ci-server-engineer/.claude/skills/data-access/SKILL.md
cliu 39e58af2ff R1.05 V4: reduced CI-Eng-Sample load tested and removed on shared server
Classes, sub-items, Modbus loopback and OPC UA loopback pass on R1.05.
New examples/CI-Eng-Sample/shared/: snapshot, reduced load/remove,
test and DSS temp-file cleanup scripts for shared servers. Before/after
snapshot identical; ISS-091 (dss_*.tmp left in tls\lst); ISS-080 note.
Certificate files of the test await deletion by the user.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-08 19:10:26 +11:00

5 KiB
Raw Blame History

name description
data-access CI Server R1.05 ACCESS Service: OPC UA, OPC DA, OPC A&E, ODBC and the RESTful API. Use when the user wants to connect CI Server to an OPC UA server (OPC UA client line, station, subscription, points, certificates, node IDs, browse, OPC UA methods MTD_KEY / MTD_TRG, OPCUAC_METHOD_CALL2_DF), let another application read CI Server data over OPC UA, OPC DA or OPC A&E (CI Server as OPC server, OPC visible / read / write, port 34493, endpoints, security policy, trusting client certificates, UaExpert, extended OPC UA functions for alarms, history and PubSub, OPC UA Information Model Mapper, NodeSet / imported information model), check why an OPC connection fails (BadCertificateUntrusted, BadSecurityChecksFailed, item stays NOT INIT, certificate expiry warning), configure DCOM or DCOM tunnelling for OPC Classic, use ODBC / SimbaClient / SQL on datasets, or check the ODBC server (odbsrv, port 1583, SSL certificate), use the RESTful API (jrstsrv, port 34597, API key, x-api-key), or copy item values and timestamps into Microsoft SQL Server with RDBMS data exposure (dbc.sup, DEM_CONNECTION, DBCSND, DBCDEM, DATA_EXPOSURE_DF, data exposure aggregation interval AGG_INTERVAL, ITEM_VALUES, SQL login, DSS-E-FLT_SYN_ERR). Sources IM 36K10L45-01EN, IM 36K10E20-01EN, IM 36K10G10-01EN ch. 10.

Data access: OPC, ODBC, RESTful API and RDBMS data exposure (R1.05; first written for R1.03)

Background: knowledge/manuals/IM36K10L45-01EN.md (ODBC, RESTful API, OPC DA/A&E/UA client and server, setup files), IM36K10E20-01EN.md (Engineering Module forms, certificates, Information Model Mapper, PubSub). Equipment lines/stations/points in general: skill equipment.

Rules:

  • Run system-check first; follow the user's chosen way of working.
  • Trusting certificates is the user's decision. Show the certificate (folder, file name, common name) and let the user trust it (Engineering Module or moving the file); do not move certificate files yourself.
  • Making items OPC visible / writable exposes them to every OPC client on the network: only with the user's approval, and prefer read-only. The same applies to the RESTful API (keep its read-only mode, the product default, unless the user decides otherwise).
  • Never connect a CI Server OPC DA or A&E client to the same node's (or a DURM-connected node's) DA/A&E server: deadlock (IM 36K10L45 5th ed. §6.3). The OPC UA loopback is fine.
  • Extended OPC UA functions are off by default since R1.04. The OPC UA server offers only Data Access and methods unless OPXUAS_ENABLE_EXTENDED_FUNC = YES in opxuas.sup (needed for Alarms & Conditions, HistoryRead and PubSub); the OPC UA client receives no alarms unless OPXC_ENABLE_EXTENDED_FUNC = YES in its <process>.sup. Both are NO on the R1.05 test server (verified 2026-10-08). Source: IM 36K10L45 5th ed. ch. 11 intro, §10.4, §10.11, §11.6.2, App. 1.3.
  • Changing opxsys.sup, opxuas.sup, <process>.sup, odbsrv.sup, jrstsrv.sup or ServerConfig.xml needs admin rights and a restart: hand it to the user (skill portal-setup, task change-setup-file.md).
  • The same applies to dbc.sup (RDBMS data exposure). SQL Server changes (mixed mode, logins, jobs) are on another system: only with the user's and the SQL Server owner's agreement.
Task File Status
OPC UA client to an OPC UA server (sample: loopback to CI Server's own server): line, station, subscription, points, certificate exchange, node IDs, browse via dataset tasks/opcua-client.md verified on R1.03 and R1.05 (loopback re-tested 2026-10-08)
Make CI Server data available to OPC clients (OPC visible / Read / Write); CI Server OPC UA server endpoints, node IDs, certificates tasks/opcua-client.md §1, §5 verified on R1.03 (UA); DA/A&E from docs
Read-only checks: ACCESS processes, ports (34493, 1583, 34597), OPC UA server config and PKI, extended functions, certificate validity, ODBC server state tasks/access-checks.md verified on R1.05 (2026-10-08)
OPC UA client methods (MTD_* object, method form, CIX_UAC_MTD point) and R1.03 → R1.04 method upgrade tasks/opcua-client.md §7 from docs
OPC DA / A&E client and server, DCOM, DCOM tunnelling L45 summary §3–§5 from docs (DA loopback not allowed)
ODBC with SimbaClient L45 summary §1 from docs; ODBC server not running on the R1.03 and R1.05 test systems (ISS-008)
RESTful API (jrstsrv, port 34597, API key, functions) L45 summary §9 from docs; port and setup keywords verified on R1.05
OPC UA alarms (external alarms), model change events, PubSub, imported information model / Information Model Mapper L45 summary §6–§7, E20 summary §2–§5 from docs
RDBMS data exposure to SQL Server: SQL login, dbc.sup DEM_CONNECTION, DATA_EXPOSURE_DF (filter syntax), item aggregation interval, checks, table behaviour, SQL-side retention tasks/rdbms-exposure.md tested in R1.05 only (ITEM_VALUES); ITEM_HISTORY / ITEM_INPUTS not tested