ci-server-engineer/knowledge/progress.md
cliu bf7d88a027 R1.05 re-check batch 3: alarms, audit, authorization, classes, HAC, reporting, pyTOOLS
Full manual diffs (L15, C20, E30, L25, J40, C10 §2, L10, P10, P11, J20,
C30, P20, R40, E10) and read-only checks on the shared R1.05 test server.
Skills and summaries moved to R1.05; new skill pytools (IM 36K10P40) from
docs (no Python on the test server). Issues ISS-132..181; corrections to
version-differences (E10, E30, P11, dss_ath_grp_u0104); C10 summary lists
the 3 new authorization actions; r105-verification V10-V17.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-09 10:21:36 +11:00

44 KiB
Raw Blame History

Progress

Status of each manual and each practiced task. Update this file as work proceeds.

Manual status: not started · summarized · in practice · done Task status: not practiced · practiced, awaiting confirmation · passed · not completed (see notes) Sample column: whether the task has been re-tested on CI-Eng-Sample: n/a (needs no project data) · pending (tested on AID only) · added (sample content built) · passed

A task is done only when Status is passed and Sample is passed or n/a. Then AID is no longer needed to repeat it.

Test system

Practice notes refer to the repo author's development test system, not to anything shipped with this repo:

  • R1.03 work (phases 0–13): CI Server R1.03.00, unlicensed, on the development machine.
  • R1.05 work (from 2026-10-08): CI Server R1.05.00, licensed, on a remote test server reached by ssh. The server is shared with other projects: checks there are read-only unless the user approves a change; no CI Server restarts; never touch other projects' records or live plant values; check query user and recent audit-trail writes before a test that changes anything; remove scratch files afterwards. Loading CI-Eng-Sample there needs the user's approval first.
  • AID (e.g. AID.WRPS.SIM.INFLOW) is the author's own test project on that machine. It is not in this repo and other systems will not have it. Item names here are evidence of what was tested, not names to use elsewhere.
  • Communication stations seen there (WRPS_PLC, MODSIM_STATION, STN_MQTT) belong to AID.

Tasks may be practiced first on AID, but everything they need is then added to the sample project CI-Eng-Sample (examples/CI-Eng-Sample/) and re-tested there, so that in the end AID is not needed.

R1.05 re-check

main moved to R1.05 on 2026-10-08; the R1.03 state is frozen on branch r1.03 (tag r1.03-final). All the status below was reached on R1.03. Each skill is re-checked on R1.05 in the order of version-differences.md §3. Then its front matter gets version: R1.05 and its row here is updated.

R1.05 status: not started · manual diff read · re-checked (read-only) · re-tested · done

Two labels for checks Claude cannot do (details and steps in r105-verification.md): not tested = the function is not available on the R1.05 test server (reason given); awaiting user verification = Claude prepared the step and the user runs it on the server or in the GUI and sends the output or a screenshot.

