| data-access | CI Server R1.03 ACCESS Service: OPC UA, OPC DA, OPC A&E and ODBC. Use when the user wants to connect CI Server to an OPC UA server (OPC UA client line, station, subscription, points, certificates, node IDs, browse), let another application read CI Server data over OPC UA, OPC DA or OPC A&E (CI Server as OPC server, OPC visible / read / write, port 34493, endpoints, security policy, trusting client certificates, UaExpert), check why an OPC connection fails (BadCertificateUntrusted, BadSecurityChecksFailed, item stays NOT INIT), configure DCOM or DCOM tunnelling for OPC Classic, use ODBC / SimbaClient / SQL on datasets, or check the ODBC server (odbsrv, port 1583, SSL certificate), or copy item values and timestamps into Microsoft SQL Server with RDBMS data exposure (dbc.sup, DEM_CONNECTION, DBCSND, DBCDEM, DATA_EXPOSURE_DF, data exposure aggregation interval AGG_INTERVAL, ITEM_VALUES, SQL login, DSS-E-FLT_SYN_ERR). Sources IM 36K10L45-01EN, IM 36K10E20-01EN, IM 36K10G10-01EN ch. 10. |
Data access: OPC, ODBC and RDBMS data exposure (R1.03; RDBMS exposure tested in R1.05 only)
Background: knowledge/manuals/IM36K10L45-01EN.md (ODBC, OPC DA/A&E/UA client and server,
setup files), IM36K10E20-01EN.md (Engineering Module forms, certificates, PubSub). Equipment
lines/stations/points in general: skill equipment.
Rules:
- Run
system-checkfirst; follow the user's chosen way of working. - Trusting certificates is the user's decision. Show the certificate (folder, file name, common name) and let the user trust it (Engineering Module or moving the file); do not move certificate files yourself.
- Making items OPC visible / writable exposes them to every OPC client on the network: only with the user's approval, and prefer read-only.
- Never connect a CI Server OPC DA or A&E client to the same node's (or a DURM-connected node's) DA/A&E server: deadlock (manual §5.3). The OPC UA loopback is fine.
- Changing
opxsys.sup,opxuas.sup,odbsrv.suporServerConfig.xmlneeds admin rights and a restart: hand it to the user (skillportal-setup, taskchange-setup-file.md). - The same applies to
dbc.sup(RDBMS data exposure). SQL Server changes (mixed mode, logins, jobs) are on another system: only with the user's and the SQL Server owner's agreement.
| Task | File | Status |
|---|---|---|
| OPC UA client to an OPC UA server (sample: loopback to CI Server's own server): line, station, subscription, points, certificate exchange, node IDs, browse via dataset | tasks/opcua-client.md |
verified |
| Make CI Server data available to OPC clients (OPC visible / Read / Write); CI Server OPC UA server endpoints, node IDs, certificates | tasks/opcua-client.md §1, §5 |
verified (UA); DA/A&E from docs |
| Read-only checks: ACCESS processes, ports, OPC UA server config and PKI, ODBC server state | tasks/access-checks.md |
verified |
| OPC DA / A&E client and server, DCOM, DCOM tunnelling | L45 summary §3–§5 | from docs (DA loopback not allowed) |
| ODBC with SimbaClient | L45 summary §1 | from docs; ODBC server not running on the test system (ISS-008) |
| OPC UA alarms (external alarms), methods, PubSub | L45 §6, E20 §2–§4 | from docs |
RDBMS data exposure to SQL Server: SQL login, dbc.sup DEM_CONNECTION, DATA_EXPOSURE_DF (filter syntax), item aggregation interval, checks, table behaviour, SQL-side retention |
tasks/rdbms-exposure.md |
tested in R1.05 only (ITEM_VALUES); ITEM_HISTORY / ITEM_INPUTS not tested |