manual: IM 36K10E20-01EN
|
||||||
|
title: OPC Interface
|
||||||
|
edition: 2nd Edition, Sep. 2023
|
||||||
|
version: R1.03
|
||||||
|
status: from docs; OPC UA point and certificate forms compared with quick load on the test system 2026-10-01 (user configured a point in the Engineering Module, exported and diffed)
|
||||||
|
---
|
||||||
|
|
||||||
|
# OPC Interface (R1.03)
|
||||||
|
|
||||||
|
Engineering Module procedures for OPC Classic, OPC UA client and OPC UA PubSub. Concepts,
|
||||||
|
setup files and the OPC servers: `IM36K10L45-01EN.md`. Everything here is under
|
||||||
|
*Configuration → I/O processing → Equipment → (OPC DA client | OPC A&E client | OPC UA Client |
|
||||||
|
OPC UA PubSub)*. CI Server must be running. Section numbers refer to the manual.
|
||||||
|
|
||||||
|
## 1. OPC Classic (§1)
|
||||||
|
|
||||||
|
- DA: line (equipment node, process name — the manual says it must start with `OPC` for DA and
|
||||||
|
A&E lines, `OPX` for OPC UA), station (OPC server node and ProgID, status item), group
|
||||||
|
(deadband, requested update rate, status item), point (external relation, group, OPC tag,
|
||||||
|
browse). Then connect items to points (Tutorial "Define points").
|
||||||
|
- A&E: line, station (server, subscription filters), subscribed attributes; to show events in
|
||||||
|
the current alarm overview, map event sources to items. External names must be unique per
|
||||||
|
station.
|
||||||
|
|
||||||
|
## 2. OPC UA client (§2)
|
||||||
|
|
||||||
|
Order: line → station → subscription → points (→ methods) → alarm components / event type
|
||||||
|
filters / event nodes / template settings (only when alarms are wanted; no alarms are received
|
||||||
|
until event nodes are configured).
|
||||||
|
|
||||||
|
| Object | Key fields (dataset field) |
|
||||||
|
|---|---|
|
||||||
|
| Line | name ≤ 31, equipment node (*None* = this node), **process name starts with `OPX`, ≤ 11 characters** (`EQUIPMENT_MAN`) |
|
||||||
|
| Station | name ≤ 19; *Host(:port)* + *Discovery* fill session/server name and endpoint, or type the endpoint (`SERVER_01_ENDPOINT`); redundant servers + *Active server item*; *On scan*; *General communication status item* (`STATUS_ITEM`); security policy and mode; anonymous or user/password; requested session time-out; alarm tab (request active alarms, store all alarms as SOE, severity → priority mapping) |
|
||||||
|
| Subscription | publishing interval, lifetime and keep-alive counts, max notifications, priority, publish enabled, status item |
|
||||||
|
| Point | external relation Input / Output / Input + Output; subscription; *Namespace*, *Node id type*, *Node Id* (or *Browse path*); read-only *Last value*, *Data type*, *Access level*, *Value rank*; array element; options (own sampling interval, monitoring mode, queue size); conversion (offset, step) |
|
||||||
|
| Method | namespace, node ID or browse path, process areas |
|
||||||
|
|
||||||
|
**Observed (2026-10-01)**: browsing in the point form stops at the item itself
|
||||||
|
(`Objects/<section>/…/<item>`) and stores the item **object** (`{"nsid":"<n>"}`), which has no
|
||||||
|
value: *Last value*/*Data type* stay empty and the point is never monitored (revised sampling
|
||||||
|
interval 0, item status 13). Type the node ID of the value instead:
|
||||||
|
`{"0":"Value","itnm":"<item>"}` (namespace `urn:Yokogawa:CI_SERVER_OPC_UA_SERVER`, type
|
||||||
|
STRING). The form also fills `OPC_DISPLAY_NAME` and `OPC_TAG_INFO` (browse bookkeeping;
|
||||||
|
not needed for quick load). ISS-033.
|
||||||
|
|
||||||
|
## 3. Certificates (§2.2)
|
||||||
|
|
||||||
|
*OPC UA Client → Certificates*: **Trusted**, **Rejected** (server certificates arrive here),
|
||||||
|
**Own certificate**. Trust = open the rejected certificate, tick *Trusted*, Apply; reject =
|
||||||
|
untick. Restart the Engineering Module to refresh the folders. *Modify* the own certificate
|
||||||
|
(name, organisation, country, domain or IP, RSA key strength, signature algorithm, validity).
|
||||||
|
|
||||||
|
**CI Server OPC UA client ↔ CI Server OPC UA server (§2.2.6)**: trust the server certificate
|
||||||
|
on the client; copy the client's own certificate
|
||||||
|
(`%TLS_ALLUSERS_PATH%\pki\opxuac\pkiclient\own\certs`) to the server's
|
||||||
|
`…\pki\opxuas\pkiserver\trusted\certs`; the manual also asks to tick *Use CI Server entity names
|
||||||
|
for nodeids* in `opxuas.sup` and restart the server. On the test system the loopback worked
|
||||||
|
**without** that option, using `itnm` node IDs (ISS-032).
|
||||||
|
|
||||||
|
## 4. OPC UA PubSub (§3)
|
||||||
|
|
||||||
|
UDP publish/subscribe of Data Access values from the CI Server OPC UA server address space
|
||||||
|
(OPC visible items). Objects: line (needs its own copy of `ServerConfig.xml` named for the
|
||||||
|
instance), published datasets, station, writer groups + dataset writers (publisher), reader
|
||||||
|
groups + dataset readers (subscriber), then *Upload dataset configurations to runtime*.
