The query window is a rolling seven days by design, and stays that way against the real SQL historian - it is not parsed out of the question. Two things I wrote assumed otherwise. H29 was wrong in two ways. It demanded the words "retention" and "seven days", and it BANNED "no records found" - which contradicts CLAUDE.md, where that is the required wording for zero rows. With a fixed one-week window June genuinely has zero rows in what was queried, so the phrase is correct rather than evasive. It also described the missing piece as question-window parsing, which is not a gap but the design. Rewritten to pin the risk that actually exists: SUBSTITUTION. A question naming June must never be answered with this week's figure wearing June's label. Answering "there were 14" would be exactly that, and nothing downstream could catch it. The observed answer refuses the substitution and states the window it used, so the case now passes on its merits rather than being red by default. must_not is the only half run_eval enforces, so the banned phrases are ones that appear only on a substitution. outside_retention is reframed as what it is: a GUARD, always false while every caller asks for seven days, there so a caller who later passes a longer window cannot get an empty result that reads as "nothing happened". REQUESTS.md and the removal guide now say that extending retention on its own is inert - the window would still ask for a week of a longer history. Both halves are needed, or neither. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
13 KiB
The stand-in historian — what it is, and how to remove it
imh (yau-sls-poc-imh) does not exist yet. Everything the assistant says about
plant history today comes from generated data in the fixture schema, built by
002_fixtures.sql.
This file exists so that removing it later is a checklist rather than an
archaeology exercise. Read it before connecting imh, not after.
Important
The real historian will not be identical to this. The stand-in was built from the SCADA configuration in
WRPS/05-scada/modbus, so the item names, sample rates, retention and timestamp semantics are taken from the machine rather than invented. Everything about the SQL Server side — table names, column names, column types, how a value is stored, how quality is expressed — is a guess. Section 4 lists every one of those guesses with a way to test it. Work through that table against the real thing before you trust a single number.
1. Why there is a stand-in at all
Phase 4 (imh access) is the only true blocker in the build. Cube, the
contracts, the agent and the UI can all be built and tested without it. The
stand-in exists so that work is not idle, and so that the shape of the data
contract is settled and reviewed before the real connection lands.
It is switched on by USE_FIXTURES=true in ~/ai/api.env.
Every row carries is_fixture = TRUE, and the flag rides all the way to a
banner on the operator's screen. Do not remove that flag as tidying-up.
2. The seam — where fixture ends and contract begins
This is the single most important thing in this document.
FIXTURE SCAFFOLDING (delete at cutover)
┌──────────────────────────────────────────────────────────────┐
│ fixture.build_meta the build clock │
│ fixture.f_peak / f_level / f_pumps / f_inflow / │
│ fixture.f_discharge / f_duty / f_alarm_word │
│ fixture.injected_condition the scripted trips and faults │
│ fixture.item_history the generated samples │
└──────────────────────────────────────────────────────────────┘
│
════════════════════╪═══════════ THE SEAM ═══════════
│
┌──────────────────────────────────────────────────────────────┐
│ fixture.process_value_history VIEW │
│ fixture.alarm_history VIEW │
│ fixture.operation_history MATERIALIZED VIEW │
└──────────────────────────────────────────────────────────────┘
CONTRACT (repoint, do not delete)
│
Cube models read only these
Above the seam is generation. Below it is contract. The three views are the only things any Cube model names. Cutover means giving those three views a new source; it does not mean touching a Cube model, and if you find yourself editing one, stop and ask why the view could not absorb the difference.
public.historian_items, public.alarm_bits, public.tags and
public.equipment are reference data, not fixtures. They live in public,
they are loaded by deploy.sh regardless of USE_FIXTURES, and they survive
cutover unchanged. That placement is deliberate: the item-to-tag mapping and
the alarm bit map are properties of the SCADA and PLC configuration, not of the
stand-in.
