name: data-access
|
||
description: >-
|
||
CI Server R1.03 ACCESS Service: OPC UA, OPC DA, OPC A&E and ODBC. Use when the user wants to
|
||
connect CI Server to an OPC UA server (OPC UA client line, station, subscription, points,
|
||
certificates, node IDs, browse), let another application read CI Server data over OPC UA, OPC
|
||
DA or OPC A&E (CI Server as OPC server, OPC visible / read / write, port 34493, endpoints,
|
||
security policy, trusting client certificates, UaExpert), check why an OPC connection fails
|
||
(BadCertificateUntrusted, BadSecurityChecksFailed, item stays NOT INIT), configure DCOM or DCOM
|
||
tunnelling for OPC Classic, use ODBC / SimbaClient / SQL on datasets, or check the ODBC server
|
||
(odbsrv, port 1583, SSL certificate), or copy item values and timestamps into Microsoft SQL
|
||
Server with RDBMS data exposure (dbc.sup, DEM_CONNECTION, DBCSND, DBCDEM, DATA_EXPOSURE_DF,
|
||
data exposure aggregation interval AGG_INTERVAL, ITEM_VALUES, SQL login, DSS-E-FLT_SYN_ERR).
|
||
Sources IM 36K10L45-01EN, IM 36K10E20-01EN, IM 36K10G10-01EN ch. 10.
|
||
---
|
||
|
||
# Data access: OPC, ODBC and RDBMS data exposure (R1.03; RDBMS exposure tested in R1.05 only)
|
||
|
||
Background: `knowledge/manuals/IM36K10L45-01EN.md` (ODBC, OPC DA/A&E/UA client and server,
|
||
setup files), `IM36K10E20-01EN.md` (Engineering Module forms, certificates, PubSub). Equipment
|
||
lines/stations/points in general: skill `equipment`.
|
||
|
||
Rules:
|
||
- Run `system-check` first; follow the user's chosen way of working.
|
||
- **Trusting certificates is the user's decision.** Show the certificate (folder, file name,
|
||
common name) and let the user trust it (Engineering Module or moving the file); do not move
|
||
certificate files yourself.
|
||
- Making items OPC visible / writable exposes them to every OPC client on the network: only
|
||
with the user's approval, and prefer read-only.
|
||
- Never connect a CI Server OPC **DA or A&E** client to the same node's (or a DURM-connected
|
||
node's) DA/A&E server: deadlock (manual §5.3). The OPC **UA** loopback is fine.
|
||
- Changing `opxsys.sup`, `opxuas.sup`, `odbsrv.sup` or `ServerConfig.xml` needs admin rights and
|
||
a restart: hand it to the user (skill `portal-setup`, task `change-setup-file.md`).
|
||
- The same applies to `dbc.sup` (RDBMS data exposure). SQL Server changes (mixed mode, logins,
|
||
jobs) are on another system: only with the user's and the SQL Server owner's agreement.
|
||
|
||
| Task | File | Status |
|
||
|---|---|---|
|
||
| OPC UA client to an OPC UA server (sample: loopback to CI Server's own server): line, station, subscription, points, certificate exchange, node IDs, browse via dataset | `tasks/opcua-client.md` | verified |
|
||
| Make CI Server data available to OPC clients (OPC visible / Read / Write); CI Server OPC UA server endpoints, node IDs, certificates | `tasks/opcua-client.md` §1, §5 | verified (UA); DA/A&E from docs |
|
||
| Read-only checks: ACCESS processes, ports, OPC UA server config and PKI, ODBC server state | `tasks/access-checks.md` | verified |
|
||
| OPC DA / A&E client and server, DCOM, DCOM tunnelling | L45 summary §3–§5 | from docs (DA loopback not allowed) |
|
||
| ODBC with SimbaClient | L45 summary §1 | from docs; ODBC server not running on the test system (ISS-008) |
|
||
| OPC UA alarms (external alarms), methods, PubSub | L45 §6, E20 §2–§4 | from docs |
|
||
| RDBMS data exposure to SQL Server: SQL login, `dbc.sup` `DEM_CONNECTION`, `DATA_EXPOSURE_DF` (filter syntax), item aggregation interval, checks, table behaviour, SQL-side retention | `tasks/rdbms-exposure.md` | tested in R1.05 only (`ITEM_VALUES`); `ITEM_HISTORY` / `ITEM_INPUTS` not tested |
|