Read-only re-check on the shared R1.05 test server plus a diff of the R1.03 and R1.05 manual editions. - installation-security: R1.05 OS list, Defender exceptions, IT security 2.0/3.0, LAPS, automatic configuration merge (jupgutl), PRM chapter, port 34597; setup_check.ps1 gets -Version (default 1.05.00). - data-access: L45 renumbered (new ch. 4 RESTful API), extended OPC UA functions off by default, OPC UA methods (OPCUAC_METHOD_CALL2_DF), Information Model Mapper, ServerConfig.xml in %TLS_SAV_PATH%. - equipment: Modbus unchanged; IEC 104/61850 run as EQT managers (eqtdbg, eqtfrcscn), IEC 61850 report control blocks, upgrade steps. - Issues ISS-076..090; R1.05 notes on ISS-003/008/032/034/061; progress and version-differences updated. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
189 lines
14 KiB
Markdown
189 lines
14 KiB
Markdown
---
|
||
manual: IM 36K01A50-01EN
|
||
title: CI Server Release Information
|
||
edition: 5th Edition, Feb. 2026 (section "Platform and installation"); other sections still from the 3rd Edition, Sep. 2023
|
||
version: R1.05 (first written for R1.03); only "Platform and installation" re-checked so far
|
||
status: from docs ("Platform and installation" compared with the 5th edition on 2026-10-08; Start-menu folder checked on the R1.05 test server)
|
||
---
|
||
|
||
# Release Information: known issues and cautions (R1.05)
|
||
|
||
Known limitations and workarounds that the other manuals do not cover. Check this list
|
||
before recommending a workflow in any area. Section numbers refer to the manual. The
|
||
"Platform and installation" table follows the 5th edition (R1.05); the other sections were
|
||
written from the 3rd edition (R1.03) and are re-checked with their skills.
|
||
|
||
## Platform and installation
|
||
|
||
| Area | Issue | What to do |
|
||
|---|---|---|
|
||
| Dual-redundant platform (1.1) | Without a Vnet/IP card, guest time sync by NTP makes host messages in the historical alarm overview show wrong timestamps. | Accept, or use Vnet/IP time sync. |
|
||
| Dual-redundant platform (1.1) | After both computers restart, the former standby may come up as *Guest OS (Isolated)*. | In the Redundancy Management Tool set Next Status to *Standby*, then restart that computer. |
|
||
| IT Security tool (1.3) | Remote Desktop to the CI Server may fail after applying IT Security if OS patch levels differ. | Patch both the server and the RDP client to the latest level. |
|
||
| IT Security tool (1.3) | Changing Windows region/language after applying IT Security causes problems. | Set region and language **before** applying IT Security; never change afterwards. |
|
||
| IT Security tool (1.3, R1.04+) | Upgrading from R1.03 or earlier where the IT security defaults were changed: a dialog offers to reset the account lockout settings (threshold, counter reset, duration). | Answer Yes (No returns to the start of the IT security setup); afterwards set any custom lockout values again. |
|
||
| Windows (1.4) | CI Server started from the command line on Win10 / Win11 needs elevation. (The R1.03 Server 2016 start-menu note is gone.) | Always use *Run as administrator*. |
|
||
| Windows (1.4) | Custom fonts can cause visual glitches in the Engineering and Edit modules. | Avoid custom fonts. |
|
||
| Windows (1.4, R1.04+) | After a user without rights to the CI Server programs opens the CI Server Start-menu folder, its icons stay blank for everyone. | In an elevated prompt, in `C:\ProgramData\Microsoft\Windows\Start Menu\Programs\CI Server` (likewise *CI Server Remote Connect*, *YOKOGAWA Security*, *YOKOGAWA Redundancy*) run `COPY /B * +,,` to touch the shortcuts. The manual's path has typos; the folder name was checked on the R1.05 test server (2026-10-08). |
|
||
| Install path (1.9) | The MELSEC EZSocket installer fails if CI Server is in a non-default path that contains spaces (still in the 5th edition). | Non-default install paths must have no spaces. |
|
||