|
||||||
|
Limits per line: 4 stations, 8 writer groups, 8 reader groups, 32 dataset writers, 32 dataset
|
||||||
|
readers, 32 published datasets. Status mapping as for the server (NORMAL → Good; NOT_INIT,
|
||||||
|
UPD_OFF, OFFSCAN, OFFLINE → Uncertain; BAD_VALUE → Bad). Not practiced (needs a PubSub peer).
|
||||||
133
knowledge/manuals/IM36K10L30-01EN.md
Normal file
133
knowledge/manuals/IM36K10L30-01EN.md
Normal file
|
|
@ -0,0 +1,133 @@
|
||||||
|
---
|
||||||
|
manual: IM 36K10L30-01EN
|
||||||
|
title: BUS Service Engineering
|
||||||
|
edition: 3rd Edition, Sep. 2023
|
||||||
|
version: R1.03
|
||||||
|
status: from docs; installed tools, setup files (dur.sup, durm_1_udp.sup, time_table.sup, fmfprt.sup, durutl.sup) and durm_start.cmd checked read-only 2026-10-01; durwfp verified; umhman, umhtestprog, umhmsg fail on the test system (ISS-030)
|
||||||
|
---
|
||||||
|
|
||||||
|
# BUS Service Engineering (R1.03)
|
||||||
|
|
||||||
|
BUS Service is CI Server's messaging layer ("DUR", Dynamic User Region): every CI Server
|
||||||
|
process attaches to a shared memory area and gets a **queue** (mailbox) under its DUR name;
|
||||||
|
processes talk by messages. It also does error-text management (UMH), node-to-node links
|
||||||
|
(MDUR), time handling, printer management and process control utilities. Section numbers refer
|
||||||
|
to the manual.
|
||||||
|
|
||||||
|
## 1. Processes (§1.2)
|
||||||
|
|
||||||
|
| Process | Role |
|
||||||
|
|---|---|
|
||||||
|
| `durini` | Initialises DUR at start, then exits |
|
||||||
|
| `durtim` | Runs every second: system time, summer/winter time, queue time-outs, checks that processes still exist (`DUR-W-REM_PROC, Process <x> exited unexpectedly`), clock queue |
|
||||||
|
| `durprt` | Writes intercepted messages to `tls\lst\DURPRT.out` (debugging; leave running) |
|
||||||
|
| `umh` / `umhlog` | Build error texts from codes (`tls\dat\messages.umh`) and write them to the message log (`umhlog.log`) |
|
||||||
|
| Optional | `dur` (DUR display utility, interactive), `durbat` (start processes on request, also remote), `durclq` (finer clock-queue resolution: `durclq 50` = 50 ms), `durdbg`, `durutl` (logical addresses, node time sync), `durecs` (external clock), `dursim`, `durstp`, `durwfp`, `umhcr`, `umhlogtoo`, `umhman`, `umhmsg` |
|
||||||
|
|
||||||
|
Process names: fixed (e.g. `UMH`), `PID<n>` when none given, or set with `-n <name>` (most
|
||||||
|
CI Server executables, e.g. `opxuas -n opxuas`).
|
||||||
|
|
||||||
|
## 2. Messages and nodes (§2–§4)
|
||||||
|
|
||||||
|
- Requests are asynchronous; CI Server makes them synchronous with a *reply required* flag. The
|
||||||
|
**server** converts data between different computer architectures.
|
||||||
|
- **MDUR** (§3): one `durm_<line>` process pair per network line (`durm_udp` + `durm_udp_slv`
|
||||||
|
on Windows), started by `tls\com\durm_start.cmd`, configured in
|
||||||
|
`tls\sup\durm_<line>_udp.sup`: `line`, `quality` (lower = preferred line), `io_timeout`
|
||||||
|
(default 8000 ms, 8 checks), `portnr` (same on all nodes of one line; > 17000 advised),
|
||||||
|
`max_snd`, `cluster`, `compress`, `connect_delay`, `max_poll_int`, `our_host_name`,
|
||||||
|
`remote_set` (up to four nodes sharing one node number = redundant set). Redundant nodes
|
||||||
|
only over TCP/IP. `durmdbg -q <durm> -f <file>` traces a line; always stop with `-s`.
|
||||||
|
- `dur.sup`: node number, `host_node`, `rout_type` (ENDPOINT or ROUTER for multi-node
|
||||||
|
routing), sizes (`pool_kbytes`, `dur_max_proc`).
|
||||||
|
- **Logical addresses** (§4): node −1 in an address = look up a table (`durlnm.dat`), distributed
|
||||||
|
by `durutl` from a master node listed with `lnm_node = …` in `durutl.sup`.
|
||||||
|
|
||||||
|
**Installed (single node)**: `dur.sup` `host_node 0`, `pool_kbytes 250000`, `dur_max_proc 250`,
|
||||||
|
`rout_type 2 ENDPOINT`; `durm_1_udp.sup` `line 1`, `quality 500`, `io_timeout 8000`,
|
||||||
|
`portnr 17001`, plus keywords not in the manual: `sndportnr 17101`, `ip_adr_method IPv4`,
|
||||||
|
`ENABLE_DURMS N, 0` (host-host encryption, §13); `durm_1` is running although there is no
|
||||||
|
second node; `durutl.sup` has no active lines.
