ci-server-engineer/examples/CI-Eng-Sample/README.md
cliu 90058ffdef Add equipment skill and Modbus loopback station to CI-Eng-Sample
- New skill equipment with task modbus-station: line, station, scan type,
  points and connected items by quick load, tested against CI Server's own
  Modbus slave mirror (eqpmdcmem + eqpmdcslvtcp)
- CI-Eng-Sample: section PLC1, station CIENG_PLC with write/read-back
  items, load/remove steps and mirror start/stop scripts
- ISS-024: the TCP slave answers Open Modbus/TCP, not RTU (closed)

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-30 17:22:58 +10:00

6.6 KiB
Raw Blame History

CI-Eng-Sample

A small, invented sample project that anyone with this repo can load into a CI Server R1.03 test system. Skills use its names in their examples, and every skill task is re-tested against it so that no other project is needed.

Built and tested on CI Server R1.03.00 (unlicensed test system), 2026-09-30.

Load and remove

Test systems only: loading writes to the CI Server database. CI Server must be running. From an elevated prompt, call the scripts by full path (a bare load.cmd may not be found from the current folder):

cmd /c "<repo>\examples\CI-Eng-Sample\load.cmd"
cmd /c "<repo>\examples\CI-Eng-Sample\remove.cmd"
  • Each step prints a summary and writes a .qlo listing; check that Errors is 0.
  • Restart CI Server after loading (stop, then start the CI Service): a new storage group stores no history until CI Server restarts.
  • load.cmd on a system that already has the project reports Exists and changes nothing.
  • remove.cmd takes about 1½ minutes: a storage group can only be deleted after its stop time has passed, so the script sets a stop time one minute ahead and waits. Removing the group also deletes its history.

Current contents

Name Kind Details
CI-Eng-Sample Section Top level
CI-Eng-Sample.TANK1, .PUMP1, .SYSTEM Sections Tank, pump, system monitoring
CI-Eng-Sample.TANK1.LEVEL Item, Real %, format 999.9, limits LL 10 / L 20 / H 80 / HH 90, scale 0–100 (alarming off), stored in CIENG_EVENT
CI-Eng-Sample.TANK1.INFLOW Item, Real m3/h, format 9999.9, scale 0–500, stored in CIENG_EVENT
CI-Eng-Sample.PUMP1.RUNNING Item, Boolean
CI-Eng-Sample.PUMP1.MODE Item, Integer 0 manual, 1 auto
CI-Eng-Sample.SYSTEM.CPU_LOAD Item, Real Target for intcpumon
CI-Eng-Sample.SYSTEM.DISK_C Item, Real Target for intdskmon (reports used %)
CI-Eng-Sample.SYSTEM.PING_LOCALHOST Item, Integer Target for inttcpmon (1 = reachable)
CI-Eng-Sample.SYSTEM.PROC_ALM Item, Integer Target for intmon (1 = alm process running)
CI-Eng-Sample.PUMP1.RUNNING.RUN_SECONDS Sub-item, Integrator Running time in seconds (adds value × integration granule, itm_int_secs in itm.sup, default 1 s)
CI-Eng-Sample.TANK1.LEVEL.MAX Sub-item, Min-Max Highest level seen
CI-Eng-Sample.DEMO Section Tutorial examples
CI-Eng-Sample.DEMO.COUNTER Item, Integer Counts 1…100, one step per second, written by DEMO.INCR1
CIENG_1S Trigger group Every second
CIENG_INCR Class (traditional) Increments DEMO.COUNTER, wraps at 100; compiled on load
CI-Eng-Sample.DEMO.INCR1 Object Instance of CIENG_INCR
CIENG_EVENT Item storage group Event/Item, lifetime 1 week, rollover 1 day
CI-Eng-Sample.PLC1 Section Modbus loopback station
CI-Eng-Sample.PLC1.COMM_OK Item, Boolean Status item of station CIENG_PLC (1 = communicating, status 22 when off-scan)
CI-Eng-Sample.PLC1.SETPOINT / .READBACK Items, Integer Written to holding register 1 (RO:1) / read from input register 1 (RI:1), same memory
CI-Eng-Sample.PLC1.CMD / .FEEDBACK Items, Boolean Written to coil 1 (DO:1) / read from input bit 1 (DI:1), same memory
CIENG_MB_LINE Modbus line (TCP/IP) Equipment manager EQPCIENG (created and started by loading the line)
CIENG_PLC Modbus station Open Modbus/TCP to localhost:5020, unit 1, output method On change and connect
CIENG_SCAN1S Modbus scan type 1000 ms
CIENG_VIEWER Authorization group Read-only: ITEM_READ, SECTION_READ, ALARM_CURRENT_READ, ALARM_CHRONO_READ. No users are created by the sample.

All items except PLC1.* are internal (no station). The PLC1 station talks to CI Server's own Modbus slave mirror (see below), so no PLC is needed either. New items start with status 13 (NOT INIT) until a value is written.

Files

File Purpose
01_section_df.qli Sections (SECTION_DF); parents before children
02_item_df.qli Items (ITEM_DF)
02b_sub_item_df.qli Sub-items (SUB_ITEM_DF)
03_his_group_df.qli Item storage group (HIS_GROUP_DF)
04_item_his_df.qli Items in the storage group (ITEM_HIS_DF, name <group>:<item>)
05_trigger_df.qli, 06_class_df.qli, 07_object_df.qli Trigger group, class (source in the METHOD memo, @" … "@, COMPILE 1), object
08_auth_group_df.qli Authorization group (AUTH_GROUP_DF)
09_modbus_line_df.qli, 10_modbus_station_df.qli, 11_item_eqp_df.qli Modbus line; station, scan type, points; items connected to points
equipment/eqpciengslv_start.cmd, _stop.cmd Start/stop the Modbus slave mirror (copy to tls\com)
80_…92_remove_*.qli Names to delete, in reverse order
load.cmd, remove.cmd Run the steps in the right order
monitoring/*.sup.txt Setup-file lines for the monitoring processes (not applied by load.cmd)

Modbus slave mirror (for station CIENG_PLC)

CIENG_PLC reads and writes CI Server's own Modbus slave: eqpmdcmem (slave memory) and eqpmdcslvtcp (Modbus TCP on port 5020). Without them the station reports bad communication (COMM_OK = 0) but everything loads. To start them with CI Server, an administrator copies equipment/eqpciengslv_start.cmd and eqpciengslv_stop.cmd to %TLS_ROOT_PATH%\tls\com; for a quick test they can also be started by hand from a normal prompt:

start eqpmdcmem -n EQPMDCMEM
start eqpmdcslvtcp -n EQPMDCSLVTCP -p 5020

Remove the two files from tls\com when the sample is removed. See skill equipment, task modbus-station.md.

Monitoring processes (optional)

monitoring/ holds the lines to add to the setup files in %TLS_ROOT_PATH%\tls\sup\ so that intcpumon, intdskmon, inttcpmon, intmon and intspawn write into the SYSTEM items. These change the system's own setup files: back the files up first and restore them after testing. See the system-management skill, task monitoring-processes.md.

Planned additions

Phase Adds
6 Template items, a class with attributes/prompts, objects that create items
8 Alarm settings on sample items
9 More storage groups (scan/time, aggregation)
10 A display and symbol
11 A report

Rules

  • Test systems only; invented names only, no real plant or customer data.
  • Keep the load order: sections → template items → classes (compiled) → objects → other items → storage groups → items in storage groups (IM 36K10J10 §5.6). Keep remove.cmd in reverse order.