| MELSEC (1.9, R1.05) | iQ-R support now uses EZSocket 5.9, installed from `<ISO drive>\Windows\EZSocketPcRedistributableInstaller` (`RunInstaller` as administrator); Mitsubishi reports a vulnerability in it. | Uninstall older EZSocket first. Keep the EZSocket folder writable by Administrators only, run antivirus, keep the PC off untrusted networks (VPN/firewall for remote access), open no untrusted files or links. |
|
||
| Virtual machines (1.19) | Live migration, failover and shared-storage path switching lose acquired data/alarms; failover during engineering can corrupt the engineering data. | Migrate only when no engineering is in progress; keep engineering backups. |
|
||
| Virtual machines (1.19) | Serial-only drivers (Siemens 3964R, telemetry integration), Siemens SAPI-S7 and MELSEC are unavailable on VMs; many other drivers work over TCP/IP only. | Check driver support before choosing a VM. |
|
||
| Virtual machines (1.19) | Do not use VM replication; do not mix physical and virtual machines in HAC; only thin clients may RDP into a virtual CI Server. | Design accordingly. |
|
||
| Virtual machines (1.19) | The software medium must be mounted as an ISO on the VM (e.g. via Hyper-V Manager › Media › DVD Drive › Insert Disk). | Read "DVD drive" in the manuals as the mounted ISO drive. |
|
||
|
||
## Services
|
||
|
||
**ACCESS (1.5)**
|
||
- OPC classic on Win10 / Win11 / Server 2019 / 2022 needs .NET 3.5 (5th edition; R1.03 listed Server 2016). Install it from the Windows medium
|
||
(`DISM /Online /Enable-Feature /FeatureName:NetFx3 /All /LimitAccess /Source:<drive>:\sources\sxs`),
|
||
then re-run the OPC Core Components Redistributable in `%TLS_EXE_PATH%`.
|
||
- OPC AE: items in the tree root (no section) appear as `.NAME` and some clients can't use them
|
||
as alarm sources. Put alarm-source items inside a section.
|
||
|
||
**ALARM (1.6)**
|
||
- Shelving cannot restrict OPC AE items by status/type.
|
||
- Shelving more than 500 alarms can overflow the DURM queue; after a Portal–Core link loss,
|
||
restart the shelf overview.
|
||
|
||
**BUS (1.7)**
|
||
- Secure MDUR on Linux: create `/tls/pki` manually before configuring the secure connection.
|
||
|
||
**DATABASE (1.8)**
|
||
- With Active Directory login, up to ~15 s may pass between the login form closing and the
|
||
application appearing. Expected behavior.
|
||
|
||
**EQUIPMENT (1.9)**
|
||
- MELSEC iQ-R: R1.03 needed Mitsubishi EZSocket 4.4 from `%TLS_ROOT_PATH%\tls\exe\EZSocketPcRedistributableInstaller`;
|
||
R1.05 uses EZSocket 5.9 from the install media (see the MELSEC row in the table above).
|
||
Uninstall older EZSocket first and run `RunInstaller` as administrator.
|
||
- IEC 61850: add the line, then the station (General tab: device IP; Options tab: domain prefix
|
||
and report object), then points. The element address is `<domain prefix><rest>`; the point
|
||
I/O address is only the part **after** the prefix (the prefix is added automatically).
|
||
Wrong delimiting means no reports/elements are created. (R1.03 edition; this precaution was
|
||
removed in the 5th edition, see the L41 summary §3.32 for R1.05.)
|
||
|
||
**PROCESS (1.10)**
|
||
- Java classes that access datasets must get the DSS session with `getDssSession()` (never
|
||
`Dss.createSession()` or `DssContext.getSession()`), must never close it, and must be
|
||
recompiled and reset after the change. Otherwise results are undefined
|
||
(e.g. `ADT-E-ECL_UNKNOWN` in the system log).
|
||
- When making items with SIGNALs, handle root-level items: if `SECTION` is empty use the tag
|
||
alone, else `SECTION || "." || tag`. Prefer automatic naming.
|
||
- Section-based SIGNAL creation does not support process area definitions.
|
||
|
||
**REPORT (1.11)**
|
||
- AD + printer management can make report generation fail (looks for the user's default
|
||
printer). Workaround: create a printer destination not bound to a device and set it as
|
||
the default destination in the AD user profile.
|
||
- Report features of Schemes take effect only after restarting the Engineering module.
|
||
|
||
**USER (1.12)**
|
||
- Remote Connect is for client machines **without** CI Server; don't install it on a CI Server.