|
||||||
|
|
||||||
|
## 3. Messages and the message log (§5, §6)
|
||||||
|
|
||||||
|
- Codes look like `FAC-S-ACRONYM` (S = S/I/W/E/F). Text comes from `messages.umh`; dynamic
|
||||||
|
values are inserted by name; several codes can form one history entry.
|
||||||
|
- `umhlog` writes to `tls\log\umhlog.log`; `-d <node>` also logs centrally on another node,
|
||||||
|
`-q <printer queue>` prints too.
|
||||||
|
- Tools: `umhtestprog` (tests the message path), `umhmsg <hex code> [<var> <value>]…`
|
||||||
|
(issue a message from a script), `umhman` (look up a hex code, interactive),
|
||||||
|
`umhlogtoo` (copy of all messages to a terminal). **On the test system** `umhman` crashes
|
||||||
|
with redirected input, `umhtestprog` crashes, and `umhmsg` ends with "license expired"
|
||||||
|
(ISS-030).
|
||||||
|
- A message shown as `UMH Message Text Error: Message number <hex> (…)` means the text could
|
||||||
|
not be formatted (e.g. a `%` in a PRINT text, ISS-025).
|
||||||
|
|
||||||
|
## 4. Time (§7, §8, §11)
|
||||||
|
|
||||||
|
- `time_table.sup`: `AUTOMATIC` (installed) = BUS Service takes summer/winter times from
|
||||||
|
Windows at start (scans ±15 years); otherwise `LST_OFFSET` (minutes, **positive = west**),
|
||||||
|
`LST_NAME`, `LCT_NAME`, `CHANGE` lines; month/day abbreviations. Reload via the DUR display
|
||||||
|
utility. Installed file still has the Central European example values (−60, MET/MEST); they
|
||||||
|
are ignored while `AUTOMATIC` is set.
|
||||||
|
- Node time sync with `durutl` on the master: `tms_params = <interval s>, <limit1>, <limit2>,
|
||||||
|
<limit3>, <step2>, <step3>` and one `tms_node = <n>` per slave; beyond limit3 the slave is
|
||||||
|
set at once and an error is logged. External clock (serial Wharton/Trimble/Arbiter) with
|
||||||
|
`durecs` and `durecs.sup` (`ecs_params`). On Windows normally use Windows time
|
||||||
|
(`system-check`, `w32tm`).
|
||||||
|
|
||||||
|
## 5. Process control utilities (§10)
|
||||||
|
|
||||||
|
| Command | Use |
|
||||||
|
|---|---|
|
||||||
|
| `durwfp -p <name> [-t <s>] [-e]` | Exit 0 if the process is attached (waits up to `-t`, default 60; `-t 0` = check now); `-e` waits for it to go away. Verified: `umh`, `opcman` → 0, unknown name → 1 |
|
||||||
|
| `durstp -m -p <name>` | Send a stop message (clean stop). `-k` kills, `-m -k` = stop, then kill after `-t` s; `-f` kills even with the common area locked (dangerous); `*` wildcard (`-p alm\*`). Never `durstp -k -p \*` |
|
||||||
|
| `durbat` | Starts processes on request from other processes (also remote) |
|
||||||
|
|
||||||
|
`durstp` stops CI Server processes: use only with the user's approval.
|
||||||
|
|
||||||
|
## 6. Printer management (§12)
|
||||||
|
|
||||||
|
`FMFPRT` (printer manager, one per node) and one `FMFP_<device>` process per device (first 8
|
||||||
|
characters of the device name must be unique). **Destinations** (logical, e.g.
|
||||||
|
`SCREEN_CAPTURE`, `ALARMS`, `MESSAGES`, `DEFAULT`) map to **devices** (instances of an output
|
||||||
|
type) with an optional backup device. Configured in `fmfprt.sup`; devices and destinations in
|
||||||
|
datasets `PRINTER_DEV_DF`, `PRINTER_DEST_DF`, `PRINTER_TYPE_DF`, `PRINTER_OPER_DEST_DF`
|
||||||
|
(job/device lists `PRINTER_JOB_OVV`, `PRINTER_DEV_OVV`).
|
||||||
|
|
||||||
|
**Installed `fmfprt.sup`**: `QUEUE_LIFE 1800` s (stalled job expires), `MAX_JOBS_SHOWN 10`,
|
||||||
|
`DEVICE_POLL 5` s, `MAX_BUSY 60` polls; output types `HARDCOPY` (`fmfphc`, Windows printing,
|
||||||
|
Courier New 8 pt, 72 lines, landscape), `FILE` (`fmfpfl`, file name
|
||||||
|
`TLS_%time:DDMMYY%_%seq:03%.lst` in `tls\lst`), `APPLICATION` (`fmfpap`, program set to
|
||||||
|
Internet Explorer); fixed destinations `ALARMS`→`ALDPRT`, `AUDIT_TRAIL`→`ADTLOG`,
|
||||||
|
`MESSAGES`→`UMHLOG`, `PRINTER_1`→`RPTMAN`, `SCREEN_CAPTURE`→`CWSSHOT`. `NODE_SHARE = <node|-1>`
|
||||||
|
shares printers between nodes. Logging processes do not print by default (enable per process:
|
||||||
|
`aldprt.sup LOGPRT`, `adtsys.sup PRT_DEV`, `umhlog -q`).
