V5 (read-only): Layouts.readme and components identical; JCEF browser component now loaded from tls\exe\lib\jcef; connectrdp.cmd present; jwuiutl help identical; AOG_UAC_MethodArg_Call2 added, AOG_OPCUA_Methods not installed; web trend DataSource.js re-enables the pen checks behind ISS-041 (probably fixed, not tested). V6 (read-only): hisdbg 1/20/6 as on R1.03; history and item start/stop scripts differ only by the extension hooks. ISS-092, 097, 100, 101 closed; notes on ISS-094, 096. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
69 lines
4.5 KiB
Markdown
69 lines
4.5 KiB
Markdown
---
|
||
manual: IM 36K10C60-01EN
|
||
title: Advanced Operating Graphics
|
||
edition: 5th Edition, Feb. 2026 (R1.05); first summarised from the 3rd Edition, Sep. 2023 (R1.03)
|
||
version: R1.05 (first written for R1.03)
|
||
status: from docs; R1.05 full text diff reviewed 2026-10-08 (only §1.2.2 changed); installed AOG displays checked read-only on R1.03 (DEPLOY\displays, mobileoperator) 2026-10-01; R1.05 AOG display/symbol lists awaiting user verification (ISS-097)
|
||
---
|
||
|
||
# Advanced Operating Graphics — AOG library (R1.05)
|
||
|
||
A ready-made library of symbols and displays in a consistent, high-performance HMI style,
|
||
used from the Edit Module's Visualization sheet. Section numbers refer to the manual.
|
||
|
||
## 1. Symbols (§1.1)
|
||
|
||
| Kind | Purpose | Palettes / examples |
|
||
|---|---|---|
|
||
| Equipment symbols | Static equipment, no live data | `AOG_ContainersAndVessels` (AOG_Tank, AOG_Vessel, AOG_Reactor, …), `AOG_HeatTransfer`, `AOG_Indicator`, `AOG_MaterialHandling`, `AOG_Mixing`, `AOG_Rotating` (pumps, compressors, turbine), `AOG_Separators`, `AOG_ValvesAndActuators`, `AOG_Electrical`, `AOG_Filters`, `AOG_Others` (Yokogawa systems such as AOG_CentumFCS, AOG_ProsafeRS, AOG_StardomFCN, AOG_FAM3, AOG_DTS; field devices; stations) |
|
||
| Item symbols | Show and change one or more item attributes | indicators (bar, needle, circular, radial, number, text, on/off, manual, alarm, trend), valves (2-way, 3-way, on/off), selection box, name/info |
|
||
| Object symbols (`AOG_O…`) | Same, driven by PROCESS Service object signals | e.g. `AOG_ONumberIndicator`, `AOG_OHorizontalBarIndicator` |
|
||
| Navigation symbol, components | Navigation between displays | |
|
||
|
||
## 2. Displays (§1.2)
|
||
|
||
Standard displays: `AOG_Default`, `AOG_DisplayTemplate` (start for new displays), `AOG_Style`
|
||
(global style parameters), `AOG_MenuMain`, alarm displays (`AOG_AlarmBanner`, `AOG_AlarmCurrent`,
|
||
`AOG_AlarmHistory`, `AOG_AlarmShelved`), `AOG_AuditTrail`, `AOG_ItemFaceplate`,
|
||
`AOG_ItemTuningPanel`, `AOG_ObjectFaceplate`, `AOG_ObjectTuningPanel`, `AOG_SetItemMode`,
|
||
`AOG_SetObjectMode`, `AOG_SetNumberPV/SV/SL/SH/SLL/SHH`, `AOG_LockStatus`, `AOG_TrendOpen`,
|
||
OPC UA method call displays; plus demo displays. R1.04 (§1.2.2) documents the demo displays
|
||
`AOG_UAC_Method_Demo` (already installed on R1.03), `AOG_UAC_MethodArg_Call2` and
|
||
`AOG_OPCUA_Methods` (not on the R1.03 machine, which has `AOG_UAC_MethodArg_Call` and
|
||
`AOG_UAC_Method_Call`; R1.05 names not checked, ISS-097): a list of OPC UA client
|
||
methods and a display to set input arguments, call a method and read the outputs, last call
|
||
time and result. The CI Server method object (made from `UAC_MTD_JBASE`) must have at least as
|
||
many input/output arguments as the external method; fewer give the errors *incorrect method
|
||
key* / *incorrect input/output parameters* (skill `data-access`, OPC UA methods; from docs).
|
||
**Installed (R1.03)**: these are in
|
||
`DEPLOY\displays`, and the alarm, audit, default, menu, style, trend and UA method displays also
|
||
exist as HTML displays.
|
||
|
||
## 3. Global style parameters (§1.1, §2.1.1)
|
||
|
||
Defined once on the `AOG_Style` display (*Parameters* tab) and used by all AOG symbols:
|
||
colours (`AOG_C…`: alarm high/medium/low/diagnostic/off, display background, equipment
|
||
running/off/not running, fluid and gas lines, indicator background/limit/normal/outline/signal,
|
||
manual control, selector, text 1–4), strokes (`AOG_S…`), fonts (`AOG_FT1–4`), engineering unit
|
||
texts (`AOG_EF1` flow, `AOG_EL1` level, `AOG_EP1` pressure, `AOG_ET1/2` temperature), on/off
|
||
texts, `AOG_BlinkOnNotAcknowledged`. Changing a value changes every symbol that uses it.
|
||
|
||
## 4. Building an HMI (§2)
|
||
|
||
Edit Module → (optionally) adjust `AOG_Style` and save → *New display* or start from
|
||
`AOG_DisplayTemplate` → place AOG symbols from the Visualization sheet → connect them to items
|
||
or objects → save → open in the operator interface. New symbols can be made in the same style.
|
||
|
||
## 5. Enterprise (§3)
|
||
|
||
Enterprise displays and AOG item/object symbols for enterprise engineering (items/objects on
|
||
several servers; locations chosen per symbol).
|
||
|
||
Not practiced: the sample display uses plain components; AOG symbols need the Edit Module GUI.
|
||
|
||
## R1.05 installed AOG displays (V5, 2026-10-09)
|
||
|
||
The R1.05 test server has the same `AOG_*` displays as R1.03 plus `AOG_UAC_MethodArg_Call2`
|
||
(display and HTML export). `AOG_OPCUA_Methods`, named in the 5th Edition §1.2.2, is **not**
|
||
installed (ISS-097). OPC UA method demo displays installed: `AOG_UAC_Method_Demo`,
|
||
`AOG_UAC_Method_Call`, `AOG_UAC_MethodArg_Call`, `AOG_UAC_MethodArg_Call2`.
|