Skill / area Manual changes after R1.03 R1.05 status Notes
system-check — re-checked (read-only) Version, paths, service, node, time on the R1.05 test server 2026-10-08. Start/stop not repeated (shared server).
installation-security C10, C30 (large: IT security 3.0, LAPS, upgrade merge jupgutl, PRM) re-checked (read-only) 2026-10-08: skill, summaries and tools/setup_check.ps1 updated to R1.05. Setup check run by hand on the R1.05 test server. Script run there too (12 OK, 5 CHECK, 20 DIFF; firewall check fixed). Not tested: IT security 2.0/3.0, LAPS, Vnet/IP, upgrade merge, PRM (not available there). ISS-086–090.
data-access L45, E20 (large: REST API, OPC UA methods, information model mapper, certificate expiry, extended functions off by default), L50 dataset rename re-checked (read-only) 2026-10-08: skill and summaries updated, L45 section numbers remapped. Setup files, datasets, ports and certificates checked; Sample qli files unchanged. New form fields confirmed in the installed form definitions (V3); OPC UA loopback re-tested on R1.05 with the reduced sample load (V4, 2026-10-08), certificate exchange done by the user. Not tested: OPC A&E direct alarms, PubSub, imported information model. ISS-080–085.
equipment L41 (IEC 61850, item status, App. 1); IEC 104/61850 drivers moved to eqt/eta re-checked (read-only) 2026-10-08: Modbus datasets, setup files and tools identical to R1.03; EQT family, IEC 61850 report control blocks and upgrade steps added. Sample qli files unchanged. eqpdbg main info run on R1.05 (V1); Modbus loopback re-tested on R1.05 with the reduced sample load (V4, 2026-10-08). Not tested: IEC 104 / IEC 61850 and the EQT tools (no device). ISS-076–079.
pytools (new) P40 new (R1.04; 2nd ed. layout only) written (from docs) 2026-10-09: SKILL.md + 5 tasks (setup and first script, items and history, filter/index, events, modify) and the P40 summary. Verified read-only on R1.05: dss.pyd 3.6.1, DSSSDAPY, dss.sup routing, Python Interface login lines. Not tested: every function (no Python on the R1.05 test server, ISS-178). Awaiting user verification: V17. ISS-174–181.
graphics C50, C60, R30; unlisted: Generic Functions rename, enterprise on the HTML display, R30 §4.10 restrictions re-checked (from docs) 2026-10-08: full diff, skill and summaries moved to R1.05. No display or layout touched on the shared server. Awaiting user verification: installed-file comparison, jwuiutl --help, web trend pen limit (V5; ISS-092, 094, 096, 097). Not tested: enterprise HTML display, RDP Connect, Password Check, custom acknowledgement (ISS-093, 098, 099).
history-management C40 §4.2 (REST API, pyTOOLS; C API dropped); L20, L35 wording only re-checked (from docs and file hashes) 2026-10-08: history setup files and dataset definitions identical to R1.03; REST/pyTOOLS cross-linked to data-access / P40. Awaiting user verification: hisdbg read-only options and the changed start scripts (V6; ISS-100, 101). Not tested: storage groups, aggregation, ITEM_HISTORY reads (restart needed, ISS-103); archive. Note: tlsdnetapi.dll (.NET API) is no longer in tls\exe on R1.05.
portal-setup R10 §3.1 ISO, §3.3; R20 punctuation only re-checked (read-only) 2026-10-08: setup-file reads, web ports 8080/8443, Remote Connect page, security headers and CSP verified on R1.05; new jwuiisg.sup keywords and dur.sup gateway core documented (ISS-108–111). Awaiting user verification: Setup File Editor GUI (V7; ISS-112, 113). Not tested: separate CI Portal node, gateway core, setup-file changes (shared server), CSP effect on displays.