|
||||||
|
|
||||||
|
The CI Service account must have the printers; `DEFAULT` uses that account's default printer.
|
||||||
|
Clean-up after a crash: stop CI Server, empty `tls\lst\printing`, delete
|
||||||
|
`tls\sav\fmf_prt_last_id.sav`, `fmfprt.sav` and `tls\dat\printer_job_ovv.*`, start.
|
||||||
|
|
||||||
|
## 7. MDUR encryption (§13)
|
||||||
|
|
||||||
|
Host-host encryption (AES-256, certificates) between CI Cores: every node must use it; no
|
||||||
|
enterprise configurations. Keys: `gen_key is_ca=1` once (CA key), `gen_key is_ca=0` on each
|
||||||
|
node → `%TLS_ALLUSERS_PATH%\pki\mel\dur\key`; certificates with the interactive `cert_write`
|
||||||
|
(CA certificate to `…\pki\mel\dur\crt\ca\ca.crt` on every node, node certificate to
|
||||||
|
`…\crt\own`; create the folders first; log `tls\log\cert_write_log.log`). Then tick *Enable
|
||||||
|
HostHost encryption* in each `durm_x_udp.sup` (installed keyword `ENABLE_DURMS`). Keep the CA
|
||||||
|
key off the servers. Not practiced (single node; `tls\pki\mel` does not exist yet).
|
||||||
|
|
||||||
|
## 8. Adaptive queues (§14)
|
||||||
|
|
||||||
|
Each process has a fixed queue (the *adaptive minimum*); for processes listed on the
|
||||||
|
*Adaptive queues* tab of `dur.sup` (`ADAPTIVE_QUEUE_SETS = <process>, <percent>`), DUR may
|
||||||
|
grow the queue temporarily by up to that percentage of the total queue area, avoiding overflows
|
||||||
|
during bursts. Add node queues for multi-node systems and new processes (extra executors,
|
||||||
|
DSS servers, equipment managers). In the performance monitor *Minimum KB*/*Maximum KB*/*Current
|
||||||
|
KB* and a high-queue of 100 % show that a queue needed more space → raise its size. Total area
|
||||||
|
exhausted → `DUR_F_NO_SPACE`.
|
||||||
|
|
||||||
|
**Installed**: `ALM` 10, `ALH` 10, `WFLGDI` 20, `WFLCDI`/`WFLIDI`/`WFLADI`/`ITHEIX`/`ITHSER` 2,
|
||||||
|
`DSSSDA*`/`DSSEVT*`/`OPCEXE` 1 %. Note: `OPCEXE` does not match the installed executor names
|
||||||
|
`OPCEXE1`…`4` (no wildcard) — see ISS-026.
|
||||||
182
knowledge/manuals/IM36K10L45-01EN.md
Normal file
182
knowledge/manuals/IM36K10L45-01EN.md
Normal file
|
|
@ -0,0 +1,182 @@
|
||||||
|
---
|
||||||
|
manual: IM 36K10L45-01EN
|
||||||
|
title: Data Access Engineering
|
||||||
|
edition: 3rd Edition, Sep. 2023
|
||||||
|
version: R1.03
|
||||||
|
status: from docs; installed setup files (odbsrv.sup, opxsys.sup, opxuas.sup, ServerConfig.xml), access_start.cmd, PKI folders, processes and ports checked 2026-10-01; OPC UA client → own OPC UA server loopback verified with CI-Eng-Sample (station CIENG_UA); ODBC not working on the test system (ISS-008); OPC DA/A&E from docs
|
||||||
|
---
|
||||||
|
|
||||||
|
# Data Access Engineering (R1.03)
|
||||||
|
|
||||||
|
ACCESS Service connects CI Server data to other software: **ODBC** (SQL on datasets), **OPC
|
||||||
|
Classic** (DA and A&E, client and server, DCOM) and **OPC UA** (client and server). Section
|
||||||
|
numbers refer to the manual. Engineering Module forms: `IM36K10E20-01EN.md`. Hands-on:
|
||||||
|
skill `data-access`.
|
||||||
|
|
||||||
|
## 1. ODBC (§1–§3)
|
||||||
|
|
||||||
|
- Multi-tier: ODBC application + driver manager + **SimbaClient** driver on the client;
|
||||||
|
**SimbaServer** + ACCESS Service ODBC engine (`odbsrv`) on the CI Server. Read and write of
|
||||||
|
existing dataset records with SQL (API level Core, SQL level minimum); datasets cannot be
|
||||||
|
created or deleted over ODBC. Needs an ODBC licence.
|
||||||
|
- `odbsrv.sup`: `PORT` (1583), `USESSL` (default on; certificate
|
||||||
|
`%TLS_ROOT_PATH%\tls\pki\odbsrv\SampleServerCertificate.pem`, key `SampleServerKey.pem`),
|
||||||
|
`REMOVE_PADDING_SPACES`, trace (`TRACE`, `VERBOSE`, `TRACE_FILE`), hidden data
|
||||||
|
(`TABLE_SUPPRESSION`, `FIELD_SUPPRESSION`, `FIELD_CONCEAL`, all on).
