303_RUN_CMD,Run command,PS_STATUS_BITS,FC01,2,Boolean,Read,,value,1.0,99999,%QX0.2,PU-303,
|
|
AID.WRPS.PU301.RUNNING,WRPS_PLC,PU301_RUNNING,Running,PS_STATUS_BITS,FC01,3,Boolean,Read,,value,1.0,99999,%QX0.3,PU-301,
|
|
AID.WRPS.PU302.RUNNING,WRPS_PLC,PU302_RUNNING,Running,PS_STATUS_BITS,FC01,4,Boolean,Read,,value,1.0,99999,%QX0.4,PU-302,
|
|
AID.WRPS.PU303.RUNNING,WRPS_PLC,PU303_RUNNING,Running,PS_STATUS_BITS,FC01,5,Boolean,Read,,value,1.0,99999,%QX0.5,PU-303,
|
|
AID.WRPS.PU301.AVAILABLE,WRPS_PLC,PU301_AVAILABLE,Available,PS_STATUS_BITS,FC01,6,Boolean,Read,,value,1.0,99999,%QX0.6,PU-301,
|
|
AID.WRPS.PU302.AVAILABLE,WRPS_PLC,PU302_AVAILABLE,Available,PS_STATUS_BITS,FC01,7,Boolean,Read,,value,1.0,99999,%QX0.7,PU-302,
|
|
AID.WRPS.PU303.AVAILABLE,WRPS_PLC,PU303_AVAILABLE,Available,PS_STATUS_BITS,FC01,8,Boolean,Read,,value,1.0,99999,%QX1.0,PU-303,
|
|
AID.WRPS.STN.IN_AUTO,WRPS_PLC,STN_IN_AUTO,Station in auto,PS_STATUS_BITS,FC01,9,Boolean,Read,,value,1.0,99999,%QX1.1,STN,
|
|
AID.WRPS.STN.HIGH_LEVEL,WRPS_PLC,STN_HIGH_LEVEL,High level alarm,PS_STATUS_BITS,FC01,10,Boolean,Read,,value,1.0,99999,%QX1.2,STN,
|
|
AID.WRPS.STN.SPILL_ACTIVE,WRPS_PLC,STN_SPILL_ACTIVE,Spill active,PS_STATUS_BITS,FC01,11,Boolean,Read,,value,1.0,99999,%QX1.3,STN,
|
|
AID.WRPS.PU301.TRIPPED,WRPS_PLC,PU301_TRIPPED,Tripped,PS_STATUS_BITS,FC01,12,Boolean,Read,,value,1.0,99999,%QX1.4,PU-301,
|
|
AID.WRPS.PU302.TRIPPED,WRPS_PLC,PU302_TRIPPED,Tripped,PS_STATUS_BITS,FC01,13,Boolean,Read,,value,1.0,99999,%QX1.5,PU-302,
|
|
AID.WRPS.PU303.TRIPPED,WRPS_PLC,PU303_TRIPPED,Tripped,PS_STATUS_BITS,FC01,14,Boolean,Read,,value,1.0,99999,%QX1.6,PU-303,
|
|
AID.WRPS.STN.LEVEL,WRPS_PLC,STN_LEVEL,Wet well level,PS_PUBLISHED,FC03,0,Signed 16-bit,Read,%,value / 60,0.016666666666666666,999.9,%QW0,STN,
|
|
AID.WRPS.STN.INFLOW,WRPS_PLC,STN_INFLOW,Inflow,PS_PUBLISHED,FC03,1,Signed 16-bit,Read,m3/h,value * 0.36,0.36,9999.9,%QW1,STN,
|
|
AID.WRPS.STN.DISCHARGE,WRPS_PLC,STN_DISCHARGE,Total discharge flow,PS_PUBLISHED,FC03,2,Signed 16-bit,Read,m3/h,value * 0.36,0.36,9999.9,%QW2,STN,
|
|
AID.WRPS.STN.PUMPS_RUNNING,WRPS_PLC,STN_PUMPS_RUNNING,Pumps running,PS_PUBLISHED,FC03,3,Signed 16-bit,Read,count,value,1.0,9,%QW3,STN,
|
|
AID.WRPS.STN.SPEED,WRPS_PLC,STN_SPEED,Common drive speed,PS_PUBLISHED,FC03,4,Signed 16-bit,Read,%,value * 0.2,0.2,999.9,%QW4,STN,
