ci-server-engineer/knowledge/manuals/IM36K10C60-01EN.md
cliu 2ae5ace753 Add graphics manual summaries (R30, C50, C60) and graphics skill
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-01 14:50:13 +10:00

54 lines
3.2 KiB
Markdown
Raw Permalink Blame History

This file contains ambiguous Unicode characters

This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.

---
manual: IM 36K10C60-01EN
title: Advanced Operating Graphics
edition: 3rd Edition, Sep. 2023
version: R1.03
status: from docs; installed AOG displays checked read-only (DEPLOY\displays, mobileoperator) 2026-10-01
---
# Advanced Operating Graphics — AOG library (R1.03)
A ready-made library of symbols and displays in a consistent, high-performance HMI style,
used from the Edit Module's Visualization sheet. Section numbers refer to the manual.
## 1. Symbols (§1.1)
| Kind | Purpose | Palettes / examples |
|---|---|---|
| Equipment symbols | Static equipment, no live data | `AOG_ContainersAndVessels` (AOG_Tank, AOG_Vessel, AOG_Reactor, …), `AOG_HeatTransfer`, `AOG_Indicator`, `AOG_MaterialHandling`, `AOG_Mixing`, `AOG_Rotating` (pumps, compressors, turbine), `AOG_Separators`, `AOG_ValvesAndActuators`, `AOG_Electrical`, `AOG_Filters`, `AOG_Others` (Yokogawa systems such as AOG_CentumFCS, AOG_ProsafeRS, AOG_StardomFCN, AOG_FAM3, AOG_DTS; field devices; stations) |
| Item symbols | Show and change one or more item attributes | indicators (bar, needle, circular, radial, number, text, on/off, manual, alarm, trend), valves (2-way, 3-way, on/off), selection box, name/info |
| Object symbols (`AOG_O…`) | Same, driven by PROCESS Service object signals | e.g. `AOG_ONumberIndicator`, `AOG_OHorizontalBarIndicator` |
| Navigation symbol, components | Navigation between displays | |
## 2. Displays (§1.2)
Standard displays: `AOG_Default`, `AOG_DisplayTemplate` (start for new displays), `AOG_Style`
(global style parameters), `AOG_MenuMain`, alarm displays (`AOG_AlarmBanner`, `AOG_AlarmCurrent`,
`AOG_AlarmHistory`, `AOG_AlarmShelved`), `AOG_AuditTrail`, `AOG_ItemFaceplate`,
`AOG_ItemTuningPanel`, `AOG_ObjectFaceplate`, `AOG_ObjectTuningPanel`, `AOG_SetItemMode`,
`AOG_SetObjectMode`, `AOG_SetNumberPV/SV/SL/SH/SLL/SHH`, `AOG_LockStatus`, `AOG_TrendOpen`,
OPC UA method call displays; plus demo displays. **Installed**: these are in
`DEPLOY\displays`, and the alarm, audit, default, menu, style, trend and UA method displays also
exist as HTML displays.
## 3. Global style parameters (§1.1, §2.1.1)
Defined once on the `AOG_Style` display (*Parameters* tab) and used by all AOG symbols:
colours (`AOG_C…`: alarm high/medium/low/diagnostic/off, display background, equipment
running/off/not running, fluid and gas lines, indicator background/limit/normal/outline/signal,
manual control, selector, text 1–4), strokes (`AOG_S…`), fonts (`AOG_FT1–4`), engineering unit
texts (`AOG_EF1` flow, `AOG_EL1` level, `AOG_EP1` pressure, `AOG_ET1/2` temperature), on/off
texts, `AOG_BlinkOnNotAcknowledged`. Changing a value changes every symbol that uses it.
## 4. Building an HMI (§2)
Edit Module → (optionally) adjust `AOG_Style` and save → *New display* or start from
`AOG_DisplayTemplate` → place AOG symbols from the Visualization sheet → connect them to items
or objects → save → open in the operator interface. New symbols can be made in the same style.
## 5. Enterprise (§3)
Enterprise displays and AOG item/object symbols for enterprise engineering (items/objects on
several servers; locations chosen per symbol).
Not practiced: the sample display uses plain components; AOG symbols need the Edit Module GUI.