cliu bf7d88a027 R1.05 re-check batch 3: alarms, audit, authorization, classes, HAC, reporting, pyTOOLS
Full manual diffs (L15, C20, E30, L25, J40, C10 §2, L10, P10, P11, J20,
C30, P20, R40, E10) and read-only checks on the shared R1.05 test server.
Skills and summaries moved to R1.05; new skill pytools (IM 36K10P40) from
docs (no Python on the test server). Issues ISS-132..181; corrections to
version-differences (E10, E30, P11, dss_ath_grp_u0104); C10 summary lists
the 3 new authorization actions; r105-verification V10-V17.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-09 10:21:36 +11:00

4 KiB

task version source status
Send reports to a file - printer device and destination R1.05 (first written for R1.03) IM 36K10C30-01EN §2.2 (4th Edition, Feb. 2026); IM 36K10L50-01EN App. 1 (PRINTER_*); practiced on CI-Eng-Sample 2026-10-01 verified on R1.03 (2026-10-01); on R1.05 the PRINTER_* definitions are identical to R1.03 (file hashes, 2026-10-08), the 6 factory destinations (no devices) are the same (2026-10-09, read-only), and the sample's file device and destination loaded and were removed with 0 errors (2026-10-08, load check only); printing to the file not tested on R1.05

Report output devices and destinations

A report goes to a destination (PRINTER_DEST_DF), which sends it to a primary (and optional secondary) device (PRINTER_DEV_DF). Devices: FILE, HARDCOPY (Windows printer queue), APPLICATION. Engineering Module: Configuration > Reporting > Printers > Device / Destinations. The printer manager is FMFPRT.

1. Find the output types of this node

dssqld -e types.csv -d PRINTER_TYPE_DF -c

Names are <node>:FILE, <node>:HARDCOPY, <node>:APPLICATION (<node> = CI Server node name, NODE_NAME in LOCAL_NODE_DF, e.g. UNLICENCED on an unlicensed system). A device needs the full name; plain FILE is refused (DSSP-E-NORELV).

2. File device and destination

@FIELDS
NAME,DESCRIPTION,OUTPUT_TYPE,PARAMETERS,SUSPEND
@PRINTER_DEV_DF
"<DEVICE>","Report file","<node>:FILE","PATH,""<folder>"",FILE,""<file>.txt"",OVERWRITE,""Yes""",0

@FIELDS
NAME,DESCRIPTION,PRIMARY_DEVICE,POLICY,ALLOW_OPERATOR,PRIORITY
@PRINTER_DEST_DF
"<DEST>","Report file","<DEVICE>","None",1,0

dssqld -i. <folder> must be a literal path that exists (no %variables%: FSL-E-PRT_PAR, Invalid device parameter in umhlog.log). OVERWRITE "Yes" keeps one file with the latest report ("No" not tried). ALLOW_OPERATOR 1 also lists the destination in PRINTER_OPER_DEST_DF (needed for ADHOC_DEST and the operator's generate/print dialogs). CI-Eng-Sample builds this file at load time from 17_printer_df.tpl (node name and %TLS_LST_PATH% filled in by 17_printer_df.ps1).

Printer instead of file: OUTPUT_TYPE <node>:HARDCOPY, PARAMETERS TYPE,"WINDOWS",QUEUE,"\\<server>\<printer>" (+ FONT, POINT, LINES, ORIENTATION) — not practiced (no printer).

3. Use it

Set DEST_NAME (scheduled/triggered runs) and ADHOC_DEST (ad-hoc runs) of the report to <DEST>, or print a generated report (define-reports.md §4).

4. Check

dssqld -e jobs.csv -d PRINTER_JOB_OVV -c      (job, file, submitter, status, destination, device)
dssqld -e devs.csv -d PRINTER_DEV_OVV -c      (device status, e.g. Ready)

A job can show Finished even when the device failed; also read %TLS_LOG_PATH%\umhlog.log (From: FMFPRT, FSL-E-…). The output file holds the text report as generated (HTML reports as HTML source).

5. Remove

Remove (or repoint) the reports that use the destination, then the destination, then the device (DSSP-E-NODEL … still in use otherwise). The output file is not deleted.

R1.05 (2026-10-08/09)

  • <folder>: use the real TLS_LST_PATH of the system (set TLS); on the R1.05 test server it is under C:\Yokogawa\CIServer\tls, not C:\Users\Public\Yokogawa\tls. 17_printer_df.ps1 fills it in from the environment, so the sample works on both.
  • Verified (R1.05 test server): factory destinations ALARMS, AUDIT_TRAIL, DEFAULT, MESSAGES, PRINTER_1, SCREEN_CAPTURE, no devices (as on R1.03, 2026-10-09); the sample's device and destination loaded and were removed with 0 errors (2026-10-08).
  • Awaiting user verification: a print to the file device on R1.05 (see define-reports.md R1.05 section); expected job Finished, device Ready, the report text in the file.

Verified (R1.03, 2026-10-01)

CIENG_FILE (UNLICENCED:FILE, C:\Users\Public\Yokogawa\tls\lst\cieng_report.txt, overwrite): printed generated reports, scheduled, triggered and ad-hoc runs wrote the file; jobs Finished, device Ready; %TLS_LST_PATH% in the path failed as above.