|
||
- HTML5 displays cannot be validated via Remote Connect; engineer them on a CI Portal.
|
||
- HTML5 is a lightweight/mobile HMI with fewer components than Java displays (details in
|
||
Edit Module, IM 36K10C50). Use Google Chrome; other browsers may render differently.
|
||
- SSO leaves a landing page open that the user must close. SSO needs Active Directory, so
|
||
Windows only.
|
||
- `jwuiutl` over Remote Desktop is denied by default. To allow it: Setup File Editor ›
|
||
`dssana.sup` › *Login Control* tab › row *Client system name `<remote>`, Display and Symbol
|
||
Utility* › Login method = *No* › restart CI Server. Needed by CI Exchange (CENTUM VP /
|
||
Prodigy) load and conversion scripts.
|
||
- Remote Connect operator interface may fail to start (Java network read issue): retry, or
|
||
clear the Java cache (Java Control Panel › Temporary Internet files › Delete files).
|
||
- Auto-login is for server / CI Portal applications only, not Remote Connect.
|
||
- "Application blocked" for `.jnlp` over HTTPS is caused by the self-signed web server
|
||
certificate. Fix with a CA/domain-issued certificate (preferred) or add
|
||
`https://localhost:8443` to trusted sites (less safe).
|
||
- Web HMI display names are case sensitive.
|
||
- Custom Java components must be signed by Yokogawa before use.
|
||
- Edit module quirks: item properties editor Value field font too small; *Update
|
||
item/parameter* on the Attributes sheet ignores the first change (repeat it or use the
|
||
Actions sheet); a symbol custom property must not reuse an existing property name;
|
||
choosing *Open display* in an event's Action combo adds a duplicate event (delete it);
|
||
function components must stay inside the drawing area and must not be grouped.
|
||
- Same-size labels may render at slightly different sizes (Java anti-aliasing). Use *Apply
|
||
text smoothing* in the CI Portal setup file, or a non-integer zoom such as 99.999 %.
|
||
- HTML5 limitations: no login name in the status bar; frame border styles map imperfectly;
|
||
Windows display scaling must be 100 %; no rotation or column filters on alarm overview /
|
||
shelved alarm overview; transparency and margin properties are ignored.
|
||
|
||
## HMI, GIS and OPC UA
|
||
|
||
**HMI general (1.13)**
|
||
- Date/Time field with *editable* or *disable* set shows a black foreground in the operator
|
||
interface (correct in HTML).
|
||
- Up/down buttons differ in size between operator interface and HTML.
|
||
- With *Fit display*, tooltips and selection dialogs of trend / alarm overview are misplaced.
|
||
Uncheck *Zoom enabled* on those components, or design displays at the target resolution.
|
||
|
||
**GIS (1.14)**
|
||
- Click info is not shown for symbols built with a data bar. Use simple symbols as map markers.
|
||
- Don't use symbols containing alarm overview, trend or report components in GIS (high memory
|
||
in Chrome; alarm overview filters don't receive item names).
|
||
- Symbols/map layer may disappear or draw behind the map after long runs (Ctrl+wheel zoom
|
||
restores). In Chrome, disabling hardware acceleration fixes symbols drawn behind the map.
|
||
|
||
**OPC UA (1.15)**
|
||
- PubSub upload fails with *Internal error* if a published dataset has zero items. Remove or
|
||
revert those datasets.
|
||
- The datatype combo in PubSub Reader item mapping has no effect.
|
||
- Variables/properties of `CIAlarmConditionType` / `CISystemEventType` nodes can't be read
|
||
(`BadNotReadable`) or subscribed individually (`BadNotSupported`); subscribe to the alarm event.
|
||
- CI Core memory for external OPC UA clients: under 20,000 items no extra memory;
|
||
20,000–99,999 add 8 GB; 100,000–199,999 add 16 GB; beyond that add 8 GB per extra 100,000.
|
||
|
||
## Server Core / Portal (1.16)
|
||
|
||
- Secure DURM with an invalid certificate common name continues **unencrypted** (only logged).
|
||
After installing/refreshing certificates, check the message log that they were accepted.
|
||
- Remote Connect Engineering module is slow against a redundant CI Core. Use RDP to the Core,
|
||
or temporarily run the redundant platform in single mode.