system-management J10 §2.9.1, new §3.2.6 gateway (unlisted), §5.1; L30 wording; L50 dataset rename; P30 none re-checked (read-only) 2026-10-08: exports, filters, -f, dsschk -e -v, durwfp, umhman, itmval -g, itmdbg, DSS compiler check re-tested on R1.05; dssqld -i/-r, itmval -p from the sample test (V4). ISS-116–123. Awaiting user verification: ithloahis (needs the full sample with history), start-script hooks (V8; ISS-121). Not tested: monitoring processes, gateway core.
item-engineering C10 §2.2; unlisted: C10 §1.1 Tools menu, string length 200 bytes (C10, G10); G10 §9.2, ch. 14–15 re-checked (read-only) 2026-10-08: item/section/sub-item definitions and itm.sup identical to R1.03; ITEM_VAL has 3 new fields (ISS-126); sample items and sub-items loaded and worked on R1.05 (V4). Awaiting decision: blocking and string writes on the shared server (V9; ISS-129). Not tested: G10 ch. 14–15 (no CENTUM VP, ISS-127).
alarm-management none listed; unlisted E30 KPI labels and corrected chart (ISS-132) re-checked (read-only) 2026-10-09: setup files, templates and definitions identical to R1.03 except the start-script hooks, alnsms.sup defaults (ISS-134) and internal ALARM_ATTRIBUTE_TEMP_DF (ISS-133); almdbg/alhdbg read-only, ALH 52 weeks default (ISS-135); load rule for the shared server (ISS-136). Awaiting user verification: alarm raise/ack/delay/repeat, INFO event (V10). Not tested: external alarms, notification, shelving, ASPA GUI, custom acknowledgement.
audit-trail none (full diff clean) re-checked (read-only) 2026-10-09: processes, ADT group, 499 classifiers (36 new, ISS-141), definitions, setup files and scripts compared; RQL read of AUDIT_TRAIL; APPROVAL_REASON/APPROVER present and filled (ISS-140); hooks (ISS-142). Awaiting user verification: ADTLOG with the new units, selection on approval fields, custom acknowledgement record (V11). Not tested: PENDING (no Vnet), classifier STORAGE change.
authorization none (J40 contact info only; C10 §2 CI_NO_LOGIN) re-checked (read-only) 2026-10-09: dssana.sup all tabs, USER/AUTH/SCHEME/API_KEYS definitions, 203 actions (ISS-146), 250 action fields and upgrade tool (ISS-147), new login interfaces (ISS-148), API keys (ISS-151), AD/SSO files (ISS-153). Awaiting user verification: MAX_UI_PER_CLIENT (V16), Add API Key GUI, users/groups and ISS-072/073 on a non-shared system (ISS-152). Not tested: AD, SPNEGO, upgrade merge (ISS-149).
class-object-engineering none listed; unlisted P11 §10.2 createSection fix (ISS-154) re-checked (read-only) 2026-10-09: definitions, opc.sup, prc.sup, templates and public Java API identical; Java 11.0.28, tls\exe\lib, hooks (ISS-156); OPC UA method system classes preinstalled (ISS-155); undocumented Java methods (ISS-159); opcdbg database check and OPCEXE1 info OK. Awaiting user verification: OPCJEXE statistics (V14). Awaiting decision: change/reset class re-test (V15). Sample classes CIENG_INCR, CIENG_TANK (traditional) and CIENG_JFLOW (Java) loaded and ran correctly on R1.05 (V4, 2026-10-08).
high-availability none (J20 contact info only) re-checked (read-only) 2026-10-09: HAC files compared (ISS-161), activate/deactivate hooks (ISS-160), A50 PubSub precaution (ISS-162); hac-checks read-only on R1.05 (single server). Not tested: redundant pair, switchover, mirror, history merge, recovery, journaling (no licensed pair).
reporting none listed (E10 one sentence removed, ISS-166) re-checked (read-only) 2026-10-09: report definitions, setup and .rpt files identical; hooks (ISS-121); 28 system reports, 6 factory destinations; interactive RQL re-run, new ITEM_VAL fields (ISS-126, 167); API_KEYS_DF not queried (ISS-168). Awaiting user verification: generate/print/delete, item trigger, rptstp, SPOOL (V12). Not tested: Excel Add-in (no Office), report component, hardcopy printers.
examples/CI-Eng-Sample — re-tested Reduced load (no history group, user or layouts) loaded, tested and removed on the shared R1.05 server 2026-10-08 (V4); scripts in shared\. Full load not tested on R1.05.