|
||||||
|
- Client: install the VC++ 2019 redistributable and `SimbaClientDriverxx.zip` from the medium
|
||||||
|
(`install.bat` as administrator); define a DSN with driver `CiSimbaClientDriver` (64-bit) or
|
||||||
|
`CiSimbaClientDriver32`, server IP and port 1583. Before R1.03, uninstall the old Simba parts.
|
||||||
|
- SQL wildcards `%`/`_` vs. MS Office `*`/`?`: escape `_` and `%` in names with `\`.
|
||||||
|
- Common errors (§2.3): IM003 driver missing; IM002 DSN unknown; 08S01 SimbaServer not
|
||||||
|
running / port mismatch / BUS Service not reachable.
|
||||||
|
|
||||||
|
**Installed (test system)**: `odbsrv.sup` `PORT 1583`, `USESSL YES`, but the folder
|
||||||
|
`%TLS_ROOT_PATH%\tls\pki\odbsrv` does not exist and no sample certificate is shipped, so
|
||||||
|
`odbsrv` stops at every start (`CppServerAPI::Run() failed: InitializeSslCtx():
|
||||||
|
SSL_CTX_use_certificate_chain_file() failed`, then `DUR-W-REM_PROC, Process ODBSRV exited
|
||||||
|
unexpectedly`); port 1583 does not listen. Fix: put a certificate and key there, or set
|
||||||
|
`USESSL = NO` (admin; not applied, ISS-008). `access_start.cmd` writes the ODBC registry
|
||||||
|
defaults once (when `%TLS_DAT_PATH%\access.new` exists).
|
||||||
|
|
||||||
|
## 2. OPC Classic basics (§4)
|
||||||
|
|
||||||
|
DCOM-based, Windows only. CI Server has DA client (`opxdac`), DA server (`opxdas12`, DA 1.0A
|
||||||
|
and 2.0, custom + automation interfaces), A&E client (`opxaec`), A&E server (`opxaes`).
|
||||||
|
- Quality: OPC DA quality goes to the **lower** 16 bits of the CI Server quality word, OPC A&E
|
||||||
|
quality to the **upper** 16 bits. Item to OPC: CI Server quality low byte → OPC high byte;
|
||||||
|
OPC low byte = offline → LAST_KNOWN, blocked → LOCAL_OVERRIDE, not initialised →
|
||||||
|
NOT_CONNECTED, else GOOD.
|
||||||
|
- Types: `VT_UI1/UI2/INT/I1/I2/I4` → Integer, `VT_UI4/UINT/R4/R8` → Real, `VT_BSTR` → String,
|
||||||
|
`VT_BOOL` → Boolean.
|
||||||
|
- Items, sections and objects appear to OPC servers (DA, A&E **and UA**) only with *OPC
|
||||||
|
visible* (and every parent section visible).
|
||||||
|
|
||||||
|
## 3. OPC DA client (§5)
|
||||||
|
|
||||||
|
- One client process per DA line (name given in the line), started/stopped with CI Server;
|
||||||
|
stop one with `durstp -msk -t10 -p <client>`. Uses a save file in `%TLS_SAV_PATH%` named
|
||||||
|
after the process; delete it (client stopped) if it gets inconsistent.
|
||||||
|
- Server check every `OPXDAC_SRV_ALIVE` ms (default 30000); station status item: 1 running,
|
||||||
|
2 failed, 3 no config, 4 suspended, 5 test. Not connected → mapped items OFFLINE. Group
|
||||||
|
status item: 1 active / 0 not active (items offline).
|
||||||
|
- Setup (`<client>.sup`, else `opxsys.sup`): `OPXDAC_SAFE_CON` (allow connecting to a CI Server
|
||||||
|
DA server — **never to the own node or a DURM-connected node: deadlock**), `OPXDAC_PING`
|
||||||
|
(ICMP check before DCOM, fast failure), `…_PING_TIMEOUT` (3 s), `…_DUR_QSZ`, `…_HBEAT`
|
||||||
|
(100 ms), `…_ITMBUF`, `…_FLUSH_GRPQUE` (500 ms), `…_BROWSE_CACHE`, `…_DISABLE_BROWSING`,
|
||||||
|
`…_CHECK_MAPPING`, `…_ASYNC_WRITE`, `…_USE_CANONICAL_DATA_TYPE` (default asks VT_R8),
|
||||||
|
`…_IGNORE_BAD_QC_UPDATES`, `…_CLEAR_SAV_FILE`, `…_DISABLE_STATUS_UPDATE`.
|
||||||
|
- Advice: one OPC server per client process (a DCOM time-out blocks the whole process).
|
||||||
|
Quick-load templates: export `LINE_DF`, `STATION_DF`, `OPC_GROUP_DF`, `ITEM_DF`,
|
||||||
|
`POINT_DF` of one station made in the Engineering Module.
|
||||||
|
- **DCOM tunnelling**: run the client on a PC in the OPC server's domain (CI Server with BUS,
|
||||||
|
DATABASE, EQUIPMENT, ACCESS licence) connected to the host by MDUR (`durm_<n>_udp.sup`,
|
||||||
|
port ≥ 20000, `dur.sup` host node = CI Core), *use DCOM tunnelling to host* on the client's
|
||||||
|
setup file; on the host add the line with *Equipment node* = tunneller node. Use `intmon`
|
||||||
|
node monitoring with *Set slave items offline when node unavailable*.