|
||
- Several MQTT stations on one MQTT line with brokers unavailable can time out during offline
|
||
engineering. Use one station per line, or a temporary local broker.
|
||
- GIS component properties *Apply* increases Edit module memory each time; close the dialog
|
||
and display to recover.
|
||
- Object Selection dialog can hang the Edit module when a section has many objects (DSSSDA at
|
||
high CPU). Type the object name directly; to recover, stop that DSSSDA instance in
|
||
Performance Monitor, close the Edit module, restart CI Server.
|
||
- Enterprise Edit Module: shelved alarm overview shows nothing if added before the alarm
|
||
overview, on another layer, or with different alarm source locations. Add the alarm overview
|
||
first, same layer, same source locations.
|
||
- Alarm overview CI attributes: changing checkboxes on the Attributes tab can reorder the
|
||
Columns tab. Workaround: *Uncheck all* › Apply › re-check › Apply › reorder on Columns › Apply.
|
||
- Engineering module CI attribute names: pick *Add new record* or an existing name from the
|
||
drop-down; cancel the *Add new CI attribute* dialog if it appears unexpectedly.
|
||
- OPC UA alarm event type filters and alarm template settings that are in use can't be
|
||
deleted, and a same-named one on another station also becomes undeletable. Use unique names
|
||
per station; to recover, copy under a new name, repoint, then delete.
|
||
- EALs can't be edited in bulk in the Engineering module. Use `dssqld` on dataset
|
||
`EXTERNAL_ALARM_DF`.
|
||
- Retrieve from archive does not restore alarm attribute databases (alarms visible, attributes not).
|
||
- ODBC writes: Microsoft Access can't write to R1.03.00+; SQL Server Management Studio and
|
||
Excel via ODBC can't either. PowerShell and custom applications can (ODBC DSN
|
||
`CiSimbaClient`, e.g. `UPDATE ITEM_VAL SET ITEM_VALUE_STR=..., STATUS_NUMBER=... WHERE NAME=...`).
|
||
Alternatives: Excel Add-in, or `dssqld` on the Core/Portal.
|
||
- Acknowledging external alarms over ODBC: filter on `NAME` in `ALARM_CURRENT`
|
||
(e.g. `UPDATE ALARM_CURRENT SET ACK = 1 WHERE NAME = '<time>/<id>'`), not
|
||
`ITEM_NAME` / `ALARM_ORIG_TIME`.
|
||
|
||
## CI Exchange tools (1.17, 1.18)
|
||
|
||
- CENTUM VP and Prodigy tools use `jwuiutl`; over RDP, first allow it in `dssana.sup` (see USER).
|
||
- HTML5 conversion warnings about graphics outside the viewing area are harmless; move Generic
|
||
/ JavaScript function components into view and reconvert to silence them.
|
||
- *Illegal reflective access* Java warnings during load are harmless.
|
||
- Folders must not contain Japanese characters (project, CI Exchange project and publish
|
||
folders; `Load.cmd` fails with `UnicodeEncodeError`).
|
||
- `Unknown encoding 'ms932'` from `Load.cmd`: in the publish folder run `chcp 1252`, then `load.cmd`.
|
||
- Loading a publication overwrites VNET station settings (on scan, recover 10 s, slow 5 s,
|
||
medium 3 s, fast 1 s) and line device (`/dev/bk00`). Correct them manually afterwards.
|
||
- RGS with EAL: if both Vnet/IP buses to an FCS are cut, faceplates don't show OFFLINE and keep
|
||
old values. Set the alarm status manually, or map the Vnet communication status to an item.
|
||
- Unsupported controllers (e.g. GSGW, APCS) get stations created but no data. Exclude them in
|
||
the Import Wizard (RGS with EAL), or filter in the Publish Wizard, e.g.
|
||
`TYPE LIKE '%%' AND STATION <> 'FCS0256' AND STATION <> 'FCS0258'`; otherwise delete the
|
||
stations in the Engineering module.
|
||
- Tuning panel SUM is shown even when CENTUM integration is disabled. To reset to 0: disable
|
||
integration in CENTUM, then set SUM to 0 on the CI tuning panel.
|
||
- RGS collecting CENTUM alarms: 30 or more controllers needs +8 GB memory.
|