Manuals, in working order

Phase Manual Title Status
0 IM 36K01A50 Release Information summarized (notes)
1 IM 36K10J10 System Design/Management done except migration (not practiced; needs a second system) and debugging tools; skill system-management (notes)
2 IM 36K01C10 CI Server Setup summarized (notes); skill installation-security
2 IM 36K01C30 Security Guide summarized (notes); skill installation-security
3 IM 36K10G10 Tutorial summarized (notes); command-line equivalents practiced on CI-Eng-Sample
4 IM 36K10R10 CI Portal Setup done except separate CI Portal node (needs a second node); skill portal-setup (notes)
4 IM 36K10R20 Setup File Editor done; Templates tab and Undo Field not explored (notes, ISS-016)
5 IM 36K10C10 Engineering Module - I/O Processes summarized (notes); default datasets checked read-only
5 IM 36K10L40 EQUIPMENT Service - Utilities summarized (notes); eqpdbg main info run read-only
5 IM 36K10L41 EQUIPMENT Service - Configuration summarized (notes); general + Modbus in detail, other drivers as a table
5 IM 36K10L35 ITEM Service - ITH summarized (notes); installed processes and setup files checked
5 IM 36K10L36 ITEM Service - ITM summarized (notes); itmdbg statistics run; itmval -f crashes (ISS-022)
6 IM 36K10L10 Class/Object Engineering done; opc.sup read-only, opcdbg read-only actions and Reset class practiced (notes); skill class-object-engineering
6 IM 36K10P10 Class Description Language - Traditional done for prompts, signals, created items, transitional operators, PRINT/ERROR; timers, alarms, containment, STEP, DSS routines, AGA from docs (notes)
6 IM 36K10P11 Class Description Language - Java done for a basic class (attach/create items, signal trigger, systemMessage); timers, containment, inheritance from docs (notes)
7 IM 36K10L55 Exchange Tool Engineering summarized, from docs only (needs CENTUM VP / RGS or Prodigy) (notes)
7 IM 36K10L30 BUS Service done for single-node checks; MDUR, encryption, logical addresses, printer devices from docs (notes); task system-management/bus-utilities.md
7 IM 36K10L45 Data Access Engineering done for OPC UA client/server (loopback); OPC DA/A&E from docs (DA loopback not allowed); ODBC not running (ISS-008) (notes); skill data-access
7 IM 36K10E20 OPC Interface summarized; OPC UA point form compared with quick load by the user (notes)
8 IM 36K10L15 Alarm Management Engineering done for item-based alarms (ack type, AOI, ASA, events, acknowledge, delay/repeat, almdbg/alhdbg); first-out, collections, notifications, shelving, acoustic/count destinations from docs (notes); skill alarm-management
8 IM 36K10C20 Engineering Module - Alarms done by quick load for item alarm fields, ack types, AOI, ASA; forms, overviews, shelving, link display, notifications, external/Vnet alarms from docs (notes)
8 IM 36K10E30 Alarm System Performance Analysis summarized, from docs (ASPA GUI not practiced; launcher and fetch limits checked) (notes)
9 IM 36K10L20 History Management Engineering done for hisdbg checks, files and rollover; archive and repair utilities from docs (notes); skill history-management
9 IM 36K10C40 Engineering Module - Historical done by quick load for Event/Item, Scan/Time and Aggregation groups (aggregation needs a higher-priority source group, ISS-040); archive from docs (notes)
10 IM 36K10R30 Graphic Display Setup done for HTML display, folders and layouts (phase 10b: desktop and web); dataset forms, form language, dual screen from docs (notes); skill graphics
10 IM 36K10C50 Edit Module done for one display (built by the user) and jwuiutl validate/search/export; other components, symbols, actions from docs (notes)
10 IM 36K10C60 Advanced Operating Graphics summarized, from docs (AOG displays checked read-only) (notes)
11 IM 36K10L50 Data Set Service Engineering done for DSS processes, dss.sup, quick load directives (macro, include, memo from file), dssutl read; dssana.sup covered by skill authorization (notes); task system-management/dss-tools.md
11 IM 36K10P30 Data Set Service Language summarized; compiler used as syntax check on a copy (no dictionary change) (notes)
11 IM 36K10P20 Report Generation Language done for queries, layout, cursors/loops, functions, SPOOL/CSV, HTML; SEND/RECEIVE, BREAK, INCLUDE, FLAG PAGE from docs (notes); skill reporting
11 IM 36K10R40 Report Server Setup done for processes, set-up files, interactive generator, rptstp; extra generators, separate RPI servers, custom destinations from docs (notes)
11 IM 36K10C30 Engineering Module - Reporting done by quick load for report definitions (ad hoc + parameters, schedule, item trigger, HTML, logbook), generated reports and a file device/destination; Engineering Module forms, generate and view checked by the user; report component in displays and hardcopy printers from docs (notes)
11 IM 36K10E10 Excel Add-in summarized, from docs (Excel not installed on the test system) (notes)
12 IM 36K10L25 Audit Trail Management done for processes, classifiers, AUDIT_TRAIL reading/export, audit report, selection groups, ADTLOG (default and filtered); distributor, extra collectors, classifier extension in C and operator-side ITEM.* events from docs (notes); skill audit-trail
13 IM 36K10J20 High Availability Computing summarized from docs; installed hac.sup, scripts, executables and HMI properties checked read-only (single unlicensed server, HAC not licensed) (notes); skill high-availability
13 IM 36K10J40 Active Directory Integration summarized from docs; installed dssana.sup AD/SSO/login settings, USER_DF fields and auth\WEB-INF templates checked read-only (no domain) (notes); skill authorization
— IM 36K01A10 / A20 / A30 Read Me First, License, OSS terms skipped (no engineering content)

