Full manual diffs (C50, R30, C60, L20, C40, L35, R10, R20, J10, L30, L50, P30, G10, C10) and read-only checks on the shared R1.05 test server where the permission system allowed them. Skills and summaries moved to R1.05. Issues ISS-092..129 (gaps 104-107, 114-115, 130-131 unused); ISS-074 closed (manual and software agree), ISS-091 corrected by ISS-119. version-differences: unlisted manual changes and installed-only changes. r105-verification: V5-V9 and new not-tested rows. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2.4 KiB
2.4 KiB
| task | version | source | status |
|---|---|---|---|
| Create sub-items (integrator, min-max) | R1.05 (first written for R1.03) | IM 36K10G10-01EN 5th ed. (Feb. 2026) §3.1.5, §3.2.3; IM 36K10C10-01EN 5th ed. (Feb. 2026) §3.2; practiced with CI-Eng-Sample 2026-09-30 (R1.03) | verified on R1.03 (2026-09-30); verified (R1.05 test server, 2026-10-08) for loading — the reduced CI-Eng-Sample load created sections, items and both sub-items with 0 errors and LEVEL.MAX followed the level; SUB_ITEM_DF and itm.sup identical to R1.03; integrator rate and the itm_int_secs change not re-tested on R1.05 |
Sub-items
A sub-item hangs under an item (<Section>.<Tag>.<Sub>) and processes the main item's value.
Types: Integrator, Min-Max, Pulse, Rate-of-Change, Typeless. Sub-items cannot connect
to equipment, cannot have sub-items, and are not blocked when the main item is blocked.
Quick load (SUB_ITEM_DF; the main item must exist):
@FIELDS
NAME,DESCRIPTION,SUB_TYPE,TIME_UNIT,MIN_MAX
@SUB_ITEM_DF
"CI-Eng-Sample.PUMP1.RUNNING.RUN_SECONDS","Pump 1 running time (seconds)","Integrator","",""
"CI-Eng-Sample.TANK1.LEVEL.MAX","Tank 1 maximum level","Min-Max","","Maximum"
Load with dssqld -i <file>.qli -l <file>.qlo; remove with a NAME-only file and dssqld -r
(before removing the main item). R1.05 accepts these files unchanged (@VERSION 1.03.00).
Behaviour
- Integrator (verified R1.03) adds value × time unit: with the main item at 1 it grows by
1 per second by default. The time unit is the integration granule
itm_int_secsinitm.sup(Setup File Editor label "Integration granule, sec."), system-wide for all integrators, installed value 1 (same file on R1.05). Setting 60 and restarting CI Server made it grow by 1 per minute (R1.03, 2026-09-30, ISS-010). Changing it is a setup-file change (skillportal-setup, taskchange-setup-file.md); existing integrator values are not converted, so reset or note them.TIME_UNITon the sub-item has no effect on integrators. - Min-Max with
MIN_MAX=Maximum(orMinimum) keeps the highest (lowest) value written to the main item: writing 30, 70, 50 gave 70 (R1.03). On R1.05TANK1.LEVEL.MAXfollowed the rising level (R1.05 test server, 2026-10-08). TIME_UNIT(Second, Minute, Hour, Day; default Day) belongs to Rate-of-Change (from docs, not practiced).
Example files: examples/CI-Eng-Sample/02b_sub_item_df.qli, 90b_remove_sub_item_df.qli.