Phase 7: BUS Service, Data Access (OPC UA/DA/A&E, ODBC), OPC Interface, Exchange tools #7
Loading…
Add table
Reference in a new issue
No description provided.
Delete branch "docs/phase-7-interfaces"
Deleting a branch is permanent. Although the deleted branch may continue to exist for a short time before it actually gets removed, it CANNOT be undone in most cases. Continue?
Summary
data-access:opcua-client.md(OPC UA client by quick load, certificate exchange, CI Server node IDs, browse viaOPCUAC_TAG_DF) andaccess-checks.md(processes, ports, OPC UA server config/PKI, ODBC server).system-management: new taskbus-utilities.md(durwfp, durstp, message tools, adaptive queues).system-check: how to see the unlicensed run time left.CIENG_UA(own client -> own server, localhost:34493), OPC visible flags forTANK1.LEVEL, itemsUA.COMM_OK,UA.LEVEL_COPY,UA.SRV_STATE; load/remove scripts and README updated.odbsrvcannot load its SSL certificate). New issues ISS-030 to ISS-034.Test plan (CI Server R1.03.00 test system, 2026-10-01)
UA.COMM_OK= 1,UA.SRV_STATE= 0,UA.LEVEL_COPYfollowsTANK1.LEVEL(55, 62.5, 71, 33, 44.4)urn:Yokogawa:CI_SERVER_OPC_UA_SERVERfound by browsing;itnmandnsidvalue node IDs both workremove.cmd/load.cmdcycle: all datasets 0 errors; station reconnects without a new certificate exchangedurwfpexit codes; BUS setup files read🤖 Generated with Claude Code