Order change after reading IM 36K10J10: its migration procedure (§5.6) shows the dependency chain communication lines/stations/points → installations/units → items (template items first) → storage groups → classes → objects → reports. So acquisition and items (phase 5) now come before classes and objects (phase 6), and the other interfaces follow as phase 7.

Tasks

Manual Task Status Sample Notes
J10 System check: version, paths, running state, time sync (skill) passed n/a Started CI Service elevated; live version R1.03.00; node UNLICENCED (expected).
J10 Time sync check (w32tm); DURUTL configuration (durutl.sup) passed (check); configuration not practiced n/a w32tm check verified in system-check. durutl.sup has no active settings (single node, not a time master); configuring DURUTL needs a second node, so not practiced.
J10 Export a dataset with dssqld (task) passed n/a Filtered export (@SELECT) passed (ISS-003, closed).
J10 Import and delete dataset records with dssqld (-i, -r) (task) passed passed Built CI-Eng-Sample: 3 sections + 4 items imported, removed and re-imported with 0 errors. 2026-09-30 later: -m (update, used to set a storage group stop time) and loading/removing storage groups passed; see ISS-005.
J10 Read an item with itmval -g (task) passed passed Read AID.WRPS.* items. -a 1..5 gave ITM-E-WRONG_ATT on an item without limits; works on items with limits (ISS-004, closed).
J10 Write an item with itmval -p (task) passed passed Sample: TANK1.INFLOW 120.5 then 130 with -s 9, PUMP1.RUNNING 1 (status 5 BOOLEAN 1); no uoff flag. AID: AID.WRPS.SIM.INFLOW 419.76 → 400 → 419.76. After the first write the item's options gained the uoff flag (0x8a → 0x8e) = updated offline, option bit 4 (written while its station was offline). See ISS-001, closed.
J10 Read the message log (tls\log\umhlog.log) passed n/a
J10 Per-component version list (tls\lst\tls_versions.lst) passed n/a
J10 Load history from CSV with ithloahis; read history back with dssqld (task) passed passed Sample storage group CIENG_EVENT (Event/Item). SCAN file (LEVEL 61–63, INFLOW 101–103) and EVENT file (LEVEL 47, 48) stored and read back via ITEM_HISTORY. New groups need a CI Server restart before they store; samples dated before the current storage unit were not stored (ISS-006).
J10 Consistency check (dsschk, ismchk) (task) passed (check); repair and ismchk not practiced n/a dsschk -e -v (check only) reports each of 228 datasets, no problems. Plain dsschk prints nothing on a single node. ismchk needs a database file name; not run (ISS-002, closed).
J10 Monitoring processes (intmon, intcpumon, intdskmon, inttcpmon, intspawn) (task) passed passed All five worked into CI-Eng-Sample.SYSTEM.* / PUMP1.MODE, started by hand with <exe> -n <name>; setup files restored afterwards. intdskmon reports used %; intspawn command path must be short (ISS-007).
J10 Backup of tls folders not practiced n/a Plan only; the actual backup tool is site-specific.
J10 Migration between systems (§5.6) not practiced added After phase 6 CI-Eng-Sample has every data kind in the chain up to classes/objects (items, points, storage groups, classes, objects). Export with dssqld -e works; the import into a second system is not practiced (no second system).
J10 Tuning checks (read-only) (task) passed n/a Read dur.sup (max processes 250), itm.sup (item pool 650,000 KB) and the automatic health snapshots tls\log\smd_*.log (common memory free, queue use per process, lock collisions). Debug launchers and interactive debuggers not practiced.
C10/C30 Setup check script tools/setup_check.ps1 (task) passed n/a Read-only; 16 OK / 5 CHECK / 15 DIFF on the Win10 Pro test PC (kept as dev PC by decision).
C10 Read ci_start.log and web ports (jwuiisg.sup) passed n/a All services started; SSL error ISS-008.
C10 Start / stop CI Server passed (phase 1) n/a Via the CI Service (elevated). Start-menu shortcuts not used.
C10 New install, reinstall, upgrade, uninstall, licence not practiced n/a Would reinstall or change the test system; only the installed R1.03 is available. Skipped.
C10 Windows settings changes (power, virtual memory, Defender, updates, …) not practiced n/a Test PC kept as a development PC (user decision 2026-09-30); not applied.
C10 Vnet/IP drivers / Vnet/IP Interface Package not practiced n/a No Vnet/IP card; not supported on Windows 10 Pro.
C30 IT Security Tool, Domain Link Management, account utilities not practiced n/a Not installed and not supported on Windows 10 Pro.
G10 Sub-items: Integrator, Min-Max (SUB_ITEM_DF) (task) passed passed Integrator adds value × seconds; TIME_UNIT ignored.
G10 Block / unblock an item (ITEM_DF.BLOCKED via dssqld -m); write with itmval -o (task) passed passed blk flag, writes without -o silently ignored; ublk (updated blocked) after unblock (ISS-001, closed).
G10 Trigger group, class (compile on load), object via quick load (task) passed passed DEMO.COUNTER counts every second; full remove/load cycle clean. Phase 6: three classes and objects in one remove/load cycle, 0 errors. A class that fails to compile is not inserted (DSI-E-OPCCOMERR); error lines appear in LISTING after insert with COMPILE 0 and a compile update (test class removed).
P10/L10 Traditional class with prompt/attribute, signal from SECTION, item created from a template, ERROR check, >=:, PRINT; attribute change via OBJECT_ATTR_VAL (task) passed passed CIENG_TANK / TANK1.CALC: volume 50→100, 82→164; capacity 0 refused; capacity 200→400 took effect on next run; created item and section deleted with the object. % in PRINT cuts the message (ISS-025).
