| audit | ||
| displays | ||
| equipment | ||
| layouts | ||
| monitoring | ||
| .gitignore | ||
| 01_section_df.qli | ||
| 01b_alarm_df.qli | ||
| 02_item_df.qli | ||
| 02b_sub_item_df.qli | ||
| 03_his_group_df.qli | ||
| 04_item_his_df.qli | ||
| 05_trigger_df.qli | ||
| 06_class_df.qli | ||
| 07_object_df.qli | ||
| 08_auth_group_df.qli | ||
| 09_modbus_line_df.qli | ||
| 10_modbus_station_df.qli | ||
| 11_item_eqp_df.qli | ||
| 12_opc_visible_df.qli | ||
| 13_opcua_line_df.qli | ||
| 14_opcua_station_df.qli | ||
| 15_item_opcua_df.qli | ||
| 16_item_alarm_df.qli | ||
| 17_printer_df.ps1 | ||
| 17_printer_df.tpl | ||
| 18_report_df.qli | ||
| 19_audit_df.qli | ||
| 19b_audit_item_df.qli | ||
| 76_remove_item_opcua_df.qli | ||
| 77_remove_opcua_station_df.qli | ||
| 78_remove_opcua_line_df.qli | ||
| 79_remove_audit_df.qli | ||
| 80_remove_item_eqp_df.qli | ||
| 81_remove_modbus_station_df.qli | ||
| 82_remove_modbus_line_df.qli | ||
| 83_remove_report_df.qli | ||
| 83a_stop_report_df.qli | ||
| 84_remove_printer_df.qli | ||
| 85_remove_auth_group_df.qli | ||
| 86_remove_object_df.qli | ||
| 87_remove_class_df.qli | ||
| 88_remove_trigger_df.qli | ||
| 89_remove_item_his_df.qli | ||
| 90_remove_his_group_df.qli | ||
| 90b_remove_sub_item_df.qli | ||
| 91_remove_item_df.qli | ||
| 92_remove_section_df.qli | ||
| 93_remove_alarm_df.qli | ||
| load.cmd | ||
| README.md | ||
| remove.cmd | ||
CI-Eng-Sample
A small, invented sample project that anyone with this repo can load into a CI Server R1.03 test system. Skills use its names in their examples, and every skill task is re-tested against it so that no other project is needed.
Built and tested on CI Server R1.03.00 (unlicensed test system), 2026-09-30.
Load and remove
Test systems only: loading writes to the CI Server database. CI Server must be running.
From an elevated prompt, call the scripts by full path (a bare load.cmd may not be found
from the current folder):
cmd /c "<repo>\examples\CI-Eng-Sample\load.cmd"
cmd /c "<repo>\examples\CI-Eng-Sample\remove.cmd"
- Each step prints a summary and writes a
.qlolisting; check thatErrorsis 0. - Restart CI Server after loading (stop, then start the CI Service): a new storage group stores no history until CI Server restarts.
load.cmdon a system that already has the project reportsExistsand changes nothing.remove.cmdtakes about 1½ minutes: a storage group can only be deleted after its stop time has passed, so the script sets a stop time one minute ahead and waits. Removing the group also deletes its history.