|
||||||
|
|
||||||
|
## 4. OPC DA server (§6)
|
||||||
|
|
||||||
|
- COM server `opxdas12.exe`, ProgID `Yokogawa.CIOpcDas.<version>`, DUR name `OPXDAS`; started by
|
||||||
|
COM on the first client connect; stop with `durstp -p opxdas` (clients get a shutdown).
|
||||||
|
- Namespace = sections/items/sub-items (hierarchical or flat), filters (type, access, VB LIKE
|
||||||
|
pattern). *Cache read* is fast and correct; *device read* blocks — use only after queue
|
||||||
|
overflow. Timestamp = time written into the server cache.
|
||||||
|
- `opxsys.sup` *Data Access Server* tab: `OPXDAS_DUR_QSZ` (100 kB), `…_HBEAT`, `…_ITMBUF`,
|
||||||
|
`OPXDAS_USER` (log on as a CI Server user to apply its authorisation; empty = full access,
|
||||||
|
fastest), `OPXDAS_DCOM_TUN`, `OPXDAS_IGNORE_FTQ`. Installed also: `OPXDAS_SET_LOG_LEVEL`
|
||||||
|
(not described).
|
||||||
|
- Remote access needs DCOM configuration (`dcomcnfg`: authentication Connect, impersonation
|
||||||
|
Identify, access/launch permissions for an OPC account; identity of the server = that account),
|
||||||
|
`secpol` (*Create permanent shared objects*, *Network access: Classic*), firewall rules for
|
||||||
|
`opxdas12.exe`, `opxdac.exe`, `opcenum.exe`, `mmc.exe` and DCOM — not needed where the IT
|
||||||
|
Security Tool is applied. Same account/password on both sides in a workgroup.
|
||||||
|
- Troubleshooting: `OCSRegistryCheck.exe` (GUI; installed), `opxdas12 /RegServer`,
|
||||||
|
`opccommonsetup` / `opcenum /RegServer` / `opcenum /Service` (set the service to automatic),
|
||||||
|
`regsvr32 opcproxy.dll` and `opccomn_ps.dll` in `%WINDIR%\SysWOW64`. Test locally first.
|
||||||
|
|
||||||
|
## 5. OPC A&E client and server (§7, §8)
|
||||||
|
|
||||||
|
- Client `opxaec` (default name `OPXAEC`, `-n` for more), setup `<name>.sup` or `opxsys.sup`
|
||||||
|
(`OPXAEC_SAFE_CON` — same deadlock rule, `…_DUR_QSZ`, `…_SRV_ALIVE`, `…_PING_TIMEOUT`,
|
||||||
|
`…_TRACE`); maps condition events to items; one server per client advised.
|
||||||
|
- Server `opxaes`, ProgID `Yokogawa.CIOpcAes.<version>`, DUR name `OPXAES`; publishes items
|
||||||
|
with alarm monitoring as conditions; `OPXAES_ACK_ALLOWED` (acknowledge from clients),
|
||||||
|
`…_ALM_REC_DELAY` (30 s), `…_BROWSE_PREP_INI`, and `OPXAES_EC_ATTR_*` switches for the
|
||||||
|
CI Server-specific event attributes (old/new value, quality, status, alarm state, item
|
||||||
|
description, units, node, group, number, sub-number). Installed: all on.
|
||||||
|
|
||||||
|
## 6. OPC UA client (§9)
|
||||||
|
|
||||||
|
- OPC UA TCP only; security by X.509 certificates (application authentication), user
|
||||||
|
anonymous or name/password; modes None/Sign/SignAndEncrypt; policies Basic256Sha256,
|
||||||
|
Aes128-Sha256-RsaOaep, Aes256-Sha256-RsaPss recommended (None, Basic128Rsa15, Basic256 not).
|
||||||
|
- Data types supported: Boolean, (S)Byte, (U)Int16/32, Float, Double, String and others as in
|
||||||
|
Table 9.4.2-2; 1-D and 2-D arrays by element. OPC UA status → CI Server quality: 0 good,
|
||||||
|
1 bad, 2 uncertain.
|
||||||
|
- A&C: external alarms from ConditionType and derived types (ALARM/NORMAL events), other
|
||||||
|
events INFORMATIONAL; filters by event type, component, event node; severity → priority
|
||||||
|
table (901–1000 → 1 … 1–100 → 15), per station; don't manage
|
||||||
|
NonExclusiveLimitAlarmType. Only `NodeDeleted` model changes are handled.
|
||||||
|
- Redundancy: no client redundancy (use HAC); servers: transparent, or non-transparent cold
|
||||||
|
backup with two endpoints (*Active server item* 0/1/2).
|
||||||
|
- Engineering objects: line (starts a client process; **name must start with `OPX`**, max 11
|
||||||
|
characters), station (= session), subscription, point (= monitored item), alarm component /
|
||||||
|
event type filter / event node / template settings, method.
|
||||||
|
- Certificates: the client process creates `<host>_<PROCESS>.der` in
|
||||||
|
`%TLS_ALLUSERS_PATH%\pki\opxuac\pkiclient\own\certs` (also listed in dataset
|
||||||
|
`OPCUAC_PKI_CERTIFICATES_DF`); server certificates arrive in `…\pkiclient\rejected` and must be
|
||||||
|
trusted (Engineering Module, or move to `…\pkiclient\trusted\certs`); folders `deleted`,
|
||||||
|
`rejected` added by CI Server. The server must trust the client's certificate too.
