Phase 7: BUS Service, Data Access (OPC UA/DA/A&E, ODBC), OPC Interface, Exchange tools #7
2 changed files with 15 additions and 5 deletions
|
|
@ -26,7 +26,7 @@ development system (see "Test system" in `progress.md`); they do not exist on ot
|
|||
| ISS-005 | 2026-09-30 | DATABASE (`dssqld`) | Loading `04_item_his_df.qli` straight after creating the storage group gave 2 errors once; three other runs were clean. Error text not captured. | open | Added a 5 s pause in `load.cmd`. If it happens again, capture `04_item_his_df.qlo`. | `examples/CI-Eng-Sample/load.cmd`; `.claude/skills/system-management/tasks/load-remove-records.md` |
|
||||
| ISS-006 | 2026-09-30 | HISTORY (`ithloahis`) | Samples dated before the start of the current storage unit were not stored (no error shown); samples after it were. Also, a new storage group stored nothing until CI Server was restarted. | open | Confirm with History Management (IM 36K10L20) in phase 9: how to load into older units, and whether a restart is really required. 2026-09-30 (phase 5): IM 36K10L35 §1.3/§5 explains the first part: event storage picks the unit by time stamp, never older than 60 units, and within the storage process's `gap_time` (ITHEEX/ITHEIX 2880 min) and, for EVENT/ITEM, `max_sample_delay` (ITHEIX 14400 min); older data needs earlier unit files (`hisdbg`, `hisrecover`, `isfrename`), `ithrecover <group> -p` and a restart. Practice in phase 9. | `.claude/skills/system-management/tasks/load-history.md`; `examples/CI-Eng-Sample/README.md`; `knowledge/manuals/IM36K10J10-01EN.md` command-line tools |
|
||||
| ISS-007 | 2026-09-30 | INTEGRATION (monitoring) | `intdskmon` wrote 61.9 for a C: drive that is 61.9 % used / 38.1 % free, although the manual says it monitors the disk free space rate. `intspawn` did nothing when the command path was ~130 characters; a short path worked (limit unknown). | open | Confirm the disk value meaning and the path limit. | `.claude/skills/system-management/tasks/monitoring-processes.md`; `knowledge/manuals/IM36K10J10-01EN.md` §4.1.6; `examples/CI-Eng-Sample/monitoring/` |
|
||||
| ISS-008 | 2026-09-30 | ACCESS (web/OPC UA server?) | `ci_start.log` on the test system shows `CppServerAPI::Run() failed: InitializeSslCtx(): SSL_CTX_use_certificate_chain_file() failed.` right after ACCESS Service starts. Which component and certificate is not known. | open | Identify in phase 7 (OPC Interface IM 36K10E20, Data Access IM 36K10L45). | `.claude/skills/installation-security/tasks/setup-check.md`; the phase 7 skill |
|
||||
| ISS-008 | 2026-09-30 | ACCESS (ODBC server `odbsrv`) | `ci_start.log` on the test system shows `CppServerAPI::Run() failed: InitializeSslCtx(): SSL_CTX_use_certificate_chain_file() failed.` right after ACCESS Service starts. Which component and certificate is not known. | open | Identify in phase 7. 2026-10-01 (phase 7): cause found. The message comes from the ODBC server `odbsrv` (ACCESS Service, Simba): `odbsrv.sup` has `USESSL = YES` and `access_start.cmd` points it at `%TLS_ROOT_PATH%\tls\pki\odbsrv\SampleServerCertificate.pem` / `SampleServerKey.pem`, but that folder does not exist and no sample certificate is installed. `odbsrv` exits right after start (`DUR-W-REM_PROC, Process ODBSRV exited unexpectedly`), port 1583 does not listen. Fix (admin, only if ODBC is licensed and wanted): install a certificate + key there, or set `USESSL = NO`. Not applied. Close when the user confirms. | `.claude/skills/installation-security/tasks/setup-check.md`; `knowledge/manuals/IM36K10L45-01EN.md` §1 (done); `.claude/skills/data-access/tasks/access-checks.md` (done) |
