New skill reporting: REPORT Service checks, interactive RQL, report definitions by quick load, file output devices. New task system-management/dss-tools.md: DSS processes, dss.sup, quick load directives, dssutl, DSS compiler syntax check. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2.9 KiB
| task | version | source | status |
|---|---|---|---|
| Send reports to a file - printer device and destination | R1.03 | IM 36K10C30-01EN §2.2; IM 36K10L50-01EN App. 1 (PRINTER_*); practiced on CI-Eng-Sample 2026-10-01 | verified |
Report output devices and destinations
A report goes to a destination (PRINTER_DEST_DF), which sends it to a primary (and optional
secondary) device (PRINTER_DEV_DF). Devices: FILE, HARDCOPY (Windows printer queue),
APPLICATION. Engineering Module: Configuration > Reporting > Printers > Device / Destinations.
The printer manager is FMFPRT.
1. Find the output types of this node
dssqld -e types.csv -d PRINTER_TYPE_DF -c
Names are <node>:FILE, <node>:HARDCOPY, <node>:APPLICATION (<node> = CI Server node name,
NODE_NAME in LOCAL_NODE_DF, e.g. UNLICENCED on an unlicensed system). A device needs the full
name; plain FILE is refused (DSSP-E-NORELV).
2. File device and destination
@FIELDS
NAME,DESCRIPTION,OUTPUT_TYPE,PARAMETERS,SUSPEND
@PRINTER_DEV_DF
"<DEVICE>","Report file","<node>:FILE","PATH,""<folder>"",FILE,""<file>.txt"",OVERWRITE,""Yes""",0
@FIELDS
NAME,DESCRIPTION,PRIMARY_DEVICE,POLICY,ALLOW_OPERATOR,PRIORITY
@PRINTER_DEST_DF
"<DEST>","Report file","<DEVICE>","None",1,0
dssqld -i. <folder> must be a literal path that exists (no %variables%: FSL-E-PRT_PAR, Invalid device parameter in umhlog.log). OVERWRITE "Yes" keeps one file with the latest
report ("No" not tried). ALLOW_OPERATOR 1 also lists the destination in
PRINTER_OPER_DEST_DF (needed for ADHOC_DEST and the operator's generate/print dialogs).
CI-Eng-Sample builds this file at load time from 17_printer_df.tpl (node name and
%TLS_LST_PATH% filled in by 17_printer_df.ps1).
Printer instead of file: OUTPUT_TYPE <node>:HARDCOPY, PARAMETERS
TYPE,"WINDOWS",QUEUE,"\\<server>\<printer>" (+ FONT, POINT, LINES, ORIENTATION) — not
practiced (no printer).
3. Use it
Set DEST_NAME (scheduled/triggered runs) and ADHOC_DEST (ad-hoc runs) of the report to
<DEST>, or print a generated report (define-reports.md §4).
4. Check
dssqld -e jobs.csv -d PRINTER_JOB_OVV -c (job, file, submitter, status, destination, device)
dssqld -e devs.csv -d PRINTER_DEV_OVV -c (device status, e.g. Ready)
A job can show Finished even when the device failed; also read %TLS_LOG_PATH%\umhlog.log
(From: FMFPRT, FSL-E-…). The output file holds the text report as generated (HTML reports as
HTML source).
5. Remove
Remove (or repoint) the reports that use the destination, then the destination, then the device
(DSSP-E-NODEL … still in use otherwise). The output file is not deleted.
Verified (2026-10-01)
CIENG_FILE (UNLICENCED:FILE, C:\Users\Public\Yokogawa\tls\lst\cieng_report.txt, overwrite):
printed generated reports, scheduled, triggered and ad-hoc runs wrote the file; jobs Finished,
device Ready; %TLS_LST_PATH% in the path failed as above.