task: Read and change login methods per client and user interface (dssana.sup Login control) version: R1.05 (first written for R1.03) source: IM 36K10C10-01EN 5th ed. (Feb. 2026) §2.2; IM 36K10J40-01EN 4th ed. (Feb. 2026) §1.1, §2.10.3; IM 36K10J10-01EN 5th ed. §2.9.1 (RESTful API, pyTOOLS); IM 36K10C50-01EN 5th ed. §2.31 (Password Check); dssana.sup help and installed values status: verified on R1.03 (2026-10-01: reading and the No-login behaviour); R1.05 dssana.sup compared read-only with R1.03 on the R1.05 test server (2026-10-09); changing the file from docs (admin)

Login methods (dssana.sup, tab Login control)

1. Read the current methods

findstr /b LOGIN_METHOD %TLS_ROOT_PATH%\tls\sup\dssana.sup (or the Setup File Editor).

LOGIN_METHOD = <client>, "<user interface>", <method>, <no login when no users>, "<no-login profile>"
  • <client>: host name or IP (wildcards allowed), "<local>" (this machine) or "<remote>" (any other); lines are evaluated top-down, <local>/<remote> always last.
  • <user interface>: the full name from the User Interfaces tab (USER_INTERFACE = …), e.g. "Engineering Module", "Edit Module", "Operator Interface", "Quickload Utility". A user interface that is not listed there cannot connect at all. Its last field can name an action the user's group must have (installed: Edit Module and Display/Symbol Utility need DISPLAY_MODIFY).
  • <method>: Automatic (Windows name = CI Server user, no password), Manual CI Server, Manual OS, No, SSO, Deny.

Installed (same on R1.03.00 and R1.05.00): local and remote Engineering Module, Edit Module, Operator Interface, Item Search, Mobile Operator, Excel Add-in → SSO (falls back to Manual CI Server while SSO is not set up); local Quickload / Display and Symbol Utility → No; remote Playback Viewer, Quickload, Display/Symbol utilities → Deny; OPC UA server, ODBC → Manual CI Server; anonymous OPC UA (local) → No with profile CI_NO_LOGIN_OPCUAS.

New in R1.04/R1.05 (verified in the R1.05 file, 2026-10-09; ISS-148):

User interface (abbreviation) Used by Installed method (local and remote) Allowed methods (manual)
RESTful API Server (JRSTSRV) RESTful API (skill data-access) Manual CI Server Manual CI Server or Manual OS (J10 §2.9.1)
Python Interface (PYDSS) pyTOOLS (skill pytools) Manual CI Server Manual CI Server only (J10 §2.9.1)
Password Check Function (JWUIPSWD) Password Check in display Generic Functions (skill graphics) Manual CI Server Manual CI Server or Manual OS (C50 §2.31)

The .NET API line was renamed: R1.03 had LOGIN_METHOD = "<local>", "dnetapi", …, a name that is not a defined user interface; R1.05 uses "Application Interface" (the TLSVBCLIB user interface), still Manual CI Server. After an upgrade, check that these lines exist: a dssana.sup carried over from R1.03 lacks them and the three new interfaces cannot log on (ISS-149, not tested: no upgrade available).

The other tabs (General, Clients System Trust, Active Directory, Single Sign On, Password rules, Logging) and all help texts are unchanged in R1.05. MAX_UI_PER_CLIENT (user interfaces per remote CI View) has help/factory default 5. The reference copies that R1.05 installs for the upgrade merge (%TLS_SAV_PATH%\jmrg\ref-data\R1.01.00 … R1.04.00\sup\dssana.sup) all have 5. On the R1.05 test server the active value is 500: a local change, saved with the Setup File Editor on 2026-09-12 (the editor shows the field label in blue = differs from the default; V16, ISS-150). The default is 5; check the active line before relying on it.

2. No login — check the profile

With No the user interface runs with the no-login profile (5th field). If no CI Server user with that name exists, the session gets full authorization (dssana.sup help, unchanged in R1.05; verified indirectly on R1.03: Quickload Utility uses No with an empty profile and every dssqld change is recorded in the audit trail as user FULL AUTHORIZATION). The installed lines name CI_NO_LOGIN, which does not exist by default (only CI_NO_LOGIN_OPCUAS does). Manual (C10 §2.2, R1.05): now also names CI_NO_LOGIN (R1.03 manual: FT_NO_LOGIN), but still says no profile is applied when that user is missing — the installed help is the reference (ISS-018, ISS-125). No is only allowed for user interfaces on the CI Portal itself, not for remote CI View.

Before setting No for an operator UI: create user CI_NO_LOGIN with a restricted authorization group (users-groups.md) and a password, then change the method.

3. Change a method

Admin rights; hand to the user (skill portal-setup, change-setup-file.md). Add a specific line above the <local>/<remote> lines (e.g. one HMI PC by host name), save, restart USER Service (or CI Server) for it to take effect. With AD integration on (AD_INT_ON = YES) the methods of the Edit and Engineering Modules are ignored: see active-directory.md. For the Password Check function the method must be Manual CI Server or Manual OS (installed default is fine); for pyTOOLS only Manual CI Server works.