New knowledge/r105-verification.md lists the R1.05 functions not available on the test server (not tested) and the read-only steps prepared for the user to verify on the server or in the GUI (eqpdbg, setup_check.ps1, Engineering Module forms) plus the CI-Eng-Sample load decision. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
4.1 KiB
R1.05 verification checklist
Two kinds of R1.05 checks are open after the read-only re-check of 2026-10-08:
- Not tested: the function is not available on the R1.05 test server, so it cannot be tested there at all. The content stays "from docs" and is marked not tested with the reason. Nothing to do until a suitable system exists.
- Awaiting user verification: Claude could not run the step itself (refused as a remote
command, needs an administrator, needs the GUI). Claude prepared the steps and expected
results below; the user runs them on the server or in the GUI and sends the output or a
screenshot, and Claude records the result in the task file and in
progress.md.
All steps below are read-only: they open forms or print information and save nothing. Close every form with Cancel.
Not tested on the R1.05 test server
| Area | Reason | Where marked |
|---|---|---|
IT Security Tool (version 2.0 / 3.0), CIX_ groups, CTM_PROCESS, LAPS, GPO import |
Tool not installed; Windows Server 2025 is not supported by the tool | skill installation-security, C10/C30 summaries |
| Vnet/IP drivers, VAGW Bossd | No Vnet/IP card; not supported on Server 2025 | skill installation-security, C10 summary |
Upgrade from R1.03/R1.04 with the automatic configuration merge (jupgutl, -c argument) |
Fresh R1.05 install, no upgrade to observe; an upgrade test needs a separate machine | C10 summary, ISS-086 |
| CI Server with PRM | No PRM | C10 summary, ISS-090 |
IEC 60870-5-104 and IEC 61850 (EQT managers, report control blocks, eqtdbg, eqtfrcscn) |
No device and no EQT line on the server | skill equipment, L40/L41 summaries, ISS-076–079 |
OPC A&E OPXAES_DIR_ALM, OPC UA PubSub, imported information model |
Needs another client/server or extra server instances | skill data-access, ISS-085 |
Awaiting user verification
V1. eqpdbg main info (skill equipment, L40 summary §3)
On the R1.05 test server, in a normal command prompt:
eqpdbg 0 EQPMDC
Type 1 (Get main info), Enter, read the output, then -1 (Exit). Expected: line type 107,
the Modbus line(s) attached, scan interval (tick) in ms, number of slaves, line load %.
Do not choose any other action number. Send a screenshot of the output.
V2. Setup check script (skill installation-security, task setup-check.md)
Copy tools/setup_check.ps1 from this repo to a scratch folder on the server, run it in an
elevated Windows PowerShell, then delete the copy:
powershell -NoProfile -ExecutionPolicy Bypass -File setup_check.ps1
Expected (from the one-by-one checks of 2026-10-08): CI Server 1.05.00 OK; Windows Server 2025
Datacenter shown as not in the list; DIFF for firewall domain profile, Defender, automatic
updates, defrag / component cleanup, page file, .NET 3.5, missing CIX_ groups; CHECK lines
for IT security. Send the result table (screenshot or text).
V3. Engineering Module forms (skill data-access)
In the Engineering Module on the server (log on as a user with engineering rights), open each form below, take a screenshot, and close it with Cancel:
- Tools › OPC UA Information Model Mapper: the mapper window opens (shows New Mapping).
- Authorisation › Users, any user: the Add API Key function exists (do not create a key).
- An OPC UA client point form (New on an OPC UA station is enough to see it, then Cancel): the checkbox Read additional node information exists.
- An OPC UA client method form: fields for node ID type, Options tab (parent object node ID) and Arguments tab; no process-area field.
If no OPC UA client line exists on the server, steps 3–4 need one: skip them and say so.
V4. Needs a decision first: CI-Eng-Sample on the R1.05 test server
The sample tasks (Modbus mirror station, OPC UA loopback, items, alarms …) can only be
re-tested on R1.05 by loading CI-Eng-Sample (all names CIENG*) onto the shared server. It
adds records and starts extra equipment processes (EQPCIENG on port 5020), but touches no
other project's records. Load only after the user approves; otherwise these tasks stay
"verified on R1.03, files checked identical on R1.05".