task version source status
Change a class that already has objects (compile and reset) R1.03 IM 36K10L10-01EN §4 (Reset class); IM 36K10P11-01EN §2.3, §10.4; practiced with CI-Eng-Sample class CIENG_TANK 2026-09-30 verified

Change a class that has objects

Objects keep running the old compiled code until their class is reset (verified). A reset restarts every object of the class; by the manual, ONCE trigger groups fire again. Items the objects created were kept, with their values (verified).

1. New source and compile

dssqld -m with the class name, COMPILE 1 and the new METHOD:

@FIELDS
NAME,COMPILE,METHOD

@CLASS_DF
"CIENG_TANK",1,@"
CLASS CIENG_TANK;
  …
ENDCLASS CIENG_TANK;
"@

Errors 0 = compiled. On a compile error the old code stays; see load-class-object.md for reading the error listing.

Export the class (load-class-object.md §2): after the compile RESET_REQUIRED = 1 and OBJECTS_RESET = 0 of OBJECTS n. Verified: the object still printed the old text.

2. Reset the class

Works — opcdbg, Classes, action 8 Reset class: class name, node (0 = this node), file for a reset report (empty = none; this prompt is not in the manual):

printf '2\n8\n<CLASS>\n0\n\n-1\n-1\n' | timeout 30 opcdbg 0

(Bash. Interactively, type the same answers.) Keep the time-out: opcdbg repeats its last prompt forever when the input runs out.

Afterwards RESET_REQUIRED = 0 and the object used the new code at once (verified).

Also works — Engineering Module: Configuration › I/O processing › Classes › right-click the class › Reset. The Class - reset window shows Reset required / Extended reset required, options Force extended reset and Abort after first failure, progress (reset n of m, failed) and a reset report; click Reset (verified by the user 2026-10-01: 1 of 1 object reset, RESET_REQUIRED 0). This window is the front end of dataset CLASS_RESET_COMMAND.

Does not work (verified 2026-09-30, ISS-028):

  • dssqld -m with NAME,RESET = "<class>",1 (also with RESET_NODE = the host node name): accepted with 0 errors but nothing happens.
  • dssqld -m on OBJECT_DF with RESET 1: refused with OPC-E-OBJ_RSTREQ, The class needs to be reset first.
  • CLASS_RESET_COMMAND (system-wide reset, fields RESET, GENERATE_REPORT, PROGRESS, OBJECTS_RESET …): the dataset allows only read and update, dssqld -e returns no record, dssqld -m gives Not found, dssqld -i is refused (DSS-E-NO_AUTH). Verified 2026-10-01.

3. Changing prompts or signals

Only a change in the method bodies was practiced. When the class prolog changes (new signals, prompts, attributes, created items), check EXTENDED_RESET_REQUIRED in CLASS_DF after compiling; what an extended reset does was not tested. The safe way is to recreate the objects (remove, load) — note that removing an object deletes the items it created, with their history links.