P11 Java class (task) passed passed CIENG_JFLOW / TANK1.JFLOW: inflow 120→2, 90→1.5, systemMessage in umhlog.log from OPCJEXE. Created item keeps the identifier's case (…JFLOW.sPerMin). Worked without a class reset (ISS-029).
L10 Change a class with objects: compile + reset (task) passed passed Old code runs until reset (RESET_REQUIRED 1). opcdbg Reset class works (extra prompt for a report file); dssqld CLASS_DF.RESET does nothing, OBJECT_DF.RESET refused (ISS-028).
L10 opcdbg read-only checks (task) passed passed Database check (one never-compiled foreign class SINUS), get class/object, object status/signals/attributes, executor main info. Dumps are not dssqld-readable (ISS-027).
G10/C10 Authorization group and user creation (task) passed passed Group CIENG_VIEWER (sample file 08_auth_group_df.qli) loaded/removed by Claude; test user CIENG_TEST (no password) loaded by the user, checked and removed. The sample creates no users.
C10 String items: length 1–200, holds length − 1 characters (task) passed passed Tested with temporary CI-Eng-Sample.DEMO.STR* items (removed): 201 rejected; too-long writes cut, status 12 OVERRANGED (ISS-019).
C10 Integrator time unit: integration granule itm_int_secs in itm.sup (task) passed passed 60 → RUN_SECONDS +1 per minute; restored to 1 (file identical to backup), +1 per second again (ISS-010). Elevated restarts run by the user.
G10 Displays, symbols, Operator Interface test display done (phase 10); symbols not practiced display added Display CIENG_Tank built in the Edit Module and checked in the HTML display.
L41/C10 Modbus TCP line, station, scan type, points, connected items by quick load (task) passed passed Loopback to CI Server's own Modbus slave (eqpmdcmem + eqpmdcslvtcp on 5020, started by hand). Line load created and started EQPCIENG; removal stopped it and deleted its files. Write/read-back, off-scan/on-scan checked; full remove/reload from sample files. Protocol must be Open Modbus/TCP (ISS-024). Mirror start files copied to tls\com by the user; after a restart everything came back under the CI Service and the setpoint was re-sent on connect.
G10 Alarms, reports, audit, RDBMS, history alarms (phase 8), history (phase 9), reports (phase 11), audit (phase 12) done; RDBMS passed on a user R1.05 system (see the RDBMS row below) alarms, history, reports, audit added; RDBMS n/a (tested in R1.05 only) Covered in their own phases (7–12); RDBMS added 2026-10-02.
R10/R20 Read a setup file: active settings and keyword help (task) passed n/a Read-only. Compared with the Setup File Editor GUI for wfla_display.sup, wflgdi.sup and all 9 tabs of jwuiisg.sup: fields and values identical. Manual differences logged as ISS-012 to ISS-017 (installed software taken as the reference).
R10 Check web access for CI View: ports, Remote Connect page, DEPLOY folder (task) passed n/a 8080/8443 listening, page 200, six DEPLOY folders.
R10/R20 Change a setup file safely (task) passed n/a jwuiisg.sup HTTP port 8080 → 8081 (text edit, elevated restart): 8081 served the page, 8080 refused; restored, hash identical to backup. Editor: OK writes at once, Reset Field restores the default (ISS-016).
R10 Separate CI Portal node (licence, DURM line, dur.sup host node, copy displays) not practiced n/a Needs a second node.
R10 Login method / login control not practiced n/a Moved to dssana.sup (ISS-017); phase 5 (C10) and 13 (J40).
L45/E20 OPC UA client → own OPC UA server loopback by quick load; certificate exchange; node IDs (task) passed passed Station CIENG_UA (opc.tcp://localhost:34493, Basic256Sha256/SignAndEncrypt): UA.LEVEL_COPY follows TANK1.LEVEL (55, 62.5, 71, 33, 44.4), UA.SRV_STATE 0. Certificates trusted by the user (client side, then server side). Entity namespace urn:Yokogawa:CI_SERVER_OPC_UA_SERVER found by browsing OPCUAC_TAG_DF (ISS-032). Full remove/reload clean, reconnects without a new exchange. User configured a point in the Engineering Module: browse stores the item object, value node must be typed (ISS-033); test item/point removed afterwards.
L45 ACCESS read-only checks: processes, ports, OPC UA server config/PKI, ODBC server (task) passed n/a ISS-008 cause found: odbsrv cannot load its SSL certificate (folder tls\pki\odbsrv missing) and exits.
G10/C10 RDBMS data exposure to SQL Server: SQL login, dbc.sup DEM_CONNECTION, DATA_EXPOSURE_DF, ITEM_DF.AGG_INTERVAL, SQL-side retention job (task) passed (R1.05 only) n/a — tested in R1.05 only (user decision) 2026-10-02 on the user's R1.05.00 system (not the R1.03 dev machine): 49 AID.WRPS.* items at 1 minute into a remote SQL Server 2022; rows survive a CI Server restart; 60-day purge job. Quoted filter field stopped DBCSND (ISS-057); ITEM_HISTORY not tested (ISS-058); SQL login needed (ISS-059); steady-item rows (ISS-060); folder rights (ISS-061). R1.03 dbc.sup and dataset definitions checked read-only (identical).
L30 BUS utilities: durwfp, setup files (dur.sup, durm_1_udp.sup, time_table.sup, fmfprt.sup) (task) passed (read-only) n/a umhman, umhtestprog, umhmsg fail (ISS-030). Unlicensed run-time limit hit and documented (ISS-031).
L30 MDUR node links, encryption, logical addresses, printer devices not practiced n/a Single node, no printer devices.