|
|
AID.WRPS.STN.TIME_TO_SPILL,WRPS_PLC,STN_TIME_TO_SPILL,Time to spill weir (32767 = drawing down),PS_PUBLISHED,FC03,5,Signed 16-bit,Read,s,value,1.0,99999,%QW5,STN,
|
|
AID.WRPS.STN.TIME_TO_LSHH,WRPS_PLC,STN_TIME_TO_LSHH,Time to LSHH (32767 = drawing down),PS_PUBLISHED,FC03,6,Signed 16-bit,Read,s,value,1.0,99999,%QW6,STN,
|
|
AID.WRPS.STN.NET_ACCUM,WRPS_PLC,STN_NET_ACCUM,Net accumulation (signed),PS_PUBLISHED,FC03,7,Signed 16-bit,Read,m3/h,value * 0.36,0.36,9999.9,%QW7,STN,
|
|
AID.WRPS.PU301.RUN_HOURS,WRPS_PLC,PU301_RUN_HOURS,Run hours,PS_PUBLISHED,FC03,8,Signed 16-bit,Read,h,value,1.0,99999,%QW8,PU-301,
|
|
AID.WRPS.PU302.RUN_HOURS,WRPS_PLC,PU302_RUN_HOURS,Run hours,PS_PUBLISHED,FC03,9,Signed 16-bit,Read,h,value,1.0,99999,%QW9,PU-302,
|
|
AID.WRPS.PU303.RUN_HOURS,WRPS_PLC,PU303_RUN_HOURS,Run hours,PS_PUBLISHED,FC03,10,Signed 16-bit,Read,h,value,1.0,99999,%QW10,PU-303,
|
|
AID.WRPS.STN.VOL_TO_SPILL,WRPS_PLC,STN_VOL_TO_SPILL,Volume remaining to spill,PS_PUBLISHED,FC03,11,Signed 16-bit,Read,m3,value,1.0,9999,%QW11,STN,
|
|
AID.WRPS.STN.STATE,WRPS_PLC,STN_STATE,Station state (enum 3.1),PS_PUBLISHED,FC03,12,Signed 16-bit,Read,,value,1.0,9,%QW12,STN,
|
|
AID.WRPS.PU301.STATE,WRPS_PLC,PU301_STATE,Pump state (enum 3.2),PS_PUBLISHED,FC03,13,Signed 16-bit,Read,,value,1.0,9,%QW13,PU-301,
|
|
AID.WRPS.PU302.STATE,WRPS_PLC,PU302_STATE,Pump state (enum 3.2),PS_PUBLISHED,FC03,14,Signed 16-bit,Read,,value,1.0,9,%QW14,PU-302,
|
|
AID.WRPS.PU303.STATE,WRPS_PLC,PU303_STATE,Pump state (enum 3.2),PS_PUBLISHED,FC03,15,Signed 16-bit,Read,,value,1.0,9,%QW15,PU-303,
|
|
AID.WRPS.STN.DUTY_PUMP,WRPS_PLC,STN_DUTY_PUMP,"Current duty pump (0 = none, 1-3)",PS_PUBLISHED,FC03,16,Signed 16-bit,Read,,value,1.0,9,%QW16,STN,
|
|
AID.WRPS.STN.ALARM_WORD,WRPS_PLC,STN_ALARM_WORD,Alarm bitmask (section 6) - READ AS UNSIGNED,PS_PUBLISHED,FC03,17,Unsigned 16-bit,Read,,value,1.0,99999,%QW17,STN,
|
|
AID.WRPS.STN.CMD_ACK,WRPS_PLC,STN_CMD_ACK,Command acknowledge (echoes %MW1),PS_PUBLISHED,FC03,20,Signed 16-bit,Read,,value,1.0,99,%QW20,STN,
|
|
AID.WRPS.SP.MODE,WRPS_PLC,SP_MODE,"Station mode: 1 = auto, 2 = off",PS_SETPOINTS,FC03/FC06,1024,Signed 16-bit,Read/Write,,value,1.0,9,%MW0,STN,
|
|
AID.WRPS.SP.CMD_WORD,WRPS_PLC,SP_CMD_WORD,Command word (section 3.3),PS_SETPOINTS,FC03/FC06,1025,Signed 16-bit,Read/Write,,value,1.0,99,%MW1,STN,
