V5 (read-only): Layouts.readme and components identical; JCEF browser component now loaded from tls\exe\lib\jcef; connectrdp.cmd present; jwuiutl help identical; AOG_UAC_MethodArg_Call2 added, AOG_OPCUA_Methods not installed; web trend DataSource.js re-enables the pen checks behind ISS-041 (probably fixed, not tested). V6 (read-only): hisdbg 1/20/6 as on R1.03; history and item start/stop scripts differ only by the extension hooks. ISS-092, 097, 100, 101 closed; notes on ISS-094, 096. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
4.5 KiB
| manual | title | edition | version | status |
|---|---|---|---|---|
| IM 36K10C60-01EN | Advanced Operating Graphics | 5th Edition, Feb. 2026 (R1.05); first summarised from the 3rd Edition, Sep. 2023 (R1.03) | R1.05 (first written for R1.03) | from docs; R1.05 full text diff reviewed 2026-10-08 (only §1.2.2 changed); installed AOG displays checked read-only on R1.03 (DEPLOY\displays, mobileoperator) 2026-10-01; R1.05 AOG display/symbol lists awaiting user verification (ISS-097) |
Advanced Operating Graphics — AOG library (R1.05)
A ready-made library of symbols and displays in a consistent, high-performance HMI style, used from the Edit Module's Visualization sheet. Section numbers refer to the manual.
1. Symbols (§1.1)
| Kind | Purpose | Palettes / examples |
|---|---|---|
| Equipment symbols | Static equipment, no live data | AOG_ContainersAndVessels (AOG_Tank, AOG_Vessel, AOG_Reactor, …), AOG_HeatTransfer, AOG_Indicator, AOG_MaterialHandling, AOG_Mixing, AOG_Rotating (pumps, compressors, turbine), AOG_Separators, AOG_ValvesAndActuators, AOG_Electrical, AOG_Filters, AOG_Others (Yokogawa systems such as AOG_CentumFCS, AOG_ProsafeRS, AOG_StardomFCN, AOG_FAM3, AOG_DTS; field devices; stations) |
| Item symbols | Show and change one or more item attributes | indicators (bar, needle, circular, radial, number, text, on/off, manual, alarm, trend), valves (2-way, 3-way, on/off), selection box, name/info |
Object symbols (AOG_O…) |
Same, driven by PROCESS Service object signals | e.g. AOG_ONumberIndicator, AOG_OHorizontalBarIndicator |
| Navigation symbol, components | Navigation between displays |
2. Displays (§1.2)
Standard displays: AOG_Default, AOG_DisplayTemplate (start for new displays), AOG_Style
(global style parameters), AOG_MenuMain, alarm displays (AOG_AlarmBanner, AOG_AlarmCurrent,
AOG_AlarmHistory, AOG_AlarmShelved), AOG_AuditTrail, AOG_ItemFaceplate,
AOG_ItemTuningPanel, AOG_ObjectFaceplate, AOG_ObjectTuningPanel, AOG_SetItemMode,
AOG_SetObjectMode, AOG_SetNumberPV/SV/SL/SH/SLL/SHH, AOG_LockStatus, AOG_TrendOpen,
OPC UA method call displays; plus demo displays. R1.04 (§1.2.2) documents the demo displays
AOG_UAC_Method_Demo (already installed on R1.03), AOG_UAC_MethodArg_Call2 and
AOG_OPCUA_Methods (not on the R1.03 machine, which has AOG_UAC_MethodArg_Call and
AOG_UAC_Method_Call; R1.05 names not checked, ISS-097): a list of OPC UA client
methods and a display to set input arguments, call a method and read the outputs, last call
time and result. The CI Server method object (made from UAC_MTD_JBASE) must have at least as
many input/output arguments as the external method; fewer give the errors incorrect method
key / incorrect input/output parameters (skill data-access, OPC UA methods; from docs).
Installed (R1.03): these are in
DEPLOY\displays, and the alarm, audit, default, menu, style, trend and UA method displays also
exist as HTML displays.
3. Global style parameters (§1.1, §2.1.1)
Defined once on the AOG_Style display (Parameters tab) and used by all AOG symbols:
colours (AOG_C…: alarm high/medium/low/diagnostic/off, display background, equipment
running/off/not running, fluid and gas lines, indicator background/limit/normal/outline/signal,
manual control, selector, text 1–4), strokes (AOG_S…), fonts (AOG_FT1–4), engineering unit
texts (AOG_EF1 flow, AOG_EL1 level, AOG_EP1 pressure, AOG_ET1/2 temperature), on/off
texts, AOG_BlinkOnNotAcknowledged. Changing a value changes every symbol that uses it.
4. Building an HMI (§2)
Edit Module → (optionally) adjust AOG_Style and save → New display or start from
AOG_DisplayTemplate → place AOG symbols from the Visualization sheet → connect them to items
or objects → save → open in the operator interface. New symbols can be made in the same style.
5. Enterprise (§3)
Enterprise displays and AOG item/object symbols for enterprise engineering (items/objects on several servers; locations chosen per symbol).
Not practiced: the sample display uses plain components; AOG symbols need the Edit Module GUI.
R1.05 installed AOG displays (V5, 2026-10-09)
The R1.05 test server has the same AOG_* displays as R1.03 plus AOG_UAC_MethodArg_Call2
(display and HTML export). AOG_OPCUA_Methods, named in the 5th Edition §1.2.2, is not
installed (ISS-097). OPC UA method demo displays installed: AOG_UAC_Method_Demo,
AOG_UAC_Method_Call, AOG_UAC_MethodArg_Call, AOG_UAC_MethodArg_Call2.