task version source status
Read-only checks of ALARM Service; generate an informational test event R1.03 IM 36K10L15-01EN §1, §2.6, §3.4, §4.3, §6; IM 36K10C20-01EN §A7; practiced on the test system 2026-10-01 verified

ALARM Service checks

1. Processes and setup files (read-only)

Check How Test system result
Processes tasklist → alm.exe, alh.exe, aldprt.exe, alnmgr.exe, alnsmtp.exe, asbman.exe; durwfp -p ALM -t 0 → 0 = attached All six running (tls\com\alarm_start.cmd)
Kernel setup %TLS_ROOT_PATH%\tls\sup\alm.sup (active lines after !ENDDEFAULT) SYNC_COMM N, SYNC_MSG N, QUESIZE 25000, RECOVER_QUEUE Y, ACK_INFO
Storage setup alh.sup CURP, CURT, CHR, QUESIZE 8000, MAX-SEARCH 5, RECOVER_QUEUE Y, DB-JRNL WAL, DB-SYNC OFF
Alarm printer aldprt.sup FORMAT prio,2,spac,1,type,6,tdef,18,name,40,text,10, EVENTS repeat,info,ackn,alarm,prio,firstup
Overview events wfladi.sup EVENTS alarm,repeat,ackn,deact,info,recov,diag,firstup (no DIRECT)
Notification / shelving alnmgr.sup, alnsmtp.sup, alnsms.sup, asbman.sup Defaults: SMTP localhost, 25, SMS COM1:, SYS_WIDE_SHELF N
History storage group dssqld -e filter 'NAME = "ALH"' on HIS_GROUP_DF Type Alarm, rollover 1 day, lifetime 52 weeks
Definitions dssqld -e <out> -d ALARM_ACK_DF -c (also ALARM_AOI_DF, ALARM_ASA_DF, ALARM_FO_DF, ALARM_FU_DF, ALARM_PRIORITY_DF, EXTERNAL_ALARM_DF, STATUS_DF) Predefined ack types AUTOMATIC, MANUAL, FULLMANUAL and their _EAL variants; everything else is project data

2. Alarm kernel debugger almdbg (read-only options)

Interactive; pipe the answers and end with -1 (from bash, with a timeout):

printf '1\n9\n12\n-1\n' | timeout 20 almdbg
printf '14\n<Section>.<Tag>\n10\n<ack type number>\n-1\n' | timeout 20 almdbg
Option Shows
1 Connected destinations, events sent, overflows (test system: ALH, OPXUAS, ALNMGR, ALDPRT)
5 / 7 / 8 / 23 First-out groups, first-out / continuation items, collections
9 / 10 Ack type numbers / matrix of one type (A automatic, M manual)
11 Items with repeat or delay running
12 Statistics: start time, item-based / non-item-based / external events received, events sent
14 Item alarm parameters: monitoring, diagnostic, ack type number, collection, first-out, repeat, delay

The last -1 makes DURTIM log DUR-W-REM_PROC, Process ALMDBG_<pid> exited unexpectedly in umhlog.log: harmless. A blank answer takes the default shown in brackets; an empty line at the main prompt repeats the previous action — never send blank lines blindly.

3. Storage debugger alhdbg

printf '1\n-1\n' | timeout 10 alhdbg → storage groups with current unit, cell and start time (test system: group 3, unit 80). Option 2 lists the units of one group. Options 3 (force connect) and 4 (stop ALH) only with approval.

4. Generate an informational test event (almdbg 16)

Changes the alarm history (adds one INFO event; no effect on current alarms). With approval:

printf '16\n\n0\n15\n<Section>.<Tag>\n<status text>\n<description>\n-1\n' | timeout 15 almdbg

Prompts: timestamp (blank = now), milliseconds, priority (0–15), name, status text, description. Check with a filter 'EVENT_TYPE = "INFO"' on ALARM_CHRONO.

Verified: the event appears with EVENT_TYPE INFO, ITEM_NAME = the given name, ALARM_TEXT = status text, DESCRIPTION = description, priority 15, ack 1. Other text columns (INSTALL, UNIT, SUB, SOURCE, CATEGORY, CONDITION) contain leftovers or unreadable characters (ISS-037): use the event only as a test marker.