|
||||
| ISS-009 | 2026-09-30 | Security Guide | DCOM port range printed as 20500–20550 in the firewall table but "2500–20550" in the OPC configuration table. Taken as a typo for 20500–20550. | open | Confirm on a system with IT security applied. | `knowledge/manuals/IM36K01C30-01EN.md` §4 |
|
||||
|
||||
| ISS-010 | 2026-09-30 | ITEM (sub-items) | The Integrator sub-item adds value × seconds; setting `TIME_UNIT` = Hour made no difference (1 per second while the main item was 1). The Tutorial lists a time unit only for Rate-of-Change. | closed | 2026-09-30 (phase 5): IM 36K10C10 §3.2 and `itm.sup` answer it: the integral is divided by the **integration granule** `itm_int_secs` (label "Integration granule, sec.") in `itm.sup` — **system-wide**, installed value 1 (seconds); 60 = minutes, 3600 = hours. `TIME_UNIT` only applies to Rate-of-Change. Practiced 2026-09-30: set to 60 and restarted → `CI-Eng-Sample.PUMP1.RUNNING.RUN_SECONDS` rose exactly 1.0 in 60 s; restored to 1 (file identical to backup) → 8 in 8 s. Existing integrator values are not converted when the granule changes. Closed 2026-09-30 (confirmed by user). | `examples/CI-Eng-Sample/02b_sub_item_df.qli`; `knowledge/manuals/IM36K10G10-01EN.md` |
|
||||
|
|
@ -49,3 +49,8 @@ development system (see "Test system" in `progress.md`); they do not exist on ot
|
|||
| ISS-027 | 2026-09-30 | PROCESS (`opcdbg`) | IM 36K10L10 §4 says the `opcdbg` *Dump classes/objects* files can be read by `dssqld`. The files have no `@LANGUAGE`/`@FIELDS`/`@<dataset>` headers (`NAME,"desc",prio` + source lines prefixed `- `); `dssqld -i` on the object dump gave `DSS-E-UNK_DS_NM, Unknown data set name`. | open | Use `dssqld -e CLASS_DF` / `OBJECT_DF` for transfers. Maybe an old tool reads the dump format; not found. | `knowledge/manuals/IM36K10L10-01EN.md` §4; `.claude/skills/class-object-engineering/tasks/opcdbg-checks.md` |
|
||||
| ISS-028 | 2026-09-30 | PROCESS (class reset) | After recompiling a class with objects (`RESET_REQUIRED` 1), `dssqld -m` with `CLASS_DF` `RESET` = 1 (also with `RESET_NODE` = host node name) is accepted with 0 errors but does not reset; `OBJECT_DF` `RESET` = 1 is refused (`OPC-E-OBJ_RSTREQ`). `opcdbg` Classes → 8 *Reset class* works; it asks for a reset report file, which the manual does not list. | open | Use `opcdbg`. Still to try: `CLASS_RESET_COMMAND` (system-wide) and the Engineering Module's reset. | `.claude/skills/class-object-engineering/tasks/change-reset-class.md`; `knowledge/manuals/IM36K10L10-01EN.md` §4 |
|
||||
| ISS-029 | 2026-09-30 | PROCESS (Java) | IM 36K10P11 §10.4 says a new Java class must be reset before objects are added, otherwise the code does not take effect. A Java class inserted with `COMPILE` 1 by `dssqld` ran its first object correctly without any reset (twice, including a full sample reload). | open | Installed behaviour is the reference; keep "reset after changing a class that has objects". Check whether the Engineering Module path (compile without quick load) behaves differently. | `knowledge/manuals/IM36K10P11-01EN.md` §7; `.claude/skills/class-object-engineering/tasks/java-class.md` |
|
||||
| ISS-030 | 2026-10-01 | BUS (UMH tools) | `umhman` (hex code → text) crashes with redirected input (bash: segmentation fault 139 with CRLF input; PowerShell `Start-Process -RedirectStandardInput`: 0xC0000005); with an argument it only prompts. `umhtestprog` prints `UMH TEST UTILITY` and crashes (segmentation fault). `umhmsg 8010008` stops with `umh_panic: …umhmsg.exe, license expired` although other tools (`dssqld`, `itmval`) still worked at that time. | open | Try `umhman` interactively in a console; check `umhmsg` on a licensed system. Similar to ISS-022 (`itmval -f`). | `.claude/skills/system-management/tasks/bus-utilities.md`; `knowledge/manuals/IM36K10L30-01EN.md` §3 |
