2.9 KiB
2.9 KiB
| manual | title | edition | version | status |
|---|---|---|---|---|
| IM 36K10L55-01EN | Exchange Tool Engineering | 3rd Edition, Sep. 2023 | R1.03 | from docs only (needs CENTUM VP / an RGS node or CCC Prodigy data; not available on the test system) |
Exchange Tool Engineering (R1.03)
Two tools convert another system's engineering data into CI Server engineering data
(a "publication" = generated quick load files plus load.cmd). Section numbers refer to the
manual; Appendix 1 lists the supported CENTUM VP function blocks.
1. CI Exchange for CENTUM VP (§2)
- Runs on an RGS (Remote Gateway Station: CI Server PC with a Vnet/IP card and driver from
the medium,
VirtualProduct_CIServer_packageRxxx.zip, option installVirtProd) that talks to CENTUM VP. Single server: the RGS is also the CI Core. Non-single: an upper CI Core gets the data from the RGS (MDUR). - Solutions: RGS (manual or automatic mode; automatic = the tool is embedded in the RGS, ENG HIS equalisation enabled, the RGS registered in the CENTUM VP project; publications generated after each CENTUM VP download) and RGS with EAL (external alarms; manual mode only).
- Manual workflow: start the tool → create a project (Single Server ticked or not) → import
CENTUM VP engineering data from the ENG HIS (and MTL file) → Publish (name pattern, folder,
optional SQL tag filter such as
%PVI%) → copy the publication folder toC:\Program Files (x86)\Yokogawa\CIServer\Utility→ run itsload.cmdon the RGS and/or CI Core (in an IT-security environment runcmd.exeas different user first). Automatic publications land in%TLS_ALLUSERS_PATH%\lst\rgs\pub\. - Output: items
<section>.<TAG>.<PARAM>(e.g.<Section>.FIC001.PV), points<STATION>:[<item>], plus lines/stations, displays and symbols (displays only on the CI Core in non-single configurations). - Precautions (§2.15): refresh open LIST displays after a CENTUM VP online download; CI Server does not allow alarm limits on the wrong side of SV; short data gaps after Vnet scan changes or RDC switch-over; trends may lag after large downloads — reload displays, roll over the history group, tune scan types.
- Installed: launcher
%TLS_ROOT_PATH%\tls\com\jwuiutl_ciexchange.cmd(no RGS on the test system).
2. CI Exchange for Prodigy (§3)
- For CCC Prodigy turbo-machinery controllers (antisurge, performance, speed). Input: the
Modbus register list (
.csv, from MakerPro) per controller; the station name and IP are entered in the tool. - Install: copy
Windows\EngineeringTools\CIExchange_Prodigy.zipfrom the medium, extract toC:\Program Files (x86)\Yokogawa\CIServer\Utility(create the folder), runCIExchange_Prodigy.cmd. - Workflow: create project → import source configuration → generate publication → load it.
Output: items
<section>.<Prodigy variable path>, Modbus points<STATION>:[<item>], and faceplates (title and engineering unit can be customised, §3.12.1).