| OPC UA client to an OPC UA server by quick load (loopback to CI Server's own OPC UA server) | R1.03 | IM 36K10L45-01EN §9, §10; IM 36K10E20-01EN §2; practiced on CI-Eng-Sample 2026-10-01 (station CIENG_UA; full remove/reload; point also configured in the Engineering Module by the user and compared) | verified |
OPC UA client to an OPC UA server
Worked example: CI-Eng-Sample station CIENG_UA, CI Server's OPC UA client reading
CI-Eng-Sample.TANK1.LEVEL back through CI Server's own OPC UA server
(examples/CI-Eng-Sample/12_–15_*.qli, removal 76_–78_). For a real server, replace the
endpoint, security settings and node IDs.
1. Server side: make the data visible
On the CI Server OPC UA server an item is reachable only when the item has OPC visible and
Read (Write to allow writing) and every parent section is OPC visible
(12_opc_visible_df.qli, loaded with dssqld -m):
@FIELDS
NAME,OPC_VISIBLE
@SECTION_DF
"CI-Eng-Sample",1
"CI-Eng-Sample.TANK1",1
@FIELDS
NAME,OPC_VISIBLE,OPC_READ,OPC_WRITE
@ITEM_DF
"CI-Eng-Sample.TANK1.LEVEL",1,1,0
Visible without Read: the item shows when browsing, but browsing into it fails
(UncertainNotAllNodesAvailable, client message OPXC-E-BRW_NODE; verified). By the manual,
Read is also what allows reading the value.
These flags also apply to the OPC DA and A&E servers.
2. Client configuration (quick load, in this order)
- Line (
OPCUAC_LINE_DF): loading it creates and starts the client processEQUIPMENT_MAN(must start withOPX, ≤ 11 characters) — wait ~10 s before the station."CIENG_UA_LINE","CI-Eng-Sample OPC UA loopback line","OPXCIENG" - Station (
OPCUAC_STATION_DF), subscription (OPCUAC_SUBSCRIPTION_DF, name<station>:<subscription>), points (OPCUAC_POINT_DF, name<station>:<point>) — see14_opcua_station_df.qli:- Station:
LINE,USER_ANONYMOUS1 (orUSER_NAME/USER_PASSWORD),MSG_SECURITY_01_MODESignAndEncrypt,MSG_SECURITY_01_POLICYBasic256Sha256,SERVER_01_ENDPOINTopc.tcp://localhost:34493,STATUS_ITEM(Boolean item, 1 = connected).SERVER_01_NAME/_URImay stay empty. - Subscription:
REQUESTED_PUBLISH_INTERVAL1000. - Point:
SUBSCRIPTION,EXTERNAL_RELATION(Input,Output,Input + Output),OPC_NAMESPACE(namespace URI, not index),OPC_NODE_ID_TYPE(STRING,NUMERIC,GUID),OPC_NODE_ID.
- Station:
- Items (
ITEM_DFwithSTATIONandPOINT), e.g.CI-Eng-Sample.UA.LEVEL_COPY→CIENG_UA,LEVEL.
3. Node IDs
| Target | Namespace | Type | Node ID |
|---|---|---|---|
| Value of a CI Server item (by name — survives recreating the item) | urn:Yokogawa:CI_SERVER_OPC_UA_SERVER |
STRING | {"0":"Value","itnm":"<Section>.<Tag>"} |
| Value of a CI Server item (by namespace id) | same | STRING | {"0":"Value","nsid":"<n>"} |
| Server state (any OPC UA server; good connection test, 0 = Running) | http://opcfoundation.org/UA/ |
NUMERIC | 2259 |
In a .qli file double the quotes inside the field:
"{""0"":""Value"",""itnm"":""CI-Eng-Sample.TANK1.LEVEL""}".
Pitfalls found on the test system:
- Namespace
http://www.yokogawa.com/CI_Server/(the one the manual shows) holds only the types; with it the point is silently not monitored (ISS-032). - In the Engineering Module's Browse path, expand the item and pick its
Valuenode (Objects/<Section>/…/<Tag>/Value, node ID{"0":"Value","nsid":"<n>"}); verified by the user: Last value and Data type filled at once. Picking the item itself stores the object ({"nsid":"<n>"}), which has no value (status 13, never monitored) (ISS-033). For quick load prefer{"0":"Value","itnm":"<item>"}: it does not depend onnsid. nsidnumbers change when the item is deleted and created again (e.g. sample reload).
A point that is not accepted shows REVISED_SAMPLING_INTERVAL 0 in OPCUAC_POINT_DF and the
log line Can't find Point [<point>] in subscription when changed; a monitored point gets the
revised interval (e.g. 1000).
Browse the server from the command line (station connected): export OPCUAC_TAG_DF with
a filter; start with an empty path, then Objects:
@SELECT
'OPC_STATION_NAME = "CIENG_UA" and OPC_TAG_PATH = "Objects"'
@OPCUAC_TAG_DF
Each record shows display name, namespace URI and node ID (inside OPC_TAG_INFO). Deeper
paths were not found yet (Objects.CI-Eng-Sample returned nothing).
4. Certificate exchange (first connection; the user does it)
| Step | Where it shows | What the user does |
|---|---|---|
| 1. Client rejects the server | OPXC-E-CER_NO_TRU … BadCertificateUntrusted in umhlog.log; file <thumbprint>.der in %TLS_ALLUSERS_PATH%\pki\opxuac\pkiclient\rejected |
Trust it: Engineering Module OPC UA Client → Certificates → Rejected → Trusted, or move the file to …\pkiclient\trusted\certs |
| 2. Server rejects the client | client log BadSecurityChecksFailed; file CI_SERVER_OPCUA_CLIENT_<PROCESS> [<thumbprint>].der in …\pki\opxuas\pkiserver\rejected (folder created now) |
Move it to …\pki\opxuas\pkiserver\trusted\certs |
PowerShell: file names with [ ] need -LiteralPath, otherwise Move-Item silently does
nothing:
Move-Item -LiteralPath "<rejected folder>\<file>.der" -Destination "<trusted folder>\"
The client retries every ~35 s (OPXC_STATION_CON_TRY_INTERVAL 30 s); then OPXC-I-SRV_CONN
and the status item goes to 1. Certificates and trust stay when the line is removed and loaded
again (verified: reload connected within 5 s without a new exchange). For an external server,
its certificate arrives the same way; the client certificate
(…\pkiclient\own\certs\<host>_<PROCESS>.der) must be trusted on that server.
5. Check
itmval -g -n CI-Eng-Sample.UA.COMM_OK→ 1;UA.SRV_STATE→ 0 status 9;UA.LEVEL_COPYfollowsTANK1.LEVELwithin ~1 s (verified 55, 62.5, 71, 33, 44.4).- Client log:
%TLS_LOG_PATH%\<PROCESS>.log(Successfully connected station, errors with status codes); server logsOPXUAS.log,OpxUas_Sdk.log(CreateMonitoredItems). - Off-scan/on-scan:
OPCUAC_STATION_DFON_SCAN0/1 withdssqld -mdisconnects/reconnects.
6. Remove
Items (76_), then points, subscription, station (77_), then the line (78_, stops the
client process). Reset the OPC flags only if they were not there before.