L55 CI Exchange for CENTUM VP / Prodigy not practiced n/a Needs CENTUM VP (RGS, Vnet/IP) or Prodigy data.
L15/C20 Acknowledgement type, area of interest, alarm selection area by quick load; ASA compile check (task) passed passed CIENG_ACK (MANUAL matrix), CIENG_TANKS, CIENG_TANK1 compiled valid. Description > 78 characters refused; an ASA without spaces is stored with VALID_EXPRESSION 0; an ack type in use cannot be deleted.
L15/C20 Item alarming, test alarm, ALARM_CURRENT / ALARM_CHRONO, acknowledge via dssqld -m on ALARM_CURRENT, delay and repeat (task) passed passed TANK1.LEVEL 85 → HIGH (Alarm 2, prio 2), 95 → HIGH HIGH; acknowledged by NAME/ACK; acknowledged return to normal cleared, unacknowledged one stayed; DELAY 5 s / REPEAT 10 s events as documented. Changing alarm fields auto-acknowledges a pending return to normal. No ALDPRT lines in umhlog.log (ISS-035). Full remove/reload clean.
L15 ALARM Service read-only checks: processes, setup files, almdbg 1/9/10/12/14, alhdbg 1, ALH storage group; INFO event with almdbg 16 (task) passed n/a Destinations ALH, OPXUAS, ALNMGR, ALDPRT. alh.sup extra keywords, ALH lifetime 52 weeks (ISS-036). INFO event stored; some text columns hold leftovers (ISS-037). Two extra INFO events named name were created by a probe with default answers.
L15/C20 First-out groups, alarm collections, shelving, link display, notifications, acoustic/count destinations not practiced n/a Need displays (phase 10), a second alarm item design, an SMTP server or a logged-in sound session.
C20 External alarms (EAL) from OPC UA A&C servers and CENTUM VP not practiced n/a No A&C source or Vnet/IP on the test system.
E30 Alarm System Performance Analysis (ASPA) not practiced n/a GUI; the test system has too little alarm history for meaningful KPIs.
C40 Item storage groups by quick load: Event/Item, Scan/Time, Aggregation; read per group (task) passed passed CIENG_SCAN10S stored LEVEL/INFLOW every 10 s after the restart; CIENG_EVENT stored live writes; restart needed for new groups (ISS-006, closed). CIENG_AGG stayed empty until the scan group got priority 10, then 30-min max 77 / min 33 / avg 52.7 (ISS-040, closed). Full remove/reload with three groups: 0 errors (before the priority field was added; PRIORITY itself verified with dssqld -m).
L20 hisdbg read-only checks and forced rollover (task) passed passed 45 groups, 30 clients; group/unit info; rollover of CIENG_EVENT closed unit 3,1. Extra history types 4 and 36 (ISS-039).
L20/L35 ithloahis into older units (task) passed passed Samples in the active unit or a unit closed after the restart stored; older ones dropped silently (ISS-006); dropped sample became the next unit's initial value (ISS-038).
L20/C40 Archive and retrieve, hasdbg, hisrecover, hiswrn, hisrep by hand not practiced n/a No archive device configured (has.sup); would change history administration.
C50 Build a display in the Edit Module, check the XML (task) passed passed User built CIENG_Tank (HTML mode): text, number field, alarm overview, trend. File stores item name + id; after a sample reload (id 248 → 268) validation still passed and a new session showed live values.
C50/R30 Deploy/remove, jwuiutl HTML export, validate, search; HTML display in the browser (task) passed passed Scripts displays/deploy_displays.cmd / remove_displays.cmd; command-line HTML identical to the Edit Module's. Number field live in the browser; HTML trend draws no line (ISS-041). Browser page reload ends the session; the display menu View > Reload keeps it (user).
R30/C50 Operator layout CIENG_Operator (menu, toolbar, navigation/main/banner frames, status line) added with layout.ps1; navigation display CIENG_Menu; open displays in frames, layouts and the popup layout (task) passed passed Desktop: second 1600 x 900 window, frame navigation and Back, popup on top and minimised with its parent, F11 within taskbar limits; the Operator Interface must be restarted after Layouts.xml changes; factory default layout unchanged for Admin. Web: ?d=CIENG_Tank&l=CIENG_Operator. Status line/command names not in the readme (ISS-042). A stray trend property connection caused a desktop error (ISS-041 update).
R30/C50 Layout parameters one by one on test layouts (LT_*): frames, window options, menu/toolbar/status line, all commands (task §6) passed n/a 2026-10-02. Desktop via jwuipoi -layout, web via &l=; popups, modal, maximumOpen via launcher display LT_Launcher. Tabs on LT_Tabs*. Readme differences and web limits: ISS-062..067. Not tested: print orientation/margins, playback, multi-screen positions, the maximumTabs limit for new tabs. Test layouts need no project data (not added to CI-Eng-Sample).
C50/R30 Trend settings one by one on CIENG_TrendLab (pen source, type, scale, axis, grid, limits; time range, performance, appearance, time axis, legend, pen panel; property sheet listed) (task) passed (desktop) passed 2026-10-02, user confirmed each round with screenshots. Pen limits, pen title and backgroundPaint had no effect (ISS-056). Internal items need trend_feed.ps1 after a restart.
C50/R30 HTML trend: cause of the empty web trend and 50-pen workaround (add_trend_spares.ps1); Micro Trend (task §6) passed (workaround) passed Web code always builds 50 columns (ISS-041). Padded CIENG_TrendLab draws in the browser with a clean legend; web ignores Show in legend (ISS-056). Micro Trend drew once, then blank (ISS-055).