|
||||||
|
- Setup (`<process>.sup`, else `opxuac.sup`): `OPXC_DUR_QUEUE_SIZE` (10000 kB), heartbeats,
|
||||||
|
buffers, `OPXC_COM_STAT_CHK_INTERVAL` (10 s), `OPXC_STATION_CON_TRY_INTERVAL` (30 s; observed
|
||||||
|
retries every ~35 s), `OPXC_TIMESTAMP_OPTION` (SERVER/SOURCE), `OPXC_LOG_LEVEL`, service and
|
||||||
|
session time-outs, `OPXC_SERVICE_COMPLIANCE`. Log file `%TLS_LOG_PATH%\<PROCESS>.log`.
|
||||||
|
- Quick load (§9.10–9.11): `OPCUAC_LINE_DF`, `…_STATION_DF`, `…_SUBSCRIPTION_DF`, `…_POINT_DF`
|
||||||
|
(+ alarm and method datasets). Dataset `OPCUAC_TAG_DF` browses a connected server
|
||||||
|
(filter on `OPC_STATION_NAME` and `OPC_TAG_PATH`).
|
||||||
|
- Installed: `opxuac_mon` (a monitor instance) is started by `access_start.cmd`.
|
||||||
|
|
||||||
|
## 7. OPC UA server (§10)
|
||||||
|
|
||||||
|
- Process `OPXUAS` (`opxuas -n opxuas`, started by `access_start.cmd`; stop `durstp -m -p
|
||||||
|
opxuas`), Unified Automation C++ SDK, port **34493**. Log `%TLS_ALLUSERS_PATH%\log\OPXUAS.log`
|
||||||
|
and `OpxUas_Sdk*.log`.
|
||||||
|
- Visible data: sections, objects, items with *OPC visible*; items also need **Read** (read
|
||||||
|
values, browse into the item) and **Write** (write values, alarm methods). Parent sections must
|
||||||
|
be visible. Without Read the item is listed but browsing into it fails
|
||||||
|
(`UncertainNotAllNodesAvailable`).
|
||||||
|
- Users: anonymous = like `OPC_UA_SERVER_READ`; authorisation actions `OPC_UA_SERVER_READ`
|
||||||
|
(browse, read, history) and `OPC_UA_SERVER_MODIFY` (+ write, methods).
|
||||||
|
- Address space: `Objects` → sections (folders) → objects → items (`CIItemNumericType`,
|
||||||
|
`…BooleanType`, `…StringType`, `…NumericSubType`) with child nodes such as `Value`,
|
||||||
|
`Status`, `Blocked`, `Offline`, `HMIInfo`, and alarm condition nodes. Types are in
|
||||||
|
`http://www.yokogawa.com/CI_Server/` (ns 3 in the manual). **CI Server entities (sections,
|
||||||
|
items) are in namespace `urn:Yokogawa:CI_SERVER_OPC_UA_SERVER`** (verified by browsing;
|
||||||
|
the manual does not name it, ISS-032).
|
||||||
|
- NodeIds are JSON strings: `{"nsid":"<namespace id>"}` for the entity,
|
||||||
|
`{"0":"Value","nsid":"<n>"}` for its value; or by name: `{"0":"Value","itnm":"<item>"}`
|
||||||
|
(case sensitive; verified). The `nsid` changes when the item is recreated — prefer `itnm`.
|
||||||
|
`OPXUAS_USE_NAME_NODEIDS` makes the server use names in its own IDs.
|
||||||
|
- Status mapping: NORMAL → Good; NOT_INIT, UPD_OFF, OFFSCAN, OFFLINE, UNREACH →
|
||||||
|
BadNoCommunication; BAD_VALUE → Bad. Types: Boolean, Int32, Double, String. Priority →
|
||||||
|
severity: 1 → 1000, 2 → 900 … 15 → 50, 0 → 1 (changed in R1.03).
|
||||||
|
- History: items in a history group show HistoryRead; max 5000 values per node per call.
|
||||||
|
- Alarm methods: Acknowledge, Confirm (= acknowledge), Disable/Enable (force to normal);
|
||||||
|
external alarms Acknowledge/Confirm passed to the source; `CIManualReset` for CENTUM.
|
||||||
|
- `opxuas.sup`: General (`FTFW_*` queue, heartbeat, log), OPC UA Server tab
|
||||||
|
(`OPXUAS_OPTIONAL_NODES`, `…_MODEL_CHANGE_EVENTS`, `…_USE_NAME_NODEIDS`,
|
||||||
|
`…_USE_DYNAMIC_SCANRATE`, `…_SOURCE_TIME_STAMPS`, `…_USE_RAW_STATUS`,
|
||||||
|
`…_VARIABLE_CACHE_SIZE` 100000, `…_NUM_VALUES_PER_NODE` 5000), Alarm settings (`EVENTS` =
|
||||||
|
ALARM, ACKN, DEACT, INFO), Logging. Installed keyword names: `OPXUAS_DYNAMIC_SCANRATE`
|
||||||
|
(manual `…_USE_DYNAMIC_SCANRATE`) and extra `OPXUAS_SET_HIGH_PRIO_15` (ISS-034).