|
|
AID.WRPS.SP.CMD_PARAM,WRPS_PLC,SP_CMD_PARAM,Command parameter (pump number),PS_SETPOINTS,FC03/FC06,1026,Signed 16-bit,Read/Write,,value,1.0,9,%MW2,STN,
|
|
AID.WRPS.SP.LEVEL_SP,WRPS_PLC,SP_LEVEL_SP,Level control setpoint,PS_SETPOINTS,FC03/FC06,1027,Signed 16-bit,Read/Write,%,value / 60,0.016666666666666666,999.9,%MW3,STN,
|
|
AID.WRPS.SP.START_DUTY,WRPS_PLC,SP_START_DUTY,Start duty level,PS_SETPOINTS,FC03/FC06,1028,Signed 16-bit,Read/Write,%,value / 60,0.016666666666666666,999.9,%MW4,STN,
|
|
AID.WRPS.SP.START_P2,WRPS_PLC,SP_START_P2,Start pump 2 level,PS_SETPOINTS,FC03/FC06,1029,Signed 16-bit,Read/Write,%,value / 60,0.016666666666666666,999.9,%MW5,STN,
|
|
AID.WRPS.SP.START_P3,WRPS_PLC,SP_START_P3,Start pump 3 level,PS_SETPOINTS,FC03/FC06,1030,Signed 16-bit,Read/Write,%,value / 60,0.016666666666666666,999.9,%MW6,STN,
|
|
AID.WRPS.SP.STOP_ALL,WRPS_PLC,SP_STOP_ALL,Stop all level,PS_SETPOINTS,FC03/FC06,1031,Signed 16-bit,Read/Write,%,value / 60,0.016666666666666666,999.9,%MW7,STN,
|
|
AID.WRPS.SP.HIGH_ALARM,WRPS_PLC,SP_HIGH_ALARM,High level alarm,PS_SETPOINTS,FC03/FC06,1032,Signed 16-bit,Read/Write,%,value / 60,0.016666666666666666,999.9,%MW8,STN,
|
|
AID.WRPS.SP.MIN_SPEED,WRPS_PLC,SP_MIN_SPEED,Minimum drive speed,PS_SETPOINTS,FC03/FC06,1033,Signed 16-bit,Read/Write,%,value * 0.2,0.2,999.9,%MW9,STN,
|
|
AID.WRPS.SP.SERVICE_HRS,WRPS_PLC,SP_SERVICE_HRS,Service interval,PS_SETPOINTS,FC03/FC06,1034,Signed 16-bit,Read/Write,h,value,1.0,99999,%MW10,STN,
|
|
AID.WRPS.SIM.INFLOW,WRPS_PLC,SIM_INFLOW,manual inflow (mode 0),PS_SIM_CONTROL,FC03/FC06,1044,Signed 16-bit,Read/Write,m3/h,value * 0.36,0.36,9999.9,%MW20,SIM,SIMULATION CONTROL - simulation build only
|
|
AID.WRPS.SIM.SCENARIO,WRPS_PLC,SIM_SCENARIO,scenario 0=man 1=diurnal 2=wet 3=ref,PS_SIM_CONTROL,FC03/FC06,1045,Signed 16-bit,Read/Write,,value,1.0,9,%MW21,SIM,SIMULATION CONTROL - simulation build only
|
|
AID.WRPS.SIM.RESET,WRPS_PLC,SIM_RESET,"write 1 to reset scenario, self-clearing",PS_SIM_CONTROL,FC03/FC06,1046,Signed 16-bit,Read/Write,,value,1.0,9,%MW22,SIM,SIMULATION CONTROL - simulation build only
|
|
AID.WRPS.SIM.TIME_SCALE,WRPS_PLC,SIM_TIME_SCALE,time scale 1-120,PS_SIM_CONTROL,FC03/FC06,1047,Signed 16-bit,Read/Write,x,value,1.0,999,%MW23,SIM,SIMULATION CONTROL - simulation build only
|