name: alarm-management
|
|
description: >-
|
|
CI Server R1.03 ALARM Service and alarm engineering. Use when the user wants to switch on
|
|
alarms for an item (alarming, limits, HIGH / HIGH HIGH / LOW alarms, alarm state, priority,
|
|
alarm text), set up acknowledgement types (manual / automatic acknowledgement, ack matrix,
|
|
ALARM_ACK_DF), areas of interest (AOI), alarm selection areas (ASA, alarm filter expressions,
|
|
compile), delayed or repeated alarms, first-out groups, alarm collections (first-up), read or
|
|
acknowledge current alarms and alarm history (ALARM_CURRENT, ALARM_CHRONO), generate a test or
|
|
informational event, check the alarm kernel or storage (ALM, ALH, ALDPRT, almdbg, alhdbg,
|
|
alm.sup, alh.sup, aldprt.sup), configure alarm e-mail / SMS notification (alnmgr, alnsmtp),
|
|
alarm shelving (asbman), alarm sound (aldaco), alarm counting (aldcnt), external alarms (EAL,
|
|
OPC UA alarms, CENTUM VP Vnet alarms) or analyse alarm performance (ASPA, alarm floods, KPIs,
|
|
EEMUA 191, ISA 18.2). Sources IM 36K10L15-01EN, IM 36K10C20-01EN, IM 36K10E30-01EN.
|
|
---
|
|
|
|
# Alarm management (R1.03)
|
|
|
|
Background: `knowledge/manuals/IM36K10L15-01EN.md` (kernel, events, mechanisms, setup files,
|
|
debuggers), `IM36K10C20-01EN.md` (Engineering Module forms, filters, grouping, shelving,
|
|
notifications, external alarms), `IM36K10E30-01EN.md` (ASPA tool and KPI targets). Item limits
|
|
and statuses: skill `item-engineering`. OPC UA alarm sources: skill `data-access`.
|
|
|
|
Rules:
|
|
- Run `system-check` first; follow the user's chosen way of working.
|
|
- **Alarms reach operators.** Switching alarming on or off, changing acknowledgement types, or
|
|
acknowledging alarms on a running plant changes what operators see: only with the user's
|
|
approval. Changing an item's alarm settings also auto-acknowledges a pending return to normal
|
|
(L15 summary, C20 §A2).
|
|
- Writing a value to force a test alarm changes live data (`system-management`, task
|
|
`read-write-item.md`): only on test items, and restore the value.
|
|
- `almdbg` options 3, 13, 15, 17, 19, 20, 25, 26 and `alhdbg` 3, 4 change or stop things:
|
|
never without approval. Read-only options are listed in `tasks/alarm-checks.md`.
|
|
- Setup files (`alm.sup`, `alh.sup`, `aldprt.sup`, `aln*.sup`, `asbman.sup`, `wfladi.sup`) need
|
|
admin rights and a restart: hand changes to the user (skill `portal-setup`, task
|
|
`change-setup-file.md`).
|
|
|
|
| Task | File | Status |
|
|
|---|---|---|
|
|
| Acknowledgement type, area of interest, alarm selection area by quick load; compile check | `tasks/alarm-definitions.md` | verified |
|
|
| Switch on alarming for an item; delay / repeat; test an alarm; read and acknowledge current alarms and history | `tasks/item-alarming.md` | verified |
|
|
| Read-only checks: alarm processes, destinations, statistics, item alarm parameters, storage group, setup files; generate an INFO event | `tasks/alarm-checks.md` | verified |
|
|
| First-out groups, alarm collections (first-up, status/ack/reset items) | C20 summary §A6 | from docs |
|
|
| Alarm overviews, priority labels, link display, shelving | C20 summary §A3, §A9, §A10 | from docs (needs displays, phase 10) |
|
|
| E-mail / SMS notification | L15 summary §10, C20 §A11 | from docs (needs an SMTP server without authentication) |
|
|
| Acoustic (`aldaco`) and count (`aldcnt`) destinations, split storage processes | L15 summary §7, §8 | from docs |
|
|
| External alarms (EAL) from OPC UA servers or CENTUM VP | C20 summary part B | from docs (no A&C source / Vnet on the test system) |
|
|
| Alarm performance analysis (ASPA) | E30 summary | from docs |
|