- R1.03 frozen on branch r1.03 / tag r1.03-final; README and CLAUDE.md explain which branch to use and the rules for the shared R1.05 server. - knowledge/version-differences.md: R1.03 -> R1.05 changes from the manual revision tables and a read-only comparison of installed files (install paths, eqt/eta IEC 104/61850 drivers, REST server, jupgutl, new pyTOOLS manual IM 36K10P40). - system-check re-checked read-only on the R1.05 test server. - progress.md: R1.05 re-check table per skill; document map lists R1.05 and R1.03 editions. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
7.4 KiB
Version differences: R1.03 → R1.05
What changed between CI Server R1.03.00 (what this repo was first written for; frozen on
branch r1.03, tag r1.03-final) and R1.05.00 (current target of main).
Each skill and manual summary is moved to R1.05 one at a time; this file is where to look for
the changes in the meantime.
Sources: the revision tables at the end of each R1.05 manual (editions dated Feb. 2026; R1.04 editions Jan. 2025) and a read-only comparison of the installed files on the R1.03 development machine and the R1.05 test server (2026-10-08). Status: from docs plus verified file lists; behaviour is not yet re-tested.
1. Installation and files (verified, 2026-10-08)
| R1.03 (development machine) | R1.05 (test server) | |
|---|---|---|
| Version string | CI Server R1.03.00 (r10200M) |
CI Server R1.05.00 (r11609M) |
Program root (TLS_ROOT_PATH) |
C:\Program Files (x86)\Yokogawa\CIServer |
C:\Yokogawa\CIServer |
Data root (TLS_ALLUSERS_PATH) |
C:\Users\Public\Yokogawa\tls |
C:\Yokogawa\CIServer\tls (same folder as the program) |
| Manuals | C:\Users\Public\Yokogawa\tls\doc\EN |
C:\Yokogawa\CIServer\tls\doc\EN |
tls_versions.lst |
all lines R1.03.00 |
112 lines R1.05.00, jython-full R1.04.00 |
The install paths may be a choice made at install time, not a product change. Always read the
TLS_* environment variables (set TLS) rather than assuming a path. Skills still show the R1.03 paths
until they are re-checked.
Installed files that are new or gone (only names that matter for engineering are listed):
| Area | New in R1.05 | Gone since R1.03 |
|---|---|---|
| IEC 60870-5-104 and IEC 61850 drivers | New driver family eqt* / eta*: eqt104, eqt850, eqt850dmp, eqtdbg, eqtfrcscn, eqtiostat, etaman, eta104*.sup, eta850*.sup, eqtini.sup, eqt850.icd, eqtfrcscn.tpl, eqtini.tpl |
eqp104, eqp850, eqp850dmp, epa104*.sup, epa850*.sup (the drivers left the eqp EQUIPMENT family) |
| IEC 61850 configuration | Quick load / form programs iec61850_line_u0104, iec61850_station_u0104, iec61850_point_u0105, iec61850_rcb_u0105 |
— |
| OPC UA | opcuac_method_u0104 (OPC UA client methods), opcuac_station_u0104, opcaec_station_u0104 |
opcaec_station_u0103 |
| REST API | jrstsrv.jar, jrstsrv.sup, jrstsrv.tpl (RESTful API server, see IM 36K10C40 §4.2) |
— |
| Upgrade | jupgutl.cmd, jmrg.jar (merge configuration files on upgrade, IM 36K01C10 ch. 3) |
— |
| Data access | dacbackfill.cmd, intimpdac.exe (OPC DA backfill; not yet investigated) |
— |
| Graphics | connectrdp.cmd (Edit Module RDP Connect action, IM 36K10C50 §2.31) |
— |
| Authorization | dss_ath_grp_u0104 (authorization group form/loader, new revision) |
— |
| Setup files | fcsini.sup, scsini.sup, ugsini.sup, vvnetini.sup now in tls\sup (were only templates in R1.03), extjython-full.sup |
— |
The R1.03 development machine also had eqpcieng*, opxcieng* and adtlogci.sup files that were added there
for the sample project CI-Eng-Sample; they are not part of the product.