3. Inventory
Delete at cutover
| Object | What it is |
|---|---|
fixture.build_meta |
Origin and horizon of the generated window |
fixture.f_peak, f_level, f_pumps, f_inflow, f_discharge, f_duty, f_alarm_word |
The prescribed plant |
fixture.injected_condition |
Scripted trips, seal leak, vibration, frozen transmitter, rejected setpoint |
fixture.item_history |
~685,000 generated samples |
The DO $$ … $$ assertion block at the foot of 002_fixtures.sql |
Asserts counts that are facts about generated data only |
Repoint, do not delete
| Object | Becomes |
|---|---|
fixture.process_value_history |
A view over the real imh analogue history |
fixture.alarm_history |
The same bit-decomposition, over the real alarm word — or a view over CI Server's ALARM_HISTORY if anyone ever configures item alarm limits |
fixture.operation_history |
The same derivation from PUMPS_RUNNING, over real data |
Consider renaming the schema from fixture to something honest (historian)
at that point, and updating sql_table: in the four Cube models. That is a
rename, not a redesign — do it in its own commit.
Keep unchanged
public.historian_items, public.alarm_bits, public.tags,
public.equipment, scripts/gen_historian_items.py, db/seed/*.csv, and all
four Cube model files.
4. Assumptions that may not hold — test every one
The shape below was reasoned from the SCADA configuration. The SQL Server side was not available and none of it is confirmed.
| # | Assumption | Where it is encoded | How to test it | If it is wrong |
|---|---|---|---|---|
| A1 | imh exposes one item-keyed history table |
fixture.item_history shape; all three views |
List the tables. Look for one row per (item, time, value) | If history is split per group or per data type, the three views absorb it with a UNION ALL. No Cube change |
| A2 | Item names appear verbatim as AID.WRPS.STN.LEVEL |
Join history.item_name = historian_items.item_name |
SELECT DISTINCT the name column and compare against db/seed/historian_items.csv |
Case, separators (. vs \), a node prefix, or a numeric item id with a lookup table. Normalise in the view, never by editing the seed |
| A3 | Timestamps are UTC | Every view; alarms.yml converts once |
Confirmed from config (TIME_ZONE "Date+time GMT", CORRECT_DAYLIGHT=0) but verify against data: take a known event and check it against wall-clock |
SQL Server has no timestamptz. A datetime2 holding UTC must be cast with AT TIME ZONE 'UTC' in the view, or every answer shifts by ten hours |
| A4 | Values are in engineering units, gain already applied | All measures; 86.7 and 91.7 thresholds in process_values.yml |
Read AID.WRPS.STN.LEVEL and check it is ~0–100, not ~0–7000 |
If raw registers, apply historian_items.eng_gain in the view. The thresholds in the Cube model assume percent |
| A5 | Quality is text GOOD / BAD / UNCERTAIN |
Every measure filters quality = 'GOOD' |
Inspect the column | CI Server may use numeric OPC quality codes. Map to the three strings in the view. A missing quality column is not "all good" — decide explicitly and write down which |
| A6 | The alarm word is retained as an item we can decompose | fixture.alarm_history |
Check AID.WRPS.STN.ALARM_WORD has history |
If it is not retained, derive alarms from the discrete items instead (STN.HIGH_LEVEL, PU30x.TRIPPED, …). public.alarm_bits.tag_id already names them |
| A7 | Sampling is regular at the declared interval | time_weighted_avg, seconds_above_* sum scan_interval_seconds |
Compare consecutive sample_time gaps against historian_items.scan_interval_seconds. This is on the Phase 4 gate |
If deadband compression is ever enabled, replace scan_interval_seconds with a LEAD window in the view. Every duration measure is wrong until you do |
| A8 | Retention is 7 days | metrics.HISTORY_RETENTION_DAYS; pre-aggregation build ranges |
SELECT min(sample_time) |
Update the constant, and widen build_range_start in all three pre-aggregations. Note the constant is also the query window — every builder asks for a rolling week whatever the question names, and that is by design. Longer retention alone is inert until the window is made variable |
| A9 | There is no operations concept — pump-downs must be derived | fixture.operation_history |
Look for any batch/campaign table | If one exists, prefer it, and re-verify the 5-minute noise threshold and the 10-minute look-back against it |
| A10 | The 32767 sentinel survives into engineering units |
Every measure excludes value <> 32767 |
Check TIME_TO_SPILL for the sentinel |
If a gain is applied to it, the sentinel is no longer 32767 and every average silently includes it. This one fails quietly |
| A11 | The alarm word can be read unsigned | fixture.alarm_history normalises with ((v % 65536) + 65536) % 65536 |
Check whether the word ever goes negative | SQL Server SMALLINT is signed, so bit 15 makes the whole word negative and a right-shift sign-extends — reporting every higher bit as active at once. The normalisation already handles it; do not remove it |
| A12 | One row per item per timestamp (the view's primary key) | process_values.id = item_name || '@' || sample_time |
Check for duplicates | Duplicate timestamps break Cube's primary key. Deduplicate in the view and find out why they exist |
A10 and A5 are the two that fail silently. A wrong sentinel or a misinterpreted quality code does not raise an error; it produces a plausible number. Test those two with data, not by reading a schema.