|
||||
| ISS-031 | 2026-10-01 | LICENCE (unlicensed node) | The unlicensed test node counts down about 1 hour of run time per CI Server start (`License time left` in `smd_<node>_LOW_smdsnp_general.log`, 3600 s → `*** license problem : 3 ***`); then `dssqld`/`itmval` stop with `license expired` and `ISF-F-LIC_PROB, DATABASE Service is not licensed`. A PC sleep pauses the count (start 17:25, ran out 09:52 next day). Restart of the CI Service resets it (verified 2026-10-01, back after ~45 s). | open | Known limitation of the test system, documented in `system-check`. Plan tests in ≤ 1 h blocks. Close when the user confirms. | `.claude/skills/system-check/SKILL.md` §3 (done) |
|
||||
| ISS-032 | 2026-10-01 | ACCESS (OPC UA server node IDs) | IM 36K10L45 §10.3 shows CI Server node IDs (`{"nsid":"32"}`, `{"0":"Value","itnm":"ITEM1"}`) and the CI Server namespace `http://www.yokogawa.com/CI_Server/` (ns 3) but not which namespace the **entities** use. With that URI (or `urn:<host>:Yokogawa:CI_SERVER_OPC_UA_SERVER`) the client point was silently not monitored. Browsing (`OPCUAC_TAG_DF`) shows sections/items in **`urn:Yokogawa:CI_SERVER_OPC_UA_SERVER`**; with it `{"0":"Value","itnm":"<item>"}` and `{"0":"Value","nsid":"<n>"}` both work. IM 36K10E20 §2.2.6 also asks to enable `OPXUAS_USE_NAME_NODEIDS` and restart for CI client ↔ CI server; not needed on the test system. | open | Installed software is the reference (standing user decision). Close when the user confirms. | `knowledge/manuals/IM36K10L45-01EN.md` §7 (done); `knowledge/manuals/IM36K10E20-01EN.md` §3 (done); `.claude/skills/data-access/tasks/opcua-client.md` (done) |
|
||||
| ISS-033 | 2026-10-01 | ACCESS (Engineering Module OPC UA point) | Tested by the user: the point form's *Browse path* stops at the item (`Objects/CI-Eng-Sample/TANK1/INFLOW`) and stores the item **object** `{"nsid":"548"}`; the point is not monitored (revised sampling interval 0, connected item status 13, *Last value*/*Data type* empty). Typing `{"0":"Value","itnm":"CI-Eng-Sample.TANK1.INFLOW"}` in *Node Id* fixed it (values followed at once). Browsing into an item that is OPC visible but not *Read* fails (`UncertainNotAllNodesAvailable`, `OPXC-E-BRW_NODE`). | open | Check whether the browse dialog can expand an item to `Value` (e.g. double-click); otherwise type the node ID. | `knowledge/manuals/IM36K10E20-01EN.md` §2 (done); `.claude/skills/data-access/tasks/opcua-client.md` §3 (done) |
|
||||
| ISS-034 | 2026-10-01 | ACCESS (OPC UA server setup) | Installed vs IM 36K10L45 §10.5–10.6: `ServerConfig.xml` enables certificate user tokens (`EnableCertificate true`, manual false) and offers no `None` endpoint (only Basic256Sha256 / Aes128_Sha256_RsaOaep / Aes256_Sha256_RsaPss with Sign or SignAndEncrypt); the `rejected` folder is created only at the first rejection; `opxuas.sup` uses `OPXUAS_DYNAMIC_SCANRATE` (manual `OPXUAS_USE_DYNAMIC_SCANRATE`) and has `OPXUAS_SET_HIGH_PRIO_15` (not described); `opxsys.sup` has `OPXDAS_SET_LOG_LEVEL` (not described). Also `dur.sup` adaptive queue entry `OPCEXE` while the installed executors are `OPCEXE1`–`4`. | open | Installed software is the reference (standing user decision). Close when the user confirms. | `knowledge/manuals/IM36K10L45-01EN.md` §4, §7 (done); `knowledge/manuals/IM36K10L30-01EN.md` §8 (done) |
|
||||
|
|
|
|||
|
|
@ -44,10 +44,10 @@ AID is not needed.