2. Manuals (from docs)
All 39 manuals were reissued (Feb. 2026). One manual is new. Most of them only added contact information. The table lists the ones with real changes after R1.03, with the sections named in the R1.04 and R1.05 revision tables.
| Manual | Changes after R1.03 | Repo area to re-check |
|---|---|---|
| IM 36K10P40 pyTOOLS Programmer's Guide | New (R1.04): Python extension module for DSS (connect, read/modify datasets, filter, lock, events, BUS messages, item history). Runs on CI Core / CI Portal, local node only. | new skill or system-management task |
| IM 36K01C10 CI Server Setup | R1.04: OS list, Defender, WMIC on Win 11 24H2, Vnet/IP drivers, Kernel DMA check, VAGW Bossd service, upgrade workflow, instance setup files vs templates. R1.05: IT security version 3.0, LAPS, automatic merge of configuration files on upgrade (jupgutl), new ch. 4 Connecting CI Server and PRM |
installation-security |
| IM 36K01C30 Security Guide | R1.04: Windows Server 2022 (2016 removed), registry permissions, firewall port table, services list. R1.05: Windows 11 Enterprise LTSC 2024, IT security 3.0, §4.8.3–4.8.4 domain join, §5.27 new, ch. 6 safe API use | installation-security |
| IM 36K01A50 Release Information | Precaution sets updated (e.g. lockout policy dialog when upgrading from R1.03 with IT security applied) | knowledge/manuals/IM36K01A50-01EN.md |
| IM 36K10L45 Data Access Engineering | R1.04: ch. 4 new, §10.3.4, 10.5, 10.6 new, setup-file parameters in §10.4, 10.9, 11, 11.5.2. R1.05: §11.4 new, §11.1.6 note, §11.6.2 setup file, App. 1.3 | data-access |
| IM 36K10E20 OPC Interface | R1.04: parent object node ID and arguments of OPC UA methods. R1.05: certificate-expiry notifications, ch. 3 new OPC UA Information Model Mapper (map external OPC UA entities to CI Server), App. 1 SQL keywords | data-access |
| IM 36K10L41 EQUIPMENT Configuration | R1.04: item status descriptions (§3.4.5–3.4.8), §3.12.2, §3.15, IEC 61850 functions (§3.32), App. 1 new (precautions on upgrade to R1.04). R1.05: §3.32, App. 1.3, App. 1.4 new | equipment |
| IM 36K10L50 Data Set Service Engineering | R1.04: OPC UA client method dataset renamed OPCUAC_METHOD_CALL_IN_DF → OPCUAC_METHOD_CALL2_DF |
system-management, data-access |
| IM 36K10C40 Engineering Module – Historical | R1.04 §4.2: external access to history now lists ODBC, .NET API, RESTful API, pyTOOLS (C API no longer listed) | history-management |
| IM 36K10C50 Edit Module | R1.04: §2.22 properties, §2.31 Password Check action, §4.12 update item/parameter. R1.05: §2.22, 2.25, 2.26, 2.33 properties, §2.31 RDP Connect action | graphics |
| IM 36K10C60 Advanced Operating Graphics | R1.04 §1.2.2: demo displays | graphics |
| IM 36K10R30 Graphic Display Setup | R1.05: §4.8 Enterprise Operation properties, §4.10 restrictions | graphics |
| IM 36K10R10 CI Portal Setup | R1.04 §3.3 (dur.sup), installation from ISO file instead of DVD |
portal-setup |
| IM 36K10J10 System Design/Management | R1.04 §2.9.1 | system-management |
| IM 36K10C10 Engineering Module – I/O | R1.04 §2.2 | item-engineering |
| IM 36K10G10 Tutorial | R1.04 §9.2, ch. 14 new. R1.05 ch. 14 extended, ch. 15 new | knowledge/manuals/IM36K10G10-01EN.md |
| IM 36K10L55 Exchange Tool Engineering | R1.04: upgrade scenario for CI Exchange for CENTUM VP. R1.05 §2.7: HIS-TSE connection options | knowledge/manuals/IM36K10L55-01EN.md |
No content change (only contact information or wording): C20, C30, E10, E30, J20, J40, L10, L15, L20, L25, L30, L35, L36, L40, P10, P11, P20, P30, R20, R40. Skills based only on these manuals still need a quick re-test on R1.05 (installed files may differ), but their content is expected to hold.
3. Re-check plan
Order (biggest change first), tracked in progress.md under R1.05 re-check:
system-check(paths, version string): done in the baseline.installation-security,data-access,equipment: real manual changes.- New pyTOOLS manual (P40) and the REST API.
graphics,history-management,portal-setup,system-management.- All other skills: re-test the task files on R1.05, no manual change expected.
The R1.05 test server is shared with other projects. Re-checks there are read-only unless
the user approves a change; see "Test system" in progress.md.