C50/R30 Web check of each trend setting (4 batches on a padded scratch copy, checked in the browser by Claude) (task §6) passed passed 2026-10-02. Works / ignored / different table in the task; matches IM 36K10C50 Table 2.27-28 except timeShift (error message) and Show in legend (ISS-056). A hidden real pen breaks the 50-pen workaround (confirmed).
C50 Remaining trend settings: custom time range, Rendering3dOrt, RenderingCSS (task §4) passed passed 2026-10-02. Custom range on desktop and web (desktop: no live update); 3dOrt draws black lines; CSS mode makes the display unloadable.
R30/C50 Sample operator HMI: 8 generated CIENG_* displays, layouts CIENG_Operator (header, tab set, banner) and CIENG_Popup, live-data feed with server-side Start / Stop (sample README, layouts §6.6) passed passed 2026-10-06 on desktop and web. Replaces CIENG_Tank, CIENG_Menu, CIENG_TrendLab. Tab sets: last child of the frame set (ISS-069), desktop zoom via navigate … stretchDisplay (ISS-070), one layout command at a time (ISS-071), connectionState breaks the web layout (ISS-068).
C50 Writing display XML directly: text size, rounding, arc angles, web item attributes, server-side command, alarm overview columns (task) passed passed 2026-10-06, test display CIENG_Test (removed) on both clients; arc angles clockwise from 3 o'clock on both clients (an earlier note on mirrored angles was wrong); jwuiutl -v re-saves (ISS-075).
C10 Sample user CIENG with empty password via quick load, profile layout and initial display (task) passed passed 2026-10-06: PASSWORD "" needed (ISS-072); web logon uses the profile layout (ISS-074); group removal with an open session stopped DSSSDA03 (ISS-073). Factory group OPERATOR is enough for the server-side Start.
J10/C50 Restart CI Server with the Edit Module open observed n/a Start aborted: JWUIGED<pid> still attached to the BUS Service (ci_start.log); closing the Edit Module fixed it (skill system-check).
R30/C50/C60 Dataset forms, symbols, AOG library, dual screen, per-user layouts not practiced n/a GUI work; user profiles not changed.
R40/C30 REPORT Service checks: processes, set-up files (rptman.sup, rptge1.rpt, rptgen.rpt), system reports, rptstp (task) passed n/a Read-only plus one cancel: rptstp rptge1 stopped the endless-loop test report CIENG_LOOP (removed). 28 system reports; two names differ from the manual (ISS-043).
R40/P20 RQL in the interactive generator (rptgen -s rptgen.rpt), CSV with SPOOL (task) passed passed Piped query files (bash <, PowerShell via cmd /c); @NEXT 0 needed; dates are local-time seconds; LOOP refused interactively (RPT-E-LPNOTAL); aggregated history empty on the test system.
C30/P20 Report definitions by quick load: ad hoc with parameters, daily schedule, item trigger, HTML with cursor loop, logbook; generate, read, print, delete; remove (task) passed passed CIENG_TANK1, CIENG_INFLOW_HI, CIENG_HTML + destination CIENG_FILE; full sample remove/reload 0 errors. Schedule ≥ 10 min, scheduled report not deletable until the schedule is cleared, CORRECT_DAYLIGHT (ISS-044); dssqld ad hoc without ADHOC_DEST logs a print error (ISS-045). User checked the Engineering Module: forms, generate dialog (item browser not filtered, ISS-048), view of text and HTML reports.
C30 File printer device and destination (task) passed passed Output type needs the node name (<node>:FILE); literal path only (%TLS_LST_PATH% failed). Sample builds the file at load (17_printer_df.ps1).
L50/P30 DSS tools: processes, dss.sup, quick load macro/include/memo file, dssutl read, DSS compiler syntax check (task) passed n/a Memo from file: absolute path ≤ 82 characters only (ISS-046). Dictionary untouched.
C30 Report component on a display, hardcopy printer, extra report generators not practiced n/a GUI / no printer / admin restart.
E10 Excel Add-in (DART) not practiced n/a Excel not installed on the test system.
J20 HAC checks: licence, processes, hac.sup, scripts, HMI properties, logs (task) passed (read-only) n/a No hacini.sup, normal ci_start, CI_PRIM unset: HAC not used; template hac.sup differs from the manual (ISS-053).
J20 Redundant pair set-up, switchover, patching; stand-alone Recovery and journaling (task, task) not practiced n/a Needs two licensed servers; stand-alone Recovery not started (default actions restart tools).
J40/C10 Login methods and the No-login profile (task) passed (read) n/a No login without a matching user = full authorization (ISS-018).
J40 Active Directory integration and SPNEGO single sign-on (task) not practiced n/a No domain on the test system; extra AD keywords installed (ISS-054).
L25 AUDIT Service checks: processes, ADT group, classifiers, selection groups (task) passed n/a adtsto + adtcol; 463 classifiers, 444 stored; ADT lifetime 52 weeks; manual differences ISS-051.
L25 Read the audit trail: export, RQL, audit report, what each tool records (task) passed passed Report CIENG_AUDIT (19_audit_df.qli); qli export needs NAME in @FIELDS; dssqld = ENT-ENG-MOD, Engineering Module = LOC-ENG-MOD (checked by the user); itmval not audited (ISS-049).
L25 Classifier STORAGE, selection groups, event logger ADTLOG (task) passed passed Selection group CIENG_ITEMS compiles on load; adtlog -n adtlogci with sample setup file printed only CI-Eng-Sample events; storage flag cached (ISS-050); AUDIT_INFO effect not shown (ISS-049). Full sample remove/reload 0 errors.