Current contents
| Name | Kind | Details |
|---|---|---|
CI-Eng-Sample |
Section | Top level |
CI-Eng-Sample.TANK1, .PUMP1, .SYSTEM |
Sections | Tank, pump, system monitoring |
CI-Eng-Sample.TANK1.LEVEL |
Item, Real | %, format 999.9, limits LL 10 / L 20 / H 80 / HH 90, scale 0–100, stored in CIENG_EVENT; alarming on (ack type CIENG_ACK, area CIENG_TANKS; 16_item_alarm_df.qli) |
CI-Eng-Sample.TANK1.INFLOW |
Item, Real | m3/h, format 9999.9, scale 0–500, stored in CIENG_EVENT |
CI-Eng-Sample.PUMP1.RUNNING |
Item, Boolean | |
CI-Eng-Sample.PUMP1.MODE |
Item, Integer | 0 manual, 1 auto |
CI-Eng-Sample.SYSTEM.CPU_LOAD |
Item, Real | Target for intcpumon |
CI-Eng-Sample.SYSTEM.DISK_C |
Item, Real | Target for intdskmon (reports used %) |
CI-Eng-Sample.SYSTEM.PING_LOCALHOST |
Item, Integer | Target for inttcpmon (1 = reachable) |
CI-Eng-Sample.SYSTEM.PROC_ALM |
Item, Integer | Target for intmon (1 = alm process running) |
CI-Eng-Sample.PUMP1.RUNNING.RUN_SECONDS |
Sub-item, Integrator | Running time in seconds (adds value × integration granule, itm_int_secs in itm.sup, default 1 s) |
CI-Eng-Sample.TANK1.LEVEL.MAX |
Sub-item, Min-Max | Highest level seen |
CI-Eng-Sample.DEMO |
Section | Tutorial examples |
CI-Eng-Sample.DEMO.COUNTER |
Item, Integer | Counts 1…100, one step per second, written by DEMO.INCR1 |
CIENG_1S |
Trigger group | Every second |
CIENG_INCR |
Class (traditional) | Increments DEMO.COUNTER, wraps at 100; compiled on load |
CI-Eng-Sample.DEMO.INCR1 |
Object | Instance of CIENG_INCR |
CI-Eng-Sample.TEMPLATES |
Section | Template items for classes |
CI-Eng-Sample.TEMPLATES.TPL_REAL |
Item, Real | Template for items that objects create (format 9999.9, scale 0–1000) |
CIENG_TANK |
Class (traditional) | Prompt Tank capacity (m3); signal LEVEL = <object section>.LEVEL (trigger on value); creates <object>.VOLUME from TPL_REAL; volume = level × capacity / 100; logs when the level crosses 80; refuses capacity ≤ 0 |
CI-Eng-Sample.TANK1.CALC |
Object | CIENG_TANK, capacity 200; creates section TANK1.CALC and item TANK1.CALC.VOLUME |
CIENG_JFLOW |
Class (Java) | Attaches <object section>.INFLOW; creates <object>.sPerMin = inflow / 60; logs each change |
CI-Eng-Sample.TANK1.JFLOW |
Object | CIENG_JFLOW; creates item TANK1.JFLOW.sPerMin (mixed case, as the Java identifier) |
CIENG_EVENT |
Item storage group | Event/Item, lifetime 1 week, rollover 1 day |
CIENG_SCAN10S |
Item storage group | Scan/Time every 10 s with quality, priority 10 (source for aggregation), lifetime 1 day, rollover 1 hour; TANK1.LEVEL, TANK1.INFLOW |
CIENG_AGG |
Item storage group | Aggregation 30 min + hourly, lifetime 4 weeks, rollover 1 week; TANK1.LEVEL max/min/average (read with INTERPOLATION = "30Minutes" / "Hour", ATTRIBUTE = "Maximum" …) |
CI-Eng-Sample.PLC1 |
Section | Modbus loopback station |
CI-Eng-Sample.PLC1.COMM_OK |
Item, Boolean | Status item of station CIENG_PLC (1 = communicating, status 22 when off-scan) |
CI-Eng-Sample.PLC1.SETPOINT / .READBACK |
Items, Integer | Written to holding register 1 (RO:1) / read from input register 1 (RI:1), same memory |
CI-Eng-Sample.PLC1.CMD / .FEEDBACK |
Items, Boolean | Written to coil 1 (DO:1) / read from input bit 1 (DI:1), same memory |
CIENG_MB_LINE |
Modbus line (TCP/IP) | Equipment manager EQPCIENG (created and started by loading the line) |
CIENG_PLC |
Modbus station | Open Modbus/TCP to localhost:5020, unit 1, output method On change and connect |
CIENG_SCAN1S |
Modbus scan type | 1000 ms |
CI-Eng-Sample.UA |
Section | OPC UA loopback station |
