3.2 KiB
| manual | title | edition | version | status |
|---|---|---|---|---|
| IM 36K10C60-01EN | Advanced Operating Graphics | 3rd Edition, Sep. 2023 | R1.03 | from docs; installed AOG displays checked read-only (DEPLOY\displays, mobileoperator) 2026-10-01 |
Advanced Operating Graphics — AOG library (R1.03)
A ready-made library of symbols and displays in a consistent, high-performance HMI style, used from the Edit Module's Visualization sheet. Section numbers refer to the manual.
1. Symbols (§1.1)
| Kind | Purpose | Palettes / examples |
|---|---|---|
| Equipment symbols | Static equipment, no live data | AOG_ContainersAndVessels (AOG_Tank, AOG_Vessel, AOG_Reactor, …), AOG_HeatTransfer, AOG_Indicator, AOG_MaterialHandling, AOG_Mixing, AOG_Rotating (pumps, compressors, turbine), AOG_Separators, AOG_ValvesAndActuators, AOG_Electrical, AOG_Filters, AOG_Others (Yokogawa systems such as AOG_CentumFCS, AOG_ProsafeRS, AOG_StardomFCN, AOG_FAM3, AOG_DTS; field devices; stations) |
| Item symbols | Show and change one or more item attributes | indicators (bar, needle, circular, radial, number, text, on/off, manual, alarm, trend), valves (2-way, 3-way, on/off), selection box, name/info |
Object symbols (AOG_O…) |
Same, driven by PROCESS Service object signals | e.g. AOG_ONumberIndicator, AOG_OHorizontalBarIndicator |
| Navigation symbol, components | Navigation between displays |
2. Displays (§1.2)
Standard displays: AOG_Default, AOG_DisplayTemplate (start for new displays), AOG_Style
(global style parameters), AOG_MenuMain, alarm displays (AOG_AlarmBanner, AOG_AlarmCurrent,
AOG_AlarmHistory, AOG_AlarmShelved), AOG_AuditTrail, AOG_ItemFaceplate,
AOG_ItemTuningPanel, AOG_ObjectFaceplate, AOG_ObjectTuningPanel, AOG_SetItemMode,
AOG_SetObjectMode, AOG_SetNumberPV/SV/SL/SH/SLL/SHH, AOG_LockStatus, AOG_TrendOpen,
OPC UA method call displays; plus demo displays. Installed: these are in
DEPLOY\displays, and the alarm, audit, default, menu, style, trend and UA method displays also
exist as HTML displays.
3. Global style parameters (§1.1, §2.1.1)
Defined once on the AOG_Style display (Parameters tab) and used by all AOG symbols:
colours (AOG_C…: alarm high/medium/low/diagnostic/off, display background, equipment
running/off/not running, fluid and gas lines, indicator background/limit/normal/outline/signal,
manual control, selector, text 1–4), strokes (AOG_S…), fonts (AOG_FT1–4), engineering unit
texts (AOG_EF1 flow, AOG_EL1 level, AOG_EP1 pressure, AOG_ET1/2 temperature), on/off
texts, AOG_BlinkOnNotAcknowledged. Changing a value changes every symbol that uses it.
4. Building an HMI (§2)
Edit Module → (optionally) adjust AOG_Style and save → New display or start from
AOG_DisplayTemplate → place AOG symbols from the Visualization sheet → connect them to items
or objects → save → open in the operator interface. New symbols can be made in the same style.
5. Enterprise (§3)
Enterprise displays and AOG item/object symbols for enterprise engineering (items/objects on several servers; locations chosen per symbol).
Not practiced: the sample display uses plain components; AOG symbols need the Edit Module GUI.