|
|||
| 6 | IM 36K10L10 | Class/Object Engineering | done; `opc.sup` read-only, `opcdbg` read-only actions and Reset class practiced ([notes](manuals/IM36K10L10-01EN.md)); skill `class-object-engineering` |
|
||||
| 6 | IM 36K10P10 | Class Description Language - Traditional | done for prompts, signals, created items, transitional operators, PRINT/ERROR; timers, alarms, containment, STEP, DSS routines, AGA from docs ([notes](manuals/IM36K10P10-01EN.md)) |
|
||||
| 6 | IM 36K10P11 | Class Description Language - Java | done for a basic class (attach/create items, signal trigger, systemMessage); timers, containment, inheritance from docs ([notes](manuals/IM36K10P11-01EN.md)) |
|
||||
| 7 | IM 36K10L55 | Exchange Tool Engineering | not started |
|
||||
| 7 | IM 36K10L30 | BUS Service | not started |
|
||||
| 7 | IM 36K10L45 | Data Access Engineering | not started |
|
||||
| 7 | IM 36K10E20 | OPC Interface | not started |
|
||||
| 7 | IM 36K10L55 | Exchange Tool Engineering | summarized, from docs only (needs CENTUM VP / RGS or Prodigy) ([notes](manuals/IM36K10L55-01EN.md)) |
|
||||
| 7 | IM 36K10L30 | BUS Service | done for single-node checks; MDUR, encryption, logical addresses, printer devices from docs ([notes](manuals/IM36K10L30-01EN.md)); task `system-management/bus-utilities.md` |
|
||||
| 7 | IM 36K10L45 | Data Access Engineering | done for OPC UA client/server (loopback); OPC DA/A&E from docs (DA loopback not allowed); ODBC not running (ISS-008) ([notes](manuals/IM36K10L45-01EN.md)); skill `data-access` |
|
||||
| 7 | IM 36K10E20 | OPC Interface | summarized; OPC UA point form compared with quick load by the user ([notes](manuals/IM36K10E20-01EN.md)) |
|
||||
| 8 | IM 36K10L15 | Alarm Management Engineering | not started |
|
||||
| 8 | IM 36K10C20 | Engineering Module - Alarms | not started |
|
||||
| 8 | IM 36K10E30 | Alarm System Performance Analysis | not started |
|
||||
|
|
@ -115,3 +115,8 @@ now come before classes and objects (phase 6), and the other interfaces follow a
|
|||
| R10/R20 | Change a setup file safely ([task](../.claude/skills/portal-setup/tasks/change-setup-file.md)) | passed | n/a | `jwuiisg.sup` HTTP port 8080 → 8081 (text edit, elevated restart): 8081 served the page, 8080 refused; restored, hash identical to backup. Editor: *OK* writes at once, *Reset Field* restores the default (ISS-016). |
|
||||
| R10 | Separate CI Portal node (licence, DURM line, `dur.sup` host node, copy displays) | not practiced | n/a | Needs a second node. |
|
||||
| R10 | Login method / login control | not practiced | n/a | Moved to `dssana.sup` (ISS-017); phase 5 (C10) and 13 (J40). |
|
||||
| L45/E20 | OPC UA client → own OPC UA server loopback by quick load; certificate exchange; node IDs ([task](../.claude/skills/data-access/tasks/opcua-client.md)) | passed | passed | Station `CIENG_UA` (`opc.tcp://localhost:34493`, Basic256Sha256/SignAndEncrypt): `UA.LEVEL_COPY` follows `TANK1.LEVEL` (55, 62.5, 71, 33, 44.4), `UA.SRV_STATE` 0. Certificates trusted by the user (client side, then server side). Entity namespace `urn:Yokogawa:CI_SERVER_OPC_UA_SERVER` found by browsing `OPCUAC_TAG_DF` (ISS-032). Full remove/reload clean, reconnects without a new exchange. User configured a point in the Engineering Module: browse stores the item object, value node must be typed (ISS-033); test item/point removed afterwards. |
|
||||
| L45 | ACCESS read-only checks: processes, ports, OPC UA server config/PKI, ODBC server ([task](../.claude/skills/data-access/tasks/access-checks.md)) | passed | n/a | ISS-008 cause found: `odbsrv` cannot load its SSL certificate (folder `tls\pki\odbsrv` missing) and exits. |
|
||||
| L30 | BUS utilities: `durwfp`, setup files (`dur.sup`, `durm_1_udp.sup`, `time_table.sup`, `fmfprt.sup`) ([task](../.claude/skills/system-management/tasks/bus-utilities.md)) | passed (read-only) | n/a | `umhman`, `umhtestprog`, `umhmsg` fail (ISS-030). Unlicensed run-time limit hit and documented (ISS-031). |
|
||||
| L30 | MDUR node links, encryption, logical addresses, printer devices | not practiced | n/a | Single node, no printer devices. |
|
||||
| L55 | CI Exchange for CENTUM VP / Prodigy | not practiced | n/a | Needs CENTUM VP (RGS, Vnet/IP) or Prodigy data. |
|
||||
|
|
|
|||
Loading…
Add table
Reference in a new issue