5. Removal procedure
-
Do not delete anything yet. Stand the real source up beside the fixtures and work through section 4 with real data. Write the answers into
BUILD-AI-CONTAINERS.md§10. -
Rewrite the three views against
imh, absorbing every difference found in step 1. The views change; the Cube models must not. -
Re-verify the Phase 5 gate by hand, without the LLM. Prove Cube returns the right number by querying it directly and checking against
imhwith your own SQL. The Phase 5 gate exists for exactly this moment. -
Re-derive the pinned eval expectations.
eval/testset.jsonlcaseH31pins a high level alarm count of 14. That is a fact about generated data and nothing else. Replace it with a real figure an engineer has verified, or remove the pin. -
Set
USE_FIXTURES=falseand repointCUBEJS_DB_*atimh. -
Drop the scaffolding listed in section 3, and delete the assertion block from
002_fixtures.sql. -
Run
scripts/verify.sh. The historian-item-mapping and no-equipment- column checks are not fixture-specific and must still pass. The fixture banner should disappear. -
Check the fixture banner is actually gone from an answer on the operator screen, not just from the database. It is driven by
used_fixture_dataoffUSE_FIXTURES, so it should follow — confirm it rather than assume it.
6. What the assertions do and do not prove
002_fixtures.sql ends with a block that fails the load on any of:
- 685,440 analogue rows; 32 alarm activations; 14 high level; 2 spills; 15 priority-1; 72 pump-downs; 720 BAD level samples
- every historised, answerable item having history
- alarm-word bit 0 agreeing with the independent discrete item
AID.WRPS.STN.HIGH_LEVEL, and bit 3 withAID.WRPS.STN.SPILL_ACTIVE - the operations derivation and the alarm derivation agreeing on spill count
- volume-remaining-to-spill reconciling with level through the plant geometry at every sample
Those are real tests of the derivation logic, and the cross-checks in
particular compare two independent paths through the data. They are worth
keeping in mind when rewriting the views, because the same cross-checks can be
run against imh and should still hold.
They prove nothing about the plant. Every number above is a fact about
generated data. The moment imh is connected they are meaningless, and step 6
deletes them.
7. History, so this is not relearned
The stand-in was rebuilt on 2026-08-31. The version before it was keyed on CI
Server point names (PS_STN_WET_WELL_LEVEL) when the historian is keyed on
CI Server item names (AID.WRPS.STN.LEVEL) — two layers apart. That single
substitution produced all three open Phase 5 findings, and each looked like an
independent bug: a tag that would not join, alarm times in the wrong timezone,
an alarm filed against the wrong equipment.
The lesson worth carrying into cutover: a stand-in that is shaped wrongly is
worse than no stand-in, because it produces confident answers and the defects
present as unrelated. When something here disagrees with imh, the first
question is not "which value is right" but "are these two things even the same
thing".