Full manual diffs (L15, C20, E30, L25, J40, C10 §2, L10, P10, P11, J20, C30, P20, R40, E10) and read-only checks on the shared R1.05 test server. Skills and summaries moved to R1.05; new skill pytools (IM 36K10P40) from docs (no Python on the test server). Issues ISS-132..181; corrections to version-differences (E10, E30, P11, dss_ath_grp_u0104); C10 summary lists the 3 new authorization actions; r105-verification V10-V17. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
4.9 KiB
| name | description |
|---|---|
| reporting | CI Server R1.05 REPORT Service, report definitions and RQL. Use when the user wants to create, change, schedule or delete a report (daily / shift / hourly report, report triggered by an item value or status, ad-hoc report with parameters such as an item, object, date or list), write or debug an RQL query (SELECT from item_val, item_history, alarm_current, alarm_chrono, audit_trail, unit_df …, item units and scale limits ENG_UNIT / SCALE_HIGH_LIMIT / SCALE_LOW_LIMIT, COLUMN formats, HEADER/FOOTER, cursors DECLARE/FETCH, LOOP, GPV_VALUE, @P0 parameters, @DATE), generate a report now (GENERATE), view, print or delete generated reports (REPORT_VAL), output a report to a file, CSV (SPOOL, @EXPORT) or HTML, use a logbook, set up report printers (printer device, destination, FILE / HARDCOPY output, PRINTER_DEV_DF, PRINTER_DEST_DF), try queries in the interactive report generator (rptgen -s rptgen.rpt), stop a hanging report (rptstp), check REPORT Service (rptman, rptge1, rptman.sup, rptge1.rpt, report_start), use the system reports (ALARM_HISTORY, AUDIT_TRAIL, ITEM_HISTORY, SYSTEM_LOG …), put a report component on a display, or use the Excel Add-in (DART) for reports. Sources IM 36K10C30-01EN, IM 36K10P20-01EN, IM 36K10R40-01EN, IM 36K10E10-01EN. |
Reporting (R1.05)
Re-checked on R1.05 on 2026-10-09 (read-only): the four manuals changed only in wording; the
REPORT datasets (REPORT_DF, REPORT_VAL, PRINTER_*), rptman.sup and the generator set-up
files (rptge1.rpt, rptgen.rpt, rptgsp.rpt) are identical to R1.03; the 28 system reports
and the 6 factory destinations are the same. New on R1.05: ITEM_VAL fields ENG_UNIT,
SCALE_HIGH_LIMIT, SCALE_LOW_LIMIT (readable in RQL), new datasets (see below), and
report_start.cmd / report_stop.cmd call extension scripts ?*_report_start.cmd /
?*_report_stop.cmd in tls\com. Report generation was not re-tested on R1.05 (shared
test server): the sample's file device, destination and three reports loaded with 0 errors
(2026-10-08) and were removed again.
Background: knowledge/manuals/IM36K10C30-01EN.md (report definition fields, scheduling and
trigger behaviour, devices, generated reports, system reports), IM36K10P20-01EN.md (RQL),
IM36K10R40-01EN.md (REPORT Service processes and set-up files), IM36K10E10-01EN.md (Excel
Add-in), IM36K10L50-01EN.md (datasets, dssqld).
Rules:
- Run
system-checkfirst; follow the user's chosen way of working. - Report names ≤ 16 characters. Report queries only read, except
SPV_*functions andGPV_VALUE(<item>, <non-zero>)(resets the item) — never use those without approval. - A scheduled report runs on its own; schedule at least every 10 minutes and set a lifetime, or generated reports pile up in history.
- Generator set-up files (
tls\sup\*.rpt),rptman.supandreport_start.cmdneed admin rights and a restart: hand them to the user (skillportal-setup,change-setup-file.md). - Example names come from
CI-Eng-Sample(CIENG_TANK1,CIENG_INFLOW_HI,CIENG_HTML, destinationCIENG_FILE). - Paths: read
set TLSfirst. R1.03 default data rootC:\Users\Public\Yokogawa\tls; on the R1.05 test server program and data shareC:\Yokogawa\CIServer\tls.SPOOLand FILE device paths must be literal, so write the real path of the system. - RQL can read every dataset. Never query
API_KEYS_DF(it holds users' API keys) and do not put it in a report. Other datasets new since R1.03 (names only):ALARM_ATTRIBUTE_TEMP_DF,UASERVER_MAPPER_DF,IEC61850_RCB_DF,OPCUAC_METHOD_CALL2_DF(replacesOPCUAC_METHOD_CALL_IN_DF/_OUT_DF; old report queries on those names fail).
| Task | File | Status |
|---|---|---|
Check REPORT Service: processes, set-up files, system reports, stop a hanging report (rptstp) |
tasks/report-checks.md |
verified (R1.03); on R1.05 processes, files and system reports checked read-only (2026-10-09); rptstp not re-tested |
Try RQL in the interactive generator (rptgen -s rptgen.rpt), CSV with SPOOL |
tasks/rql-interactive.md |
verified (R1.03); queries re-run read-only on R1.05 (2026-10-09), SPOOL not re-tested |
| Define reports by quick load (ad hoc with parameters, schedule, item trigger, HTML, logbook); generate, read, print, delete; remove | tasks/define-reports.md |
verified (R1.03, command line and Engineering Module); on R1.05 load and remove only (2026-10-08), generation not tested |
| Report output to a file: printer device and destination | tasks/output-devices.md |
verified (R1.03); on R1.05 load and remove only (2026-10-08) |
| Report component on a display; Operator Interface generate/view | C30 summary §5 | from docs |
| Hardcopy printers, application devices, more generators, separate RPI servers | C30 summary §3, R40 summary §1, §3 | from docs |