CI-Eng-Sample.UA.COMM_OK |
Item, Boolean | Status item of station CIENG_UA (1 = connected) |
CI-Eng-Sample.UA.LEVEL_COPY |
Item, Real | TANK1.LEVEL read back through CI Server's own OPC UA server |
CI-Eng-Sample.UA.SRV_STATE |
Item, Integer | OPC UA server state node (ns 0, i=2259), 0 = Running |
CIENG_UA_LINE |
OPC UA client line | Client process OPXCIENG (created and started by loading the line) |
CIENG_UA |
OPC UA station | opc.tcp://localhost:34493, Basic256Sha256 / SignAndEncrypt, anonymous; subscription CIENG_SUB (1 s); points LEVEL, SRV_STATE |
| OPC visible | Flags | Sections CI-Eng-Sample, TANK1 and item TANK1.LEVEL are OPC visible, item read-only (12_opc_visible_df.qli) |
CIENG_ACK |
Acknowledgement type | Every alarm needs an acknowledgement; return to normal automatic only if the alarm was acknowledged (same matrix as MANUAL) |
CIENG_TANKS |
Area of interest | Label for tank items (TANK1.LEVEL AOI_1) |
CIENG_TANK1 |
Alarm selection area | SECTION = "CI-Eng-Sample.TANK1", compiled on load |
CIENG_VIEWER |
Authorization group | Read-only: ITEM_READ, SECTION_READ, ALARM_CURRENT_READ, ALARM_CHRONO_READ. No users are created by the sample. |
CIENG_FILE |
Printer device + destination | FILE output to %TLS_LST_PATH%\cieng_report.txt (overwritten by each printed report); destination visible to operators |
CIENG_TANK1 |
Report | Values of the TANK1 items + last-hour statistics of one item (ad-hoc parameter chosen in an item browser, default LEVEL); daily 06:00 local time and ad hoc; output CIENG_FILE; lifetime 1 week |
CIENG_INFLOW_HI |
Report | Generated 5 s after TANK1.INFLOW rises above 400; output CIENG_FILE |
CIENG_HTML |
Report | Ad hoc; TANK1 values as an HTML table (cursor loop) plus the logbook text |
CIENG_AUDIT |
Report | Ad hoc; audit trail events on CI-Eng-Sample.* of the last hour |
CIENG_ITEMS |
Audit selection group | Expression sbid >= "CI-Eng-Sample." and sbid < "CI-Eng-Sample/", compiled on load |
Items created by objects (TANK1.CALC.VOLUME, TANK1.JFLOW.sPerMin) and their sections are
deleted with the objects; they are not in 02_item_df.qli.
All items except PLC1.* are internal (no station). The PLC1 station talks to CI Server's own Modbus slave mirror (see below), so no PLC is needed either.
New items start with status 13 (NOT INIT) until a value is written.
Files
| File | Purpose |
|---|---|
01_section_df.qli |
Sections (SECTION_DF); parents before children |
02_item_df.qli |
Items (ITEM_DF) |
02b_sub_item_df.qli |
Sub-items (SUB_ITEM_DF) |
03_his_group_df.qli |
Item storage groups (HIS_GROUP_DF): event, scan, aggregation |
04_item_his_df.qli |
Items in the storage group (ITEM_HIS_DF, name <group>:<item>) |
05_trigger_df.qli, 06_class_df.qli, 07_object_df.qli |
Trigger group; classes (source in the METHOD memo, @" … "@, COMPILE 1; Traditional and Java); objects (ATTR_VALUE_1 = prompt answer) |
08_auth_group_df.qli |
Authorization group (AUTH_GROUP_DF) |
09_modbus_line_df.qli, 10_modbus_station_df.qli, 11_item_eqp_df.qli |
Modbus line; station, scan type, points; items connected to points |
12_opc_visible_df.qli |
OPC visible / read flags (loaded with dssqld -m) |
13_opcua_line_df.qli, 14_opcua_station_df.qli, 15_item_opcua_df.qli |
OPC UA client line; station, subscription, points; connected items |
01b_alarm_df.qli |
Alarm definitions: acknowledgement type, area of interest, alarm selection area (ALARM_ACK_DF, ALARM_AOI_DF, ALARM_ASA_DF) |
16_item_alarm_df.qli |
Switch on alarming for TANK1.LEVEL (loaded with dssqld -m) |
17_printer_df.tpl, 17_printer_df.ps1 |
Report file device and destination; the script fills in this system's node name and %TLS_LST_PATH% and writes 17_printer_df.qli (not in the repo) |
18_report_df.qli |
Reports (REPORT_DF, RQL in the QUERY memo) |
19_audit_df.qli |
Audit selection group (AUDIT_SELGRP_DF) and audit report |
audit/adtlogci.sup |
Setup file for an extra audit event logger ADTLOGCI filtered on CIENG_ITEMS (copied to tls\sup by an administrator, not by load.cmd) |
83a_stop_report_df.qli |
Clears the schedule of CIENG_TANK1 before removal (a scheduled report cannot be deleted) |
equipment/eqpciengslv_start.cmd, _stop.cmd |
Start/stop the Modbus slave mirror (copy to tls\com) |
76_…93_remove_*.qli |
Names to delete, in reverse order (audit 79, reports and printer 83/84 first, alarm definitions last, 93) |
load.cmd, remove.cmd |
Run the steps in the right order |
displays/CIENG_Tank.xml |
Display (HTML mode): title, number field on TANK1.LEVEL, PUMP1.MODE field with buttons Manual (0) / Auto (1) (write the item), alarm overview, trend of TANK1.LEVEL, button Operator layout |
19b_audit_item_df.qli |
Audit trailing wanted for PUMP1.MODE (loaded with dssqld -m) |
displays/CIENG_Menu.xml |
Navigation display (200 x 700): Tank 1, Current Alarm (main frame), Tank 1 popup (layout popup) |
layouts/CIENG_Operator.xml, layouts/layout.ps1 |
Operator layout block and the script that adds/removes it in Layouts.xml |
displays/deploy_displays.cmd, remove_displays.cmd |
Copy the displays into the operator interface and export their HTML versions / delete them |
monitoring/*.sup.txt |
Setup-file lines for the monitoring processes (not applied by load.cmd) |
Modbus slave mirror (for station CIENG_PLC)
CIENG_PLC reads and writes CI Server's own Modbus slave: eqpmdcmem (slave memory) and
eqpmdcslvtcp (Modbus TCP on port 5020). Without them the station reports bad communication
(COMM_OK = 0) but everything loads. To start them with CI Server, an administrator copies
equipment/eqpciengslv_start.cmd and eqpciengslv_stop.cmd to %TLS_ROOT_PATH%\tls\com;
for a quick test they can also be started by hand from a normal prompt:
start eqpmdcmem -n EQPMDCMEM
start eqpmdcslvtcp -n EQPMDCSLVTCP -p 5020
Remove the two files from tls\com when the sample is removed. See skill equipment, task
modbus-station.md.
OPC UA loopback (station CIENG_UA)
CIENG_UA is CI Server's OPC UA client connected to CI Server's own OPC UA server, so no
external server is needed. The first connection on a system needs a one-time certificate
exchange, done by the user (skill data-access, task opcua-client.md §4):
- After loading, the client logs
OPXC-E-CER_NO_TRU; trust the server certificate in%TLS_ALLUSERS_PATH%\pki\opxuac\pkiclient\rejected(Engineering Module, or move it to…\pkiclient\trusted\certs). - The server then rejects the client; move
CI_SERVER_OPCUA_CLIENT_OPXCIENG […].derfrom%TLS_ALLUSERS_PATH%\pki\opxuas\pkiserver\rejectedto…\pkiserver\trusted\certs(PowerShell:Move-Item -LiteralPath, the name contains brackets).
Then UA.COMM_OK = 1 and UA.LEVEL_COPY follows TANK1.LEVEL. The trust is kept when the
sample is removed and loaded again.
Alarms (TANK1.LEVEL)
TANK1.LEVEL raises HIGH above 80 (Alarm 2, priority 2) and HIGH HIGH above 90 (Alarm 3,
priority 1). To try it on a test system: itmval -p -n CI-Eng-Sample.TANK1.LEVEL -v 85, export
ALARM_CURRENT (filter on ITEM_NAME), acknowledge with dssqld -m on ALARM_CURRENT
(NAME, ACK 1), write the level back below 80. See skill alarm-management, task
item-alarming.md.
Displays and layout (optional)
No admin rights needed. After load.cmd:
displays\deploy_displays.cmdcopiesCIENG_TankandCIENG_Menuinto the operator interface and creates their HTML versions.powershell -ExecutionPolicy Bypass -File layouts\layout.ps1adds the layoutCIENG_OperatortoLayouts.xml(first run savesLayouts-before-CIENG.xml). Restart the Operator Interface afterwards: it reads the layouts only at start.- Operator Interface (desktop): open
CIENG_Tankfrom the display box and click Operator layout - a second window opens with the sample menu (File / View / Displays), toolbar,CIENG_Menuon the left,CIENG_Tankin the main framedefaultand the alarm banner. HTML display (web):http://localhost:8080/mobileoperator/?d=CIENG_Tank&l=CIENG_Operator(CI Server login).
Remove: layouts\layout.ps1 -Remove (restores the file exactly) and
displays\remove_displays.cmd. Close the displays in the Edit Module first. See skill
graphics.
Monitoring processes (optional)
monitoring/ holds the lines to add to the setup files in %TLS_ROOT_PATH%\tls\sup\ so that
intcpumon, intdskmon, inttcpmon, intmon and intspawn write into the SYSTEM items.
These change the system's own setup files: back the files up first and restore them after
testing. See the system-management skill, task monitoring-processes.md.
Reports
No admin rights needed. load.cmd creates the device, destination and three reports; each report
gets its own storage group of type Report. Try them (skill reporting, task define-reports.md):
- Ad hoc:
REPORT_DFNAME,PARAM_VALUE_1,GENERATE="CIENG_TANK1","CI-Eng-Sample.TANK1.INFLOW",1withdssqld -m, or in the Engineering Module Configuration > Reporting > Reports › right-click › Generate. The output lands inREPORT_VAL; runs from the Engineering Module also print to%TLS_LST_PATH%\cieng_report.txt(runs fromdssqlddo not print, ISS-045). - Trigger:
itmval -p -n CI-Eng-Sample.TANK1.INFLOW -v 450→CIENG_INFLOW_HI5 s later; write a value below 400 before the next test. CIENG_TANK1also runs every day at 06:00 (local time).
remove.cmd clears the schedule, removes the reports (with their generated reports and logbook
files), the destination and device, and deletes cieng_report.txt.
Audit trail
No admin rights needed for 19_audit_df.qli. Every change made by load.cmd, dssqld or the
Engineering Module is in the audit trail (skill audit-trail):
- Generate
CIENG_AUDIT(ad hoc, like the other reports) to list the last hour of changes onCI-Eng-Sample.*: time, dataset, field, action, source, user, old and new value. - Operator writes: with the displays deployed, click Manual (0) / Auto (1) on
CIENG_Tank; each click is stored asITEM.VALUE.MODIFY.OPER-INTERFACEbecausePUMP1.MODEhas Audit trailing wanted (19b_audit_item_df.qli). - Export:
dssqld -e audit.qlo -d AUDIT_TRAIL(whole trail) or a qli with@SELECT(keepNAMEin@FIELDS). - Event logger (optional, admin): copy
audit\adtlogci.supto%TLS_ROOT_PATH%\tls\sup\, then runadtlog -n adtlogciin a console; it prints each new CI-Eng-Sample event on one line (Ctrl+C to stop). Delete the file fromtls\supwhen the sample is removed.
Audit records themselves cannot be deleted; remove.cmd removes only the report and the
selection group.
Planned additions
| Phase | Adds |
|---|---|
| 10 | A symbol and a faceplate popup (displays and the operator layout exist) |
Rules
- Test systems only; invented names only, no real plant or customer data.
- Keep the load order: sections → template items → classes (compiled) → objects → other
items → storage groups → items in storage groups (IM 36K10J10 §5.6). Keep
remove.cmdin reverse order. - Every file notes the CI Server version it was built and tested on.