|
||||||
|
- `%TLS_ROOT_PATH%\tls\exe\ServerConfig.xml`: endpoint `opc.tcp://[NodeName]:34493`; trust list
|
||||||
|
`…\pki\opxuas\pkiserver\trusted\certs`, rejected `…\pkiserver\rejected` (created at the first
|
||||||
|
rejection), own certificate `ciserveruaserver.der`. **Installed**: only Basic256Sha256,
|
||||||
|
Aes128_Sha256_RsaOaep, Aes256_Sha256_RsaPss with Sign / SignAndEncrypt (no None endpoint);
|
||||||
|
anonymous, user/password **and certificate** user tokens enabled (manual: certificate off,
|
||||||
|
ISS-034); `AutomaticallyTrustAllClientCertificates` false.
|
||||||
|
- First connection of any client: trust the server certificate on the client, then move the
|
||||||
|
client certificate from the server's `rejected` to `trusted\certs`. UaExpert is the
|
||||||
|
suggested test client.
|
||||||
|
- Discovery: LDS on 4840 only when several servers are on a host; GDS for central certificate
|
||||||
|
management (concepts only).
|
||||||
51
knowledge/manuals/IM36K10L55-01EN.md
Normal file
51
knowledge/manuals/IM36K10L55-01EN.md
Normal file
|
|
@ -0,0 +1,51 @@
|
||||||
|
---
|
||||||
|
manual: IM 36K10L55-01EN
|
||||||
|
title: Exchange Tool Engineering
|
||||||
|
edition: 3rd Edition, Sep. 2023
|
||||||
|
version: R1.03
|
||||||
|
status: from docs only (needs CENTUM VP / an RGS node or CCC Prodigy data; not available on the test system)
|
||||||
|
---
|
||||||
|
|
||||||
|
# Exchange Tool Engineering (R1.03)
|
||||||
|
|
||||||
|
Two tools convert another system's engineering data into CI Server engineering data
|
||||||
|
(a "publication" = generated quick load files plus `load.cmd`). Section numbers refer to the
|
||||||
|
manual; Appendix 1 lists the supported CENTUM VP function blocks.
|
||||||
|
|
||||||
|
## 1. CI Exchange for CENTUM VP (§2)
|
||||||
|
|
||||||
|
- Runs on an **RGS** (Remote Gateway Station: CI Server PC with a Vnet/IP card and driver from
|
||||||
|
the medium, `VirtualProduct_CIServer_packageRxxx.zip`, option *installVirtProd*) that talks
|
||||||
|
to CENTUM VP. *Single server*: the RGS is also the CI Core. *Non-single*: an upper CI Core
|
||||||
|
gets the data from the RGS (MDUR).
|
||||||
|
- Solutions: **RGS** (manual or automatic mode; automatic = the tool is embedded in the RGS,
|
||||||
|
ENG HIS equalisation enabled, the RGS registered in the CENTUM VP project; publications
|
||||||
|
generated after each CENTUM VP download) and **RGS with EAL** (external alarms; manual mode
|
||||||
|
only).
|
||||||
|
- Manual workflow: start the tool → create a project (*Single Server* ticked or not) → import
|
||||||
|
CENTUM VP engineering data from the ENG HIS (and MTL file) → *Publish* (name pattern, folder,
|
||||||
|
optional SQL tag filter such as `%PVI%`) → copy the publication folder to
|
||||||
|
`C:\Program Files (x86)\Yokogawa\CIServer\Utility` → run its `load.cmd` on the RGS and/or CI
|
||||||
|
Core (in an IT-security environment run `cmd.exe` *as different user* first). Automatic
|
||||||
|
publications land in `%TLS_ALLUSERS_PATH%\lst\rgs\pub\`.
|
||||||
|
- Output: items `<section>.<TAG>.<PARAM>` (e.g. `<Section>.FIC001.PV`), points
|
||||||
|
`<STATION>:[<item>]`, plus lines/stations, displays and symbols (displays only on the CI
|
||||||
|
Core in non-single configurations).
|
||||||
|
- Precautions (§2.15): refresh open LIST displays after a CENTUM VP online download; CI Server
|
||||||
|
does not allow alarm limits on the wrong side of SV; short data gaps after Vnet scan changes
|
||||||
|
or RDC switch-over; trends may lag after large downloads — reload displays, roll over the
|
||||||
|
history group, tune scan types.
|
||||||
|
- Installed: launcher `%TLS_ROOT_PATH%\tls\com\jwuiutl_ciexchange.cmd` (no RGS on the test
|
||||||
|
system).
|
||||||
|
|
||||||
|
## 2. CI Exchange for Prodigy (§3)
|
||||||
|
|
||||||
|
- For CCC Prodigy turbo-machinery controllers (antisurge, performance, speed). Input: the
|
||||||
|
Modbus register list (`.csv`, from MakerPro) per controller; the station name and IP are
|
||||||
|
entered in the tool.
|
||||||
|
- Install: copy `Windows\EngineeringTools\CIExchange_Prodigy.zip` from the medium, extract to
|
||||||
|
`C:\Program Files (x86)\Yokogawa\CIServer\Utility` (create the folder), run
|
||||||
|
`CIExchange_Prodigy.cmd`.
|
||||||
|
- Workflow: create project → import source configuration → generate publication → load it.
|
||||||
|
Output: items `<section>.<Prodigy variable path>`, Modbus points `<STATION>:[<item>]`, and
|
||||||
|
faceplates (title and engineering unit can be customised